| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : Garrison Engineer Kapurthala 2nd Call Name of Work : Repair/Replacement / maintenance of LED Security lights and switchgear and allied works at Mil Stn Kapurthala under GE Kapurthala Contract No : GE KPT- /2025-26 Bidder Name : SCHEDULE OF WORKS(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # S.No Description of work Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Attending of day to day maintenance LED street/security/Gate light/Post top lantern/High mast light fixed at up to 16 mtr height of any make complaints received through telephone or in person and reactification of defects installed on street light poles 9/11 mtr long, building walls, roof by bringing down the fittings on ground or in position including replacement of LED lights, Driver, flexible wire, reflector etc including cleaning of glass/acrylic cover for clear reflection of light, replacement of old unserviceable street light fittings with new fittings etc as required to make the light fitting functional Vehicle, ladder, tools and takes as required at site for repair/for making light fittings functional shall be provided by the contractor at his own cost and arrangement.Note : (i) Light fitting, cable, flexible wire and LED drive if required to be replaced in repair shall be measured and paid separetely under relevant item of this BOQ for supply and fixing in replacement. (ii) contractor manpower should be daily recieve a complaints at complaint cell at 9.00 AM by JE E/M and report after completion of complaints and handover a complaint slip as record of complaints with user signature.(iii) Old retrived material shall be deposited in AGE E/M yard and will be given to contractor after completion of contract. (vi) . Quantity of material by contractor shall be decided by Engineer in charge based on requirement. Note: Recovery @ 120/- per hour of the complaints is not being attended within six hours from intimation by rep of E/M subdivision through or telephonic/digital/ written complaints. |
| 3 | Taking down old unserviceable any type fitting and S&F Energy saving LED street light fitting 35 Watt, 230 V AC outdoor type, with PDC Aluminium body and toughened glass visor fitted in frame, separately driver compartment provided, secondary optical lens for superior light distribution efficiency >105Lm/W, CCT 5700K, IP66, input voltage from 120-270 V power factor above 0.95 complete with driver, lamp, suitable for 40/50 mm dia bracket with impact resistant complete all as specified and directed by Engineer-in-Charge. Make : BAJAJ/CROMPTON/HAVELLS |
| 4 | Complete all as per item no 2 above but for 60 watt |
| 5 | Complete all as per item no 2 above but for 70 watt |
| 6 | Taking down old unserviceable any type fitting and supply and fixing LED flood light 70 watt 230 V AC outdoor type, not less than 105 lumens/Watt , toughned glass with high pressure die cast aluminum hosing, thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp all as specified and directed by Engineer-in-Charge. Make : BAJAJ/CROMPTON/HAVELLS |
| 7 | Complete all as per item no 5 above but for 100 watt |
| 8 | Complete all as per item no 5 above but for 170 watt |
| 9 | Taking down old unserviceable any type of post top lantern fitting and supply and fixing decorative LED post top lantern 20 watt powder coated aluminium die cast and spun aluminium body with clear/opel diffuser suitable for Landscape lighting available in 5700K CCT IP65 input voltage from 120-270 V power factor above 0.95 complete fitting including PCC platform MS column pipe 1.50 Mtr length, all accessories all as specified and directed by Engineer-in-Charge. Make : Havells/ Philips/Bajaj |
| 10 | Taking down old unsv garden light and supply and fixing LED decorative Bollard garden lights suitable for 10 Watt IP65 10 watt in inverted pyramid tropod type LED Bollard with soft 360 light, resistant to corrosion with better optic for uniform distribution complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable complete all as specified and as directed by Engr-in-Charge. Make : Havells/ Philips/Bajaj |
| 11 | Supply, fixing and installation of Octagonal poles hot dip galvanized steel (IS 5986 Gr. Fe 510) Octagonal pole 7.0 mtr long, top top die 70 mm botom dia 130 mm having thickness 3 mm having door operating of size 500 mm above ground level with CI Base plate of size 240x240x16mm having PCD 220 mm foundation J bolts M20 x 70 mm (530 + 130 of J) nuts and screwes and having hot dip galvanized double plain arm bracket 1000 mm overhang on both side with 48.3 mm outer dia pipe of thickness 3.2 mm fixed on top with bolts and necessary earth work RCC/PCC work for the foundation of pole, including necessary form work and fare finish to exposed surfaces without using extra cement etc. Complete all as specified. Make : BAJAJ/CROMPTON/HAVELLS |
| 12 | M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate for fdn of poles, stay etc. |
| 13 | M&L for PCC 1:2:4 type B2 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement. |
| 14 | Taking out old unserviceable underground cable from trenches/ floors/road/wall /pipe/ pole LT cable of any size/ description. |
| 15 | Supplying, laying, jointing and testing under ground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 vols grade cross sectional area 16 Sqmm 4 core laid in trences, in floor, in duct, through pipes or along the pole including taking down old one complete all as specified and directed by Engr-in-Charge. Make : Grandlay/HAVELLS/Polycab |
