| 1 | Supply & fixing of 9 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 155 mm and base plate 12mm thik) having 3mm thikness with Double arm bracket (1 Mtr length each ) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. |
| 2 | S/F of 63 kVA 11/0.433 KV outdoor type 3 phase conventional 50 C/S aluminium wound Delta/Star DYN 11, ONAN cooled transformer with of circuit tap changer having range +5% to -10% with complete fitting an accessories confirming to IS 11804 Star rating with latest amendements including first filling of oil complete in all respect as per UPPCL Approved make & Specifications as per direction of engineer incharge. |
| 3 | Supply of STP 11M IS:410 SP-55 botom galvenised complete in all respect. |
| 4 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 meter and upto 12.00 meter.[8177*0.789=6451.65*(111/110)=6510.30] |
| 5 | Supplying of 50 mm X 8 mm M.S. flat iron pole top bracket/ cross arm for single 11/22/33 KV over head line conductor complete with fixing clamps, bolts, nuts and washers drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required. [615*0.789 =485.23* (111/110) =489.64] |
| 6 | Supplying of two lengths of channel iron 75mm * 40mm * 6mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50mm * 6mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. [5125*0.789 =4043.625* (111/110) =4080.385] |
| 7 | S/Fixing of 11 KV pin insulator with pin including Labour T&P complete in all respect as per direction of E/I. |
| 8 | X/Fixing of 11 KV TPMO complete in all respect, as per direction by E/I. |
| 9 | S/Fixing of 11 KV Fuse sets (drop out) with clamps complete in all respect as per direction by E/I. |
| 10 | S/Fixing of 11 KV Lighting Arrestor set (03 Nos.) complete in respect, as per direction by E/I. |
| 11 | S/F of 2.54 mtr long 20 mm dia MS Earth Rod with 6 SWG GI earth wire, nut, bolt & washer etc. complete in all respect. |
| 12 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. [6855*0.789 =5408.595* (111/110) =5457.764] |
| 13 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I.pipe from earth electrode including connection with G.I. nut, bolt,spring, washer excavation and re-filling etc. as required. [706*0.789 =557.034* (111/110) =562.097] |
| 14 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. [70*0.789 =55.23* (111/110) =55.732] |
| 15 | Trenchless boring with HDPE Pipe by Machine Technology including Labour, T&P, cost of Pipe and all required meterial suitable for laying of LT upto 95 Sqmım size with proper completion of work as per direction of E/I. |
| 16 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63mm Dia (OD-63mm & ID-51 mm nomial) [247*0.789=194.89*(111/110)=196.65] |
| 17 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer Incharge,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Size: 25 sq.mm 3-1/2 core |
| 18 | Street Light work:Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 110 to 130 Watt. Confirming to IP 66 Protection complete in all respect. CAT-AAA |
| 19 | Supply and fixing 40 A TPN capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. |
| 20 | S/L of 10 Sqmm x 2 core Unarmoured LT 1100 Volt Aluminium Conductor twin flate cable Complete. Please Enable Macros to View BoQ information |