Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Civil Work |
| 2 | OVERHEAD TANKS |
| 3 | Investigate the soil bearing capacity by only nationalised institute and If net safe allowable bearing capacity is found to be equivalent or more than 8 t/m2, the design of OHT will be based on 8 t/m2 capacity. However, in case the net safe allowable bearing capacity is found to be below 8 t/m2, then the design of OHT will be based on the actual bearing capacity. Design, Supply of all materials labour T&P etc. required for complete construction of R.C.C. Over Head Tank of following capacity and staging as specified in bid document as per direction of Engineer-in-charge. The key feature, but not limited to, pertaing to design and construction of OHT are as follows: 1. The finished floor level of OHT shall be min 0.3m above the finished ground level of the campus. 2. Soil investigation and bearing capacity. 3. Structural design and drawing confirming to IS: 456, IS: 3370, IS: 1893, IS: 875 & Other relevant IS Code. 4. Grade of concrete M30 for water retaining structure and concrete grade for other components shall not be less then M25. 5. Saprete two column based RCC stair case of width minimum 1m. 6. 1m wide R.C.C. M30 balcony, SS ladder inside the tank from top dome to bottom dome shall be made of 50x50x6 mm angle section with hand rails of 20mm SS pipes. The grade shall be SS 316. 7. Railing with 20mm dia medium class G.I.pipe (in 3 rows) on both sides of stair case, supported on 50x50x6mm M.S. angle section, spaced at intervals not more than 1.5m. 8. Proper ventilator at top dome in circular shape of 1.2 m dia. |
| 4 | 9. Food Grade epoxy coating of FOSROC / Ciba-Geigy or reputed brand on inside surface area of water container after testing of water tightness, two coat of apex painting over one coat of primer of approved colour after finishing of RCC surface with grinder. 10. Repairs of pin holes, unevenness of all concrete surface. 11. Ultra Sonic Water level indicator fabricated with sensor connecting to automation 12. Lightening conductor as per I.S.S.2309 or its latest amendments of latest electricity rules, consisting of proper elevation rod with 5 or more fork points as prescribed in ISS 2309‐1969 and ISS 3013‐1966. 13. C.I. manhole of min 60x60cm size with locking arrangement. 14. Supply, fixing, jointing of D.I.D/F Pipes of appropriate size with D.I.D/F specials conforming to IS 8329/2000 as vertical pipes for inlet, outlet, overflow and washout with Bell Mouth as per latest / relevant I.S. specifications with all jointing materials for proper completion of work. 15. Construction of 120mm thick RCC floor in 1:1.5:3 with cement, coarse sand, approved stone grit and reinforcement t@8mm dia @250mm c/c both way over 100mm thick PCC 1:4:8. 16. Supply, fixing of D/F Sliuce Valve with D.I.D/F specials conforming to IS 8329/2000 as vertical pipes for inlet, outlet, overflow and washout as per latest / relevant I.S. specifications with all jointing materials for proper completion of work. 17. Construction of washout / overflow chamber and chambers for sluice / butter fly valves as per departmental type design and drawing. |
| 5 | 18 . Supply of 200 mm dia PVC pipe for disposal of water from washout chamber to suitable point outside the water works compound. 19 .MS steel box type enclosure of at the entrance of the staircase having locking arrangements. 20 .The C.I (D/F)pipe dimensions for inlet,outlet,washout,overflow will be decided as per site requirements. For bidding purpose, bearing capacity of soil shall be considered as 8t/sq.m. Working design shall be based on the SBC determined after soil investigation / 8 tonne/sqm Note :- The bid price of Over Head Tanks is to be submitted considering that the design of over head tank will be done by retired / working Associate proffessor of any IIT and it shall be vetted by a working professor also of IIT and The net safe allowable bearing capacity as 8 t/m2, keeping the minimum foundation depth to be 2.5 m below existing ground level at the site of work. |
| 6 | Construction of R.C.C. Over Head Tank 1200 KL/25 mtr including all Materials, Labours, T & P etc. Complete. For Zone-2 |
| 7 | Construction of R.C.C. Over Head Tank 1300 KL/25 mtr including all Materials, Labours, T & P etc. Complete. For Zone-3 |
| 8 | Construction of R.C.C. Over Head Tank 1300 KL/23 mtr including all Materials, Labours, T & P etc. Complete. For Zone-4 |
