| 1 | Surface excavation not exceeding 30cm deep and averaging 15cm deep and getting out in soft/loose soil complete all as specified and directed. |
| 2 | Excavation in trenches not exc. 1.5 m wide and not exc.1.5 m deep for foundation, shafts, wells etc not exc 10 sqm on plan and getting out in soft/loose soil complete all as specified and directed. |
| 3 | Material and labour for sand filling under floors or in foundation including watering and consolidation complete all as specified and directed. |
| 4 | Material and labour for machine pressed precast interlocking paver block 60mm thick made of M-35 grade concrete in any shape with grey cement and pigment complete all as specified and as directed. |
| 5 | Material and labour providing cement concrete type B1 1:2:4 (20mm graded aggregate) copings,kneelers,apex stones, bed plates, kerbs, water troughs and the like including weathering slightly rounded or chamfered angles and throating complete all as specified and as directed. |
| 6 | Material and labour for cement concrete type D2 1:4:8 using 40 mm graded aggregate as in foundation, filling and mass concrete complete all as specified and as directed. |
| 7 | Material and labour for brick work with old size fly ash bricks built in CM 1:6, straight or curved on plan exc 6m mean radius on plan complete all as specified and directed. |
| 8 | Material and labour for rendering 15 mm thick in CM 1:4 on fair face of brick work or concrete surfaces and finished even and smooth without using extra cement complete all as specified and as directed. |
| 9 | Material and labour for Hardcore using broken stone or boulders of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified and as directed. |
| 10 | Material and labour 100mm thick PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in sub base of floors complete all as specified and directed. |
| 11 | Material and labour for 50mm thick PCC 1:2:4 type B1(using 20 mm graded aggregate) finished even and fair without using extra cement complete all as specified and as directed |
| 12 | Material and labour for forming construction joint 30x10mm filled with sealing compound grade 'A' complete all as specified and directed0. |
| 13 | Returning filling in trenches including spreading levelling watering and well ramming in layers not exc.25 cms in soil complete all as specified and as directed. |
| 14 | Removing excavated material / soil to a distance n.exc 50m away and depositing where as directed at a level n.exc 1.5m above the starting point, complete all as specified and as directed. |
| 15 | Supply and fixing 110mm dia PVC (SWR) pipe and single socketed in any length with rubber ring joint laid in trenches or in floor etc complete all as specified and as directed. |
| 16 | Material and labour for mild steel TMT bars 10 mm dia., and over cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia., or securing with clips complete all as specified and as directed. |
| 17 | All as per item No 16 above but 6 to 8mm dia complete |
| 18 | Flat rough finished formwork to sides of concrete foundations, footings, bases of columns complete all as specified and as directed. |
| 19 | Material and labour RCC Nominal Mix 1:2:4 (20 graded aggregates) as in Foundations, foundation beams; plinth beams; bases for columns complete all as specified and directed. |
| 20 | Supply and fixing Mild steel bolts purpose made with hexagonal or square head one end and screwed the other, or screwed both ends; each screwed end to be fitted with washers and one hexagonal or square nut. exc 30cm long complete all as specified and directed. |
| 21 | Supply and fixing Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment Fe-410 W(Gde E-250) quality B complete all as specified and directed. |
| 22 | Supply and fixing Rolled sections as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates Fe 410-W (Gde-E-250) quality A complete all as specified and directed. |
| 23 | Supply and fixing Membrane Tensile Translucent /Translucido Precontraint 902S2 weight 950 gm/Sqm Tensile Strength 420/400 daN/5cm Tear strength 55/50 daN adhension 12 daN/5Cm, Surface treatment Top/back both side S2 PVDF/PVDF Finished, Yarn High Tenacity Polyster 1100 Dtex Low wick Treatment for anticappillarity Any different colours all as approved by Engr-in-Charge |
| 24 | Material and labour for preparation of new steel surface of any description over 10cm in girth and applying two coats of synthetic enamel paint over a coat of rex oxide primer complete all as specified. |
| 25 | Material and labour for point wiring with two single core 1100 V grade FRLS-H conforming to IS-694 PVC insulated unsheathed cables of size 1.5 Sq mm multi-stranded Copper conductor drawn through and including rigid PVC conduit and conduit accessories fixed on surface including breaking of walls and making good to disturbed surfaces in wall/roof/ceiling where required complete an earth wire of PVC cable 1.5 Sqmm multi stranded copper conductor and connected to all metal boxes and common earth dolly for one light/bell/fan controlled by one number one way switch for 5 Amps complete all as specified and directed . |
| 26 | All as per item No 25 above nut for One 3 pin 5 Amps switch socket combination on independent board |
| 27 | Material and labour for ceiling rose surface Bakelite, 65x50mm, two to three terminals, complete all as specified and as directed by the Engineer-in-Charge |
| 28 | Supply and fix modular switch 1 way 6 Amps 1 Module complete all as specified and as directed |
| 29 | Supply and fix modular socket 6A 5 pin combined 2 Module complete all as specified and as directed |
| 30 | Supply and fix LED tube light fitting 4 feet 20W, 230V,energy efficiently comprising of extruded PVC housing with inbuilt driver and C diffuser including connecting up with three core flexiblecopper conductor cable of suitable size from ceiling rose complete all as specified and directed |