| 16 | All As per item No 14 but cross sectional area 10 Sqmm 4 core. |
| 17 | M&L for excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for foundation of poles/ stays/ laying of cables etc and getting out including trimming of sides of trenches complete all as specified and directed. |
| 18 | M&L for returning, filling the soft / loose soil including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer complete all as specified and directed. |
| 19 | M&L for removing of surplus excavated soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 20 | M&L for sand cushioning to under ground cable with a layer of sand 8 cm thick before laying of cable and 15 cm thick after laying of cable complete all as specified and directed. |
| 21 | M&L for brick protection using old size sub class ‘B’ bricks, laid flat, dry adjacent to each other laid length wise perpendicular to the axis of cable complete all as specified and directed. |
| 22 | M&L for steel tubing GI light grade 50 mm dia for cable protection, passing under road/floor or for fixing to poles/walls all as specified and directed. |
| 23 | M&L for steel tubing GI light grade 40 mm dia for cable protection, passing under road/floor or for fixing to poles/walls all as specified and directed. |
| 24 | M&L for preparation of old painted surface of Steel tubuler Street light poles and applying two coats of synthetic Aluminium paint from top to bottom including Light breakets complete all as specified and as directed. |
| 25 | Labour only for cutting/pruning of tree branches 1.5 mtr all around the LT overhead lines of span n.exc 70 mtr and around the pole obstruction the overhead line & removing the branches to distance n.exc 50 mtr to be the entire satisfaction of Engineer-in-charge, |
| 26 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polythylene including coupler & Bend with smoooth inernal and profiled external surface for non pressue under ground cable complete all as specified. |
| 27 | Supply and fixing aluminum thimbles/Lugs crimping type of size 16 to 25 Sq mm |
| 28 | Supply & Fix junction box factory made weather proof size 250mmx200mmx 100mm made of 16 gauge steel sheet powder coated inculded 25mmx6mm aluminium TPN bus bars & 01 MCB 10 Amps for controlled one No's of LED Lights complete all as specifed & directred |
| 29 | Supply and fix in replacement of Time light distribution board analog Time switch 230 volt three phase of 16 Amps rating with contactor fixed inside steel enclosure box and fixed to pole/LT Panel including MCB/MCCB, selector switch, RYB indicator, cable glands, clamps, nuts, bolts and washers etc complete all as specified and directed. |
| 30 | Supply and fix, Analog time switch 3 module of capacity 32A, suitable for LT panel 415V, complete all as specfied and directed. |
| 31 | Supply and fix, modular contactor 3 module of capacity 16-40A alongwith add on block suitable for LT panel 415V, complete all as specfied and directed. |
| 32 | Taking out old unserviceable Service wire and supply and fixing Service wire Al Conductor Weather Proof 6 Sqmm 2 core complete all as specified and directed. |
| 33 | Taking out old unserviceable Service wire and supply and fixing Service wire Al Conductor Weather Proof 10 Sqmm 2 core complete all as specified and directed. |
| 34 | Taking out old unserviceable Service wire and supply and fixing Service wire copper conductor Weather Proof 2.5 Sqmm 2 core in and including 15 mm dia pvc conduit with clamps, nuts, bolts and srew complete all as specified and directed. |
| 35 | S&F LED street/flood Light Driver 35-70 Watt |
| 36 | S&F LED street/flood Light Driver 100-170 Watt |
| 37 | Supply fabricating erecting LT panel outdoor type CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts 50 cycles, AC supply factory made fully compart mentalized made out of 3.00 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of abgle iron/flat iron frame work/ support required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioning with including the following :- (a) Aluminium bus bar of capacity 600 Amps for phase and 300 Amps for Neutral. (b) Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three)Incoming : (i) MCCB TPN 250 Amps, 36 KA 415 Volts 4 pole (Thermal Magnatic and microprocessor release- 01 No Outgoing : (i) MCCB 4 pole 63 Amps 36 KA, 415 Volts (adjustable thermal and magnatic type70% to 100%)- 04 No (ii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover (1co) total 28 programs. |
| 38 | M & L for earthing complete with galvanized iron or steel or steel earth plate electrode of size 60cmx60cmx6.3mm thick buried directly in ground, vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI Strip of size 32x6 mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe light grade 20 mm bore for watering including providing funnel and wire mesh GI frame and 10 cm thick suitably reinforced RCC pit cover PCC chamber pit with PCC 1:3:6 type C2 using 40mm graded stone aggregates complete including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in plate No 5 of SRR-1991 Part-1 . |
| 39 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. Total in Figures 0.0 23 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |