| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc.complete all as specified and directed. |
| 2 | M&L for Point wiring complete with 1100 volts grade PVC insulated unsheathed FRLS cable of copper conductor, multi stranded of size 1.5 sqmm, single core, in and including new rigid non-metallic PVC concealed conduit /surface conduit with all accessories if require such as bends, reducers, spacers, saddles, junction boxes, Bakelite sheets, wooden rectangular boards/round blocks (for housing lamp holder and light fittings etc) and MS pressed steel/cast iron sunken boxes( minimum thickness 1.2mm) of suitable size for mounting switches/bell pushes/sockets/fan regulator etc covered with new 3 mm thick laminated Bakelite sheet top cover including continuous earth wire of size 1.5 Sqmm unsheathed stranded copper conductor with green PVC insulation connected to common earth dolly complete all as specified and directed for the followings :- (a) One light/fan/Bell Point controlled by one single pole one way switch 6 Amp. |
| 3 | (b) One 3 pin socket outlet 5/6 Amp on the same board controlled by one single pole one way switch 6A complete all as specified and directed. |
| 4 | (c) One 5/6 Amp socket outlet independent controlled by one single pole 6 Amp switch complete all as specified and directed. |
| 5 | All as per Srl Item No 2 here-in-before but one three pin 6/16 Amps socket outlet on the independent board with 2.5 Sqmm PVC insulated copper conductor and 2.5 sqmm copper conductor for continuous earthing complete all as specified and directed. |
| 6 | All as per item No 3 above but existing conduit and existing MS pressed steel/ cast iron box complete all as specified and directed.(a) One light point/fan/bell point controlled by one single pole one way switch 6 Amp. |
| 7 | (b) One light point controlled by two 2-way switches 6 A, with cables 1.5 sq. mm size complete all as specified and directed. |
| 8 | (c) One 6 Amps socket outlet independent controlled by one single pole 6 Amp switch complete all as specified and directed. |
| 9 | S&F new ms pressed steel/cast iron sunken boxes rectangular block in replacement of old rusted sunken box. The MS Pressed Steel/ CI Box shall be galvanised or painted black with two coats of black bituminous paints or any other paint as indicated .The MS pressed steel/cast iron sunken boxes should be suitable for mounting of normal/modular switches, sockets, fan regulator etc and the item rate quoted also including making good the disturbed surfaces to match with the existing surface. The new MS pressed steel/cast iron sunken boxes suold be of following sizes with suitable thickness as per IS Code complete all as specified and directed.(a) 8\\" x 5\\" and Suitable for Main switch board |
| 10 | (c) All as per Srl Item No 9 but of size 5\\"x5\\" and Suitable for 05 Amp Independent board. |
| 11 | S&F bakelite sheet hylam 3mm thick of white top fixed with cup washers, machine screws on new/existing MS Shuken box including removing existing switch/ switch sockets/ bell push etc and refixing the only serviceable switchs/socket by making slots on new sheet complete all as specified and directed.(a) Min size 8'' x 5\\" and Suitable for 15 Amp Independent board. |
| 12 | (c) All as per Srl item No 11 but of Min size 5'' x 5\\" and Suitable for 05 Amp Independent board. |
| 13 | S&F Switch piano flush type 6 Amps, one way complete all as specified and directed. |
| 14 | S&F Switch piano flush type 16 Amps, one way complete all as specified and directed. |
| 15 | S&F Socket outlet 3 pin, 6 Amps, piano flush type complete all as specified and directed. |
| 16 | S&F Socket outlet, 2 in 1, 6 pin 6 and 16 Amps piano flush type complete all as specified and directed. |
| 17 | S&F Switch piano flush type 6 Amps, two way complete all as specified and directed. |
| 18 | S&F in repair Ceiling rose surface type, PVC/polycarbonate ,isolated, bakelite 65 x 50mm, 3 terminals complete all as specified and directed. |
| 19 | S&F in lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed. |
| 20 | S&F in repair stepped type electronic fan regulater (Socket/switch type), flush type on the existing phenolic laminated sheet etc. as reqd complete all as specifed and directed. |
| 21 | S&F in repair bell push piano flush type 6 Amps single pole complete all as specified and directed. |
| 22 | S&F in repair bell AC 230 volts single pole complete all as specified and directed. |
| 23 | S&F in repair sheet metal enclouser DB's 8 way double door factory made powder coated out of CRCA mild steel sheet 1.2 mm thick wih metallic painting white series, 240 volts 200 Amps rated enameled bus bar 8 way dust and vermin proof suitable for incorporation of MCBs duly concealed in wall and making good to distrubed surface and colour matching complete all as specified and directed. |
