| 1 | Supply, install and testing split Air Conditioner of 2.0 TR capacity inverter type 5 star rating with indoor and outdoor units (copper condenser coil, copper cooling coil and evaporator, smart AC with hybrid jet inverter technology including copper pipe which has also blue fin technology condenser coils and fins, including required length of copper tubing and cables for connecting indoor and outdoor units) complete with cordless remote control unit, with inverter rotary compressor with inbuilt air ionizer and dual PM 2.5 HD filter with anti viral technology for better indoor air quality including inlet and outlet copper pipe and all accessories required as per site requirement all as specified and directed by Engineer-in-Charge.Note: Rate quoted is deemed to be inclusive of the following:- (i) Drilling hole on the brick wall to facilitate routing of Copper pipe, drain pipe and cable from indoor unit to outdoor unit.(ii) Sealing the hole from outside, after installation, with white cement and painting complete to match with existing.(iii) Pressure testing, cooling performance check and product demonstration(iv) Installation to be done by authorized dealer only. |
| 2 | Material and labour for Modular socket with 25 Amp SP MCB complete all as specified and directed by Engr-in charge. |
| 3 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5.0 KVA complete all as specified and directed by Engineer-in-Charge. |
| 4 | Material and labour sub main wiring with two single core 1100 V grade conforming to IS 694 PVC insulated unsheathed cables 4 Sq mm FRLSH multi stranded copper conductor drawn through and incl 25 mm dia non metallic PVC rigid conduit and conduit accessories concealed on walls/floors/ceiling etc with an earth wire of one run 4 sqmm FRLSH copper wire earth continuity conductor complete all as specified and directed by Engr-in-Charge. Note : Three runs of 4 sqmm cable with one run of PVC conduit shall be measured as one run. |
| 5 | Supply and fixing of GI powder coated brackets , for fixing of split AC's including grouting with suitable size fasteners complete all as specified and directed. |
| 6 | Supply and fixing Copper pipe 1/2\\" dia with foam insulation including connecting complete all as specified and directed. |
| 7 | Supply and fixing Copper pipe 1/4 \\" mm dia with foam insulation including connecting complete all as specified and directed. |
| 8 | Supply and fix Drain pipe PVC from indoor unit (at any floor) to ground floor level and is to be fixed with necessary clamps complete all as specified and directed. |
| 9 | Supply and fix four core wire 1.5 sqmm interconnecting cable IDU - ODU complete all as specified and directed. |
| 10 | Supply and Fix MCB SP 240 V, 6A to 32 Amps 10KA, 50Hz 'C' curve complete all as specified and directed. |
| 11 | Supply and Fix Sheet metal enclosures Vertical TPN DB 8 way suitable for MCCB incomer, double door, TPN, AC 415 Volts complete all as specified and directed. |
| 12 | Supply and fix MCCB TP, AC 415 Volts 160 Amps 36KA,Adjustable type 50Hz 'C' curve complete all as specified and directed. |
| 13 | Supply and Fix MCB TPN, AC 415 Volts 40 to 100 Amps 10KA, 50Hz 'C' curve complete all as specified and directed. |
| 14 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of the following sizes complete all as specified and directed. Note: Excavation ,returning filling and removal shall be measured and paid for separately. |
| 15 | 3.5 core 95 sqmm |
| 16 | 4 core 25 sqmm |
| 17 | Excavation in trenches not exc. 1.5 m wide and not exc.1.5 m deep for laying of cable, pipe and for erecting of steel tubular swaged pole etc, and getting out in hard/dense soil complete all as specified and directed by Engr-in-charge |
| 18 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed by Engr-in-charge |
| 19 | Removing excavated material not exc 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting points in soil all as directed by Engineer-in-Charge. |
| 20 | Supply,Laying,jointing and testing of HDPE DWC Pipe 90 mm OD Conforming to IS 16098 SN-8 Class complete rubber ring joints complete all specified and as directed by Engr-in Charge. |
