| 1 | Supply and Laying of 3 core AL conductor XLPE (Cross linked polyethylene ) insulated pvc bedded ,galvanised flat steel strip armoured cables confirming to I.S7098 . 11 kv grade at a depth of 900 mm belowground level over acushion of 100 mm thick fine rever sand all around and protected with well burnt bricks on side and on top put across as directed by engineer in charge complete in all respect . 120 sqmm 3 core |
| 2 | Earthing with G.I earth plate 600 mm x 600mmx 6 mm thick including accessories,and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr long etc with charcoal/coke and salt as required. |
| 3 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 120 sqmm size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 5 | wiring for circuit/submain wiring along with earth wire with the 2x4sq.mm + 1x4sq.mm FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit complete in all respect. |
| 6 | Supplying and fixing 8 way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. (But without MCB/RCCB/lsolator) |
| 7 | Supplying and fixing 40 A rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. |
| 9 | S/F Heavy Duty Exhaust fan 900 RPM respects.Make- Havells or Equivalent |
| 10 | 11KV Switch Gear Panel : |
| 11 | SITC of 11KV, VCB Panel. (3 Incoming + 3 Outgoing) 26.3kA indoor type metal clad floor mounted vermin proof horizontal drawout fully interlocked Horizontal isolation vacuum circuit breaker panel board fabricated out of minimum 2mm thick CRCA sheet as per specifications. The panel shall be complete with all accessories / fitting / wiring like insulated copper Bus bar, cable termination boxes suitable for up to 3C x 300 Sq mm XLPE armoured, aluminium conductor cable for outgoing feeder, foundation bolts etc. The Bus Bar of Panel shall be suitably Rated High Cinductive Copper Bus Bar. The Job shall be completed as per site requirement and as specified below. Make- L&T / Schneider or Equivalent |
| 12 | Incoming : 3 set (Each Consisting of) |
| 13 | (3) Nos. 11KV 800 Amps. Electrically/ manually operated draw out type vacuum circuit breaker complete with trip free spring charged closing mechanism, necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc. |
| 14 | (3) Set 11kV Cast resin 2 core Dual Ratio CTs for Metering, Cl. 5P10 for Protection. |
| 15 | (3) Nos. digital type multifunction |
| 16 | (3) Set of phase indication lamps with SP MCB for protection (Red, Yellow and Blue). |
| 17 | (3) Set of Red/ Green indicating lamp for close and open position. |
| 18 | (3) Nos. amber indicating lamp for auto trip. |
| 19 | (3) Nos. clear indicating lamp for trip circuit healthy. |
| 20 | (3) Nos. white indicating lamp for spring charged. |
| 21 | (3) Set of 3 O/C + 1No E/F Numerical Relay IDMT with High set (51+51N/50+50N) |
| 22 | (3) Nos. Master Trip Relay (86) |
| 23 | (3) Nos. Local/ Remote Selector Switch |
| 24 | (3) Nos. TNC Switch |
| 25 | (3) Set 3 Phase Potential Transformer 11KV/√3/110/√3 50VA burden |
| 26 | Auxiliary switch/relay, anti-pumping relay Trip circuit supervision relay and other controlrelays etc. as per requirements. |
| 27 | Busbar : |
| 28 | (3) Set of 800 Amp. TP copper busbar with heat shrinkable sleeved. |
| 29 | Outgoing : 3 Set (Each Consisting of) |
| 30 | 3) Set 11KV 630 Amps. 350MVA Electrically/ manually operated draw out type vacuum circuit breaker complete with trip free spring charged closing mechanism, necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc. |
| 31 | (3) Set 11kV Cast resin 2 core Dual Ratio CTs for Metering, Cl. 5P10 for Protection. |
| 32 | (3) Set digital type ammeter Cl.1 |
| 33 | (3) Set of 3 O/C + 1No E/F Numerical Relay IDMT with High set (51+51N/50+50N) |
| 34 | (3) Set of 3 Element 24V DC Aux. Relay with S/R flag for tripping of Transformer Fault ie. OTI, WTI & Buchholz Tripping (27A/B/C) |
| 35 | (3) Set of 3 Element 24V DC Aux. Relay with S/R flag for Alarm of Transformer Fault ie. OTI, WTI & Buchholz Alarm (28A/B/S) |
| 36 | (3) Set of 8 Stage 24V DC Annunciator with built in test/Accept/ Reset Push Button along with 24V DC Hooter. |
| 37 | (3) Set Master Trip Relay (86) |
| 38 | (3) Set TNC Switch |
| 39 | Auxiliary switch/relay, anti-pumping relay, Trip circuit supervision relay and other control relays etc. as per requirements. |
| 40 | Power Pack : |
| 41 | One (1) Set 230V A.C, / 24V DC, 12AH Battery Backup, Power Pack to operate at least 3Nos. Operation without AC Supply. |
| 42 | Providing and fixing 50 mm x 6 mm G.I strip at 0.50 mtr below ground as strip earth electrode including connection termination with nut bolt spring washer etc as required |
| 43 | Supply and fixing of insulated Rubber matting 11kv/class B.Size(1x2mtrx2.5 mm) |
| 44 | Supply and fixing of PVC sheet electric shock treatment chart. |
| 45 | Supply and fixing of M.S Danger plate Size not less than 12\\"x9\\". |
| 46 | Supply and fixing of 4.5 kg capacity co2 type Fire extinguisher clyinder. |
| 47 | Supply and fixing of fire bucket,round bottom made of GI Sheet having 9-11 lit capacity duly painted as per fire brigade design supported on hanging chained and lock, initially filled with river local sand . |
| 48 | Charges for dismantling of 630A 11KV VCB existing panel including removing connection, pulling out 120 sqmm HT cables from panel and shifting of Panel to new location with help of hydra, Labour T&P, etc. The whole work is to be executed as per direction of E-in-charge. |
| 49 | Providing of temporary arrangement of existing supply to be available for engineers of present step up during dismantling of cable till required commissioning of H T Panel properly. By temporary Installation of bare bus bar to some other location. Temporary installed bus bar and providing of same also supervision of temporary arrangement 24 hours the job shall be completed including cost of D G Rent, labour, T&P, Tools etc. |
| 50 | Supply & Fabrication of MS Chequred Plate. Made of Outer Frame Angle and Supported MS Angle Frame 50x50x06 mm For Chequred Plate of Size 06 mm Thick Complete in All Respect. |
| 51 | SITC of armourd copper control cable 2.5* 6 Includings Lugs , Gland etc. Complete in all respect |
| 52 | Add : GST @18% Please Enable Macros to View BoQ information |