| 1 | Supply & Fixing and testing of LT cable 1100 volts grade, XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) ISI Marked with aluminium conductor suitable for earthed system of following sizes in trenches, on poles and in ducts complete all as specified and directed by Engr in charge. |
| 2 | -- do-- all as per ser item No 1.00 above but size 120 sq mm 3½ core |
| 3 | -- do-- all as per ser item No 1.00 above but size 95 sq mm 3½ core |
| 4 | -- do-- all as per ser item No 1.00 above but size 70 sq mm 3½ core |
| 5 | -- do-- all as per ser item No 1.00 above but size 50 sq mm 3½ core |
| 6 | -- do-- all as per ser item No 1.00 above but size 16 sq mm 4 core |
| 7 | -- do-- all as per ser item No 1.00 above but size 10 sq mm 4 core |
| 8 | -- do-- all as per ser item No 1.00 above but size 10 sq mm 2 coreNote for Sr No 01 to 08 : Excavation & Earthwork, Protection pipe etc shall be measured and paid seprately under relevent items of this Schedule. |
| 9 | Excavation in trenches n.exc 1.5 mtr in depth and not exceeding 1.5 Mtr wide for laying of cable/ pipe etc and getting out in any type of soil complete all as specified and directed. |
| 10 | -- do-- all as per ser item No 9.00 above but exceeding 1.5 mtr & not exceeding 3 mtr in depth. |
| 11 | Returning filling in trenches excavated soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick each layer as in soil complete all as specified nad directed.. |
| 12 | Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified nad directed. |
| 13 | Supply & laying of HDPE DWC pipe ISI mark of outer dia 110 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-ChargeMake : Supreme / Infra / Astral/Prince/jain irrigation |
| 14 | Supply & laying of HDPE DWC pipe ISI mark of outer dia 63 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-ChargeMake : Supreme / Infra / Astral/Prince/jain irrigation |
| 15 | S&F GI Tubes of size 40mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed. |
| 16 | S&F GI Tubes of size 50mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed. |
| 17 | S&F GI Tubes,of size 80mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed. |
| 18 | M&L for road cutting upto 300mm deep and 200mm wide for crossing GI pipe line through road including making good the disturbed surface by filling mass concrete( 1:2:4) etc complete all as specified and directed by Engineer-in-Charge.Note : Rate of mass concrete is included in quated rate. |
| 19 | Demolation of u/s cement concrete in coping etc complete all as specified and directed by Engineer-in-Charge. |
| 20 | M&L for PCC(1:2:4) type C-2 using 20mm grade stone aggregates for coping and similar work including necessary form work complete all as specified and directed. |
| 21 | S&F in replacement PVC Junction box of size 200x175x100mm, IP 66 with hinged door including locking arrangment and MCB SP 6 Amp with necessary nut,bolt etc and including TPN aluminium bus bar mounted on insulators with suitable holes to provide incoming and outgoing LT cables and street light MCB complete all as specified and directed |
| 22 | Supply and fix in replacement wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, Three core cable in surface/recessed as required 2x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire (From PVC Junction box to Security light)Note : Excavation & Earthwork, Protection pipe etc shall be measured and paid seprately under relevent items of this Schedule. |
| 23 | Supply & fix in replacement, installation, testing and commissioining factory made LT feeder pillar panel in replacement CPRI approved, size of panel as per CPRI Specification, double door floor mounted outdoor type, as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 400 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape, mounted on insulators etc with RYB indicater, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated,locking should be screw type, mechanical type,inter locking, should have danger notice for 415 volt, AC, mounted on 50 x 50 x 6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainless steel glands Nuts & Bolts complete all as specifid and directed. (Main Panel) Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II ( DMR 319/320) |