| 21 | Supply and laying of 50 mm steel tubing galvanised light grade complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply, install and testing split Air Conditioner of 1.5 TR capacity inverter type 5 star rating with indoor and outdoor units (copper condenser coil, copper cooling coil and evaporator, smart AC with hybrid jet inverter technology including copper pipe which has also blue fin technology condenser coils and fins, including required length of copper tubing and cables for connecting indoor and outdoor units) with cordless remote control unit, inverter rotary compressor, inbuilt air ioniser and dual PM 2.5 HD filter with anti viral technology for better indoor air quality including inlet and outlet copper pipe and all accessories required as per site requirement all as specified and directed by Engineer-in-Charge.Note: Rate quoted is deemed to be inclusive of the following:- (i) Drain Pipe UPVC with the insulation from indoor unit ( at any floor) to ground floor level and is to be fixed with necessary clamps complete.(ii) Sealing the hole from outside, after installation, with white cement and painting complete to match with existing.(iii) Pressure testing, cooling performance check and product demonstration.(iv) 4 core cable of any required length for connecting indoor and outdoor unit.(v) During installation the copper pipe to be in vacuum condition.(vi) Installation to be done by authorized dealer only with GI powder brackets. |
| 23 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 150 V to 285 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4.0 KVA complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply and fix Sheet metal enclosures, double door, MCB DB, 4 way, SPN, AC 240 Volts complete all as specified and as directed. |
| 25 | Supply and Fix MCB SPN 240 V, 32 Amps 10KA, 50Hz 'C' curve complete all as specified and directed. |
| 26 | Supply, installation, testing and commissioning of Portable Air Conditioner through insulated GI ducting , 3.5 TR, 12 KW , 2 HP, 42000 Btu/Hr, 3 phase 415 Volt Ac, operating Temperature 15-45c, Refrigerant type 410a/R407c with maximum air flow, Noise should be lower than 60 db, providing and fixing 250 mm dia circular GI air distribution ducting, spiral-wound, fabricated from 24 gauge (0.6 mm) GI sheet, complete with slip/flanged joints, rubber gaskets, sealant, supports and 19 mm thick nitrile rubber insulation (Class-O), suitable for handling 1850 CFM air volume, including all fittings, accessories, testing and commissioning, as per IS:655 / SMACNA standards, Aluminum powder-coated supply air grille/diffuser of approved design and size ,Providing RCC pedestal hard standing for portable AC unit at Ground Floor, minimum 150 mm height above finished floor level, including anti-vibration rubber pads, complete with fixing accessories all as directed by Engr-in-charge. |
| 27 | Supply and fixing three phase metal clad Plug and socket of rating 63 Amp with TPN MCB 63 Amp with enclosure complete all as directed by Engr-in-charge. |
| 28 | Material and labour for of sub-main wiring with four runs of 1100 V grade FRLSH PVC insulated & unsheathed 10.0 Sqmm single core multi stranded copper conductor cable alongwith one run of 10.0 Sqmm 1100 V grade PVC insulated & unsheathed single core multi stranded copper conductor cable for earth continuity conductor connected to common earth dolly, drawn through Concealed/Surface PVC conduit complete all as specified and as directed by the Engr-in-Charge. Note : (i) Five runs of 10.0 Sqmm cable and conduit shall be measured as one length. |
| 29 | Material and labour for Earthing with Copper Earth Plate Electrode 600X600X3.15mm, buried directly in Ground vertically at a depth not less than 2.25 METRE below Ground Level with the Top Edge of Earth Plate at a depth not less than 1.50 METRE below Ground Level connected to copper strip of size 25x3mm as Earth Lead by means of Bolts, Nuts, Check Nuts and Washers of copper , Earth Plate Electrode surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, GI Strip protected with and including 40mm bore GI Light Grade Pipe upto 1.0METRE above the Floor Level of the Building including PCC Pit in Cement Concrete (1:3:6) type C1 (20mm Graded Stone Aggregate) and RCC Cover of size 450X450X50mm in RCC (1:2:4) type B1 (20mm Graded Stone Aggregate) reinforced with GI Wire Mesh, Funnel, 20mm bore Medium Grade GI Watering Pipe, necessary Excavation in Soft/Loose Soil, returning, filling in and removal of surplus Spoil up to a distance of 50.00 METRE and all as shown in Electrical Plate No. 5 of MES Schedule Part-I and Testing on completion complete all as specified and directed by the Engineer-in-Charge. |
| 30 | Supply and fix Copper strip 25 x 3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground |
| 31 | Excavation in trenches not exc. 1.5 m wide and not exc.1.5 m deep for laying of cable etc, and getting out in soft/loose soil complete all as specified and directed by Engr-in-charge |
| 32 | Supply and laying of HDPE DWC Pipe 50 mm OD Conforming to IS 16098 SN-8 Class complete all specified and as directed by Engr-in Charge. Please Enable Macros to View BoQ information |