| 31 | Material and labour for sub main wiring with PVC insulated two runs of single core 1.5 sqmm FRLSH copper conductor and one run of 1.5 sqmm multistranded copper conductor as earth continuity conductor drawn through and including 25 mm dia heavy duty non metallic rigid PVC conduit and accessories complete all as specified and as directed.Note : (i) Two run 1.5 Sqmm of single core, one run of 1.5 sqmm earth conductor and one run of PVC conduit will be measured as one RM |
| 32 | Supply and fixing door bottom sealing strip/guard 750mm to 1200mm long with 25mm wide aluminum strip and 25mm wide Nylon brush fixed at bottom of door for prevention of snakes/insects as per sample complete all as specified and directed. |
| 33 | Supply and fixing Lighting Arrester working on the principle of ESE Early Streamer Emission Technology made of stainless steel body to be mounted on 05 mtrs height from roof of the building complete all as directed by Engg-in-charge. Make-RPS/SG Power or Equivalent. |
| 34 | Supply and fixing heavy duty GI post of 5mtr height for mounting of lightening arrester with GI wire, PCC work, Nut & bolts etc complete all as directed by Engg-in-charge. Make-RPS/SG Power or Equivalent. |
| 35 | Supply and fixing Strike Counter six digit complete all as directed by Engg-in-Charge. Make-RPS/SG Power or Equivalent. |
| 36 | Material and labour for earthling with Copper Earth Plate Electrode 600X600X3.15mm, buried directly in Ground vertically at a depth not less than 2.25 METRE below Ground Level with the Top Edge of Earth Plate at a depth not less than 1.50 METRE below Ground Level connected to copper strip of size 25x3mm as Earth Lead by means of Bolts, Nuts, Check Nuts and Washers of copper , Earth Plate Electrode surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, GI Strip protected with and including 40mm bore GI Light Grade Pipe up to 1.0METRE above the Floor Level of the Building where Main Switch/DB situated including PCC Pit in Cement Concrete (1:3:6) type C1 (20mm Graded Stone Aggregate) and RCC Cover of size 450X450X50mm in RCC (1:2:4) type B1 (20mm Graded Stone Aggregate) reinforced with and including 8.0mm dia TMT Bars @ 100mm centre to centre both ways, GI Wire Mesh, Funnel, 20mm bore Medium Grade GI Watering Pipe, necessary Excavation in Soft/Loose Soil, returning, filling in and removal of surplus Spoil upto a distance of 50.00 METRE and all as shown in Electrical Plate No. 5 of MES Schedule Part-I and Testing on completion including Taking down unserviceable Earthling ,complete all as specified and directed by the Engineer-in-Charge. |
| 37 | Supply and fix Copper strip 32x6 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as directed by Engg-in-charge. |
| 38 | Supply and fix Copper strip 25x3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as directed by Engg-in-charge. |
| 39 | Supply and fixing GI pipe light grade 50mm with all fitting and fixed to walls and ceilings or laid in floors complete all as specified and as directed. |
| 40 | Supply, installation, testing and commissioning of 5 KW capacity, 415 Volts, 50 Hz, 3-phase Exhaust Blower, axial flow, to be mounted on existing duct with any required modification by mounting heavy duty frame made with angle channel and angle iron with suitable connection and inlet & outlet wire mesh bird guard screen, vibration isolators, including wooden packing charges, complete all as specified and as directed. |
| 41 | Supply and fix MCB 16 -32 Amps TPN, 415 Volts, 50Hz 10 KA rupturing capacity 'C' curve on the existing Starter panel by cutting the suitable hole , fixing the MCB mounting channel complete all as specified and as directed. |
| 42 | Supply and fix DOL starter suitable for 3-phase, 415 Volts, 50 Hz AC supply, capacity up to 16 Amps, complete with contactors, thermal overload relay, timer and necessary control accessories, enclosed in sheet metal powder coated enclosure, duly pre-wired and tested at site, The starter should me mounted on the existing angle iron frame by completing any required modification, adding required amount of angle iron, welding at site, complete all as specified and as directed be Engg -in-charge. |
| 43 | Supply, Installation, Testing & Commissioning of 5 kVA IGBT based digitally controlled double conversion True On-line UPS- 1 Phase input & 1 Phase output with built-in Isolation Transformer on the inverter output suitable for Plasma Cutting Machine, Exide / Amara Raja make SMF batteries of 12V, 26AH x 16 Nos to provide 30 Mins backup with provision of Battery/UPS rack, Battery Interlink, UPS to battery cable complete all as directed by engg-in-charge. |
| 44 | Material and labour sub main wiring with two single core 1100 V grade conforming to IS 694 PVC insulated unsheathed cables 10 Sq mm FRLSH multi stranded copper conductor drawn through and incl 25 mm dia non metallic PVC rigid conduit and conduit accessories fixed on walls/roof/floors/ceiling etc with an earth wire of one run 10 sqmm FRLSH copper wire earth continuity conductor etc complete all as specified and directed by Engr-in-Charge. Note : Three runs of 10 sqmm cable with one run of PVC conduit shall be measured as one run. |
| 45 | Supply and Fix MCB DP, AC 240 Volts 32 Amps 10KA, 50Hz 'C' curve complete all as specified and directed. |
| 46 | Supply and Fix sheet metal enclosures for DBs single pole 4 way 240 V with neutral bus bar 200 Amps double door type with locking arrangement complete all as specified and directed. |
| 47 | Material and labour sub main wiring with four runs of single core 1100 V grade conforming to IS 694 PVC insulated unsheathed cables 4 Sq mm FRLSH multi stranded copper conductor drawn through and incl 25 mm dia non metallic PVC rigid conduit and conduit accessories fixed on walls/roof/floors/ceiling etc with an earth wire of one run 4 sqmm FRLSH copper wire earth continuity conductor etc complete all as specified and directed by Engr-in-Charge. Note : Five runs of 4 sqmm cable with one run of PVC conduit shall be measured as one run. Please Enable Macros to View BoQ information |