| 24 | S&F in repair MCB single pole neutral (SPN) 240 volts, 20 to 40 Amps, 10 KA complete all as specified and directed. |
| 25 | S&F in repair MCB single pole (SP) 240 volts, 40 Amps, 10 KA 'B' Series complete all as specified and directed. |
| 26 | complete all as specified and directed. MCB single pole, 240 volts, 6 to 32 Ampere, rupturing capacity 10 KA, ‘B’ curve type complete all as specified and directed. |
| 27 | S&F MCB TPN 415 volts 63 Amps, 10 KA breaking capacity complete all as specified and directed. |
| 28 | S&F in repair LED tube light fitting 1 X 20 W decorative ultra slim linear LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient 230V, complete with all accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed.Makes Cat Part No LHEXBLP7PN1W020 of make - Havells or techno-commercially equivalent in approved makes. |
| 29 | S&F exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers complete all as specified and directed. |
| 30 | S&F exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300mm complete all as specified and directed. |
| 31 | S&F in repair sub main wiring of 6 sqmm PVC insulated unsheathed FRLS cable multistranded copper conductor with earth wire of 6.0 sqmm PVC insulated unsheathed FRLS cable multistranded copper conductor including PVC conduit pipe 25 mm dia all as specified and directed.Note:-Two run of single core 6 sqmm cable and one run single core 6.0 sqmm cable for earth wire and including conduit pipe 25 mm dia shall measured as one length). |
| 32 | All as per Srl item No 31 here-in-before but 4 Sqmm submain wiring complete all as specified and directed. |
| 33 | S&F sheet steel metal enclosure single pole & neutral with a 2 pin and earth plug and socket complete with one single pole MCB SP 20 Amp, 240 volts complete all as specified and directed. |
| 34 | S&F Efficient Neo BLDC inverter technology ceiling fans copper winding and without remort complete with blades, down rods, and accessories, 230 V, 1200 mm sweep. Min air delivery 215 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed.Note:-Contractor shall submit sample of ceiling fan before make/sample approval for demonstration purpose. The submitted sample shall be tested with the existing regulatorto verify compatibility,smooth operation and satisfactory speed variation at all regulator position. |
| 35 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated luminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 1.5 sq. mm 3 core nominal cross section in service connections complete all as specified and directed. |
| 36 | S&F sheet metal enclouser double door factory made powder coated out of CRCA mild steel sheet 1.2 mm thick wih metallic painting white series TPN DBs (Vertical type)fitted with ABS frame and 415 volts 200 Amps rated enameled bus bar 4 way dust and vermin proof ssuitable for incorporation of MCBs duly concealed in wall and making good to distrubed surface and colour matching complete all as specified and directed. |
| 37 | S&F MCCB 100 Amps, 415 volts, 16 KA, 4 Pole complete all as specified and directed. |
| 38 | S&F in repair MCB single pole (SP) 240 volts, 40 Amps, 10 KA 'B' Series complete all as specified. (For TPN use) complete all as specified and directed. |
| 39 | S&F MCB, Single Pole and neutral 240 V, 32 Amps 10 KA 'B' series complete all as specified and directed. |
| 40 | M&L Earthing complete with galvanized steel plate elecrode of size 60 cm x 60cm & 6.0 mm thick burried directly in ground vertically to a depth not less than 2.5 mtr below the ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt, earth lead GI wire of 4mm dia (8 SWG) by means of bolts , nuts, check nuts and washers of galvanised iron with thimbles. The other end of GI earth wire is connected to main switch board and protected by light grade GI pipe of 15 mm bore. provision of 20mm bore light grade GI pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horrizontally to the earth pit. Cement concrete chamber of PCC ( 1:3:6 ) type C-2 using 40 mm graded stone aggregate.The chamber shall be constructed one metre away from edge of earth pit. 50 mm thick pre cast cover of cement conrete (1:2:4) type B-1 using 20 mm graded stone aggregate, excavation in soft / loose soil, returning filling and removal of surplus soil to a distance of 50 mm as directed and shown in Electrical Plate No- 3 of SSR Part-1 (2009) complete all as specified and directed. Please Enable Macros to View BoQ information |