| 24 | (i) Incoming MCCB 4P, 200 Amp, 25 KA,thermal and magnetic adjustable -01 No (Ics = 100% Icu) |
| 25 | (ii) Outgoing -Al bus bar 400 Amps |
| 26 | (iii) Outgoing MCCB ,4P, 63 Amps,16 KA- 5 Nos |
| 27 | (iv) Digital voltmeter & Ammeter with necessary CTs |
| 28 | (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm |
| 29 | (vi) Phase indicating LED lamps (R-Y-B) -01 set |
| 30 | ( vii) Spare chamber for MCCBs - 01 Nos |
| 31 | Supply & fix in replacement, installation, testing and commissioining factory made LT feeder pillar panel in replacement CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 400 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater, internal wiring with suitable size of copper wire,panel should be dust proof, vermin proof, powder coated, locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volt, AC, mounted on 50 x 50 x 6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainless steel glands Nuts & Bolts complete all as specifid and directed. (Main Panel) Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II (DMR canteen) |
| 32 | (i) Incoming MCCB 4P, 200 Amp, 25 KA,thermal and magnetic adjustable -01 No (Ics = 100% Icu) |
| 33 | (ii) Outgoing -Al bus bar 400 Amps |
| 34 | (iii) Outgoing MCCB 4P 100 Amp, 16 KA -02Nos ( Ics = 100% Icu) |
| 35 | (iv) Outgoing MCCB ,4P, 63 Amps,16 KA- 1 Nos |
| 36 | (iv) Digital voltmeter & Ammeter with necessary CTs |
| 37 | (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm |
| 38 | (vi) Phase indicating LED lamps (R-Y-B) -01 set |
| 39 | (vii) Spare chamber for MCCBs - 01 Nos |
| 40 | Supply & fix in replacement, installation, testing and commissioining factory made LT feeder pillar panel in replacement CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type, as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled, insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater, internal wiring with suitable size of copper wire,panel should be dust proof, vermin proof, powder coated,locking should be screw type,mechanical type, inter locking, should have danger notice for 415 volt, AC, mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainless steel glands Nuts & Bolts complete all as specifid and directed.(Main Panel)Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II ( Eletronic wing) |
| 41 | (i) Incoming MCCB 4P, 160 Amp, 25 KA, thermal and magnetic adjustable -01 No (Ics = 100% Icu) |
| 42 | (ii) Outgoing -Al bus bar 300 Amps |
| 43 | (iii) Outgoing MCCB 4P 63 Amp, 16 KA -04Nos ( Ics = 100% Icu) |
| 44 | (iv) Outgoing MCB TPN 63 Amps,16 KA- 1 Nos |
| 45 | (iv) Digital voltmeter & Ammeter with necessary CTs |
| 46 | (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm |
| 47 | (vi) Phase indicating LED lamps (R-Y-B) -01 set |
| 48 | (vii) Spare chamber for MCCBs - 01 Nos |
| 49 | Supply & fix in replacement for fabrication of bus bar chamber of size not less than 600 x 600 x 450 mm suitable for 415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Incoming MCCB : 200 AMps ,4P,25 KA Busbar Capacity : 300 AMps mounted on DMC/ porcelain insulator support with RYB indicatorOutgoing : one MCB/MCCB mounted chanel slotted 500 mm long |
| 50 | Supply & fix in replacement for fabrication of bus bar chamber of size not less than 600 x 600 x450 mm suitable for 415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Incoming MCCB : 63 AMps ,4P,16 KA Busbar Capacity : 160 AMps mounted on DMC/ porcelain insulator support with RYB indicatorOutgoing : 08 Nos mounted chanel slotted 500 mm long Please Enable Macros to View BoQ information |
| 51 | Supply & fix in replacement for fabrication of bus bar chamber of size not less than 600 x 600 x450 mm suitable for 415 volts 3 phase 4 wire system , outdoor type, double door, with pedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Incoming MCCB : 63 AMps ,4P,16 KA Busbar Capacity : 160 AMps mounted on DMC/ porcelain insulator support with RYB indicatorOutgoing : 08 Nos mounted chanel slotted 500 mm long Please Enable Macros to View BoQ information |