| 9 | Construction of R.C.C. Over Head Tank 1100 KL/25 mtr including all Materials, Labours, T & P etc. Complete. For Zone-5 |
| 10 | Construction of R.C.C. Over Head Tank 1200 KL/27 mtr including all Materials, Labours, T & P etc. Complete. For Zone-6 |
| 11 | Construction of R.C.C. Over Head Tank 1200 KL/25 mtr including all Materials, Labours, T & P etc. Complete. For Zone-7 |
| 12 | Construction of R.C.C. Over Head Tank 1600 KL/22 mtr including all Materials, Labours, T & P etc. Complete. For Zone-8 |
| 13 | Construction of R.C.C. Over Head Tank 2200 KL/25 mtr including all Materials, Labours, T & P etc. Complete. For Zone-9 |
| 14 | Construction of R.C.C. Over Head Tank 2400 KL/27 mtr including all Materials, Labours, T & P etc. Complete. For Zone-10 |
| 15 | C.W.R. CUM - PUMP HOUSE |
| 16 | Supply of all materials, labour and T&P etc. complete for the construction of Ground RCC CWR of Different capacities & with 1.00m wide P.C.C. appron alround with 20 cm semi circular P.C.C. drain M.S. ladder with hand rails out side and inside the tank body proper ventilators at top, water level indicator, Lightening conductor as per latest I.S.I. or electricity rules, 1150mm dia medium pattern C.I. Manhole cover hinged with locking arrangement fixing and jointing vertical DID/F, pipes, specials and duck foot bents of required size for inlet, outlet fising of outlet sluice valve and wash out sluice valves with all jointing materials for proper completion and other appurtenant works including excavation in all type of soil & in rock etc. painting on exposed water proof cement paint, painting of pepes and ladder with approved anticorrosive paints also including testing of the CWR including carriage of construction materials by truck/ head load etc. upto site of work. |
| 17 | 550 KL, For Zone 10 |
| 18 | Rising Main |
| 19 | Supply of following sizes (D.I.) pipes for rising main/distribution system conforming to latest/relevant I.S. 8329/2000 Specifications with all jointing materials such as specials conforming to latest /relevant I.S. specifications, suitable for D.I pipes, as per IS-1239 /2000 and IS 8329/2000 or their latest amendment including F.O.R. destination and all taxes and insurance etc. with loading, unloading |
| 20 | 200mm dia D I K-9 for Zone-2 |
| 21 | 200mm dia D I K-9 for Zone-3 |
| 22 | 200mm dia D I K-9 for Zone-4 |
| 23 | 200mm dia D I K-9 for Zone-5 |
| 24 | 200mm dia D I K-9 for Zone-6 |
| 25 | 200mm dia D I K-9 for Zone-7 |
| 26 | 150mm dia D I K-9 for Zone-8 |
| 27 | 200mm dia D I K-9 for Zone-9 |
| 28 | 200mm dia D I K-9 for Zone-10 |
| 29 | From CWR to OHT 250mm dia D I K-9 |
| 30 | Excavation of earth in ordinary soil (loam, clay or sand) for pipe line and rising main trenches including lift upto 1.50 m and lead upto 50 m and refilling watering, ramming of the excavated earth into the trench and also disposal of surplus earth upto 50m from the center of the trenches including supply of all material labour, T&P etc complete as per instructions of Engineer -in -charge. |
| 31 | Carting, laying and jointing of the following sizes of pipes into the trenches including cost of all jointing materials, labour and T&P, testing etc. complete. |
| 32 | 200mm dia D I K-9 for Zone-2 |
| 33 | 200mm dia D I K-9 for Zone-3 |
| 34 | 200mm dia D I K-9 for Zone-4 |
| 35 | 200mm dia D I K-9 for Zone-5 |
| 36 | 200mm dia D I K-9 for Zone-6 |
| 37 | 200mm dia D I K-9 for Zone-7 |
| 38 | 150mm dia D I K-9 for Zone-8 |
| 39 | 200mm dia D I K-9 for Zone-9 |
| 40 | 200mm dia D I K-9 for Zone-10 |
| 41 | From CWR to OHT 250mm dia D I K-9 |
| 42 | Dismantling of the following type of road surface for laying of pipe line including sorting out and stacking of serviceable materials and disposal of unserviceable materias. as per instructions of Engineer -in -charge. |
| 43 | B.O.E. surface |
| 44 | Bituminous surface |
| 45 | Interlocking Road |
| 46 | C.C. Road |
| 47 | Permanent re-instatement of the following ty pe of road surface after laying of pipeline including supply of all materials, labour, T&P etc. required for completion of work. it also includes necessary excavation required for preparation of trench for reinstatement of road, disposal of surplus unserviceable material, watering, ramming, cleaning surface for proper completion of the work as per directions of Engineer ‐in ‐charge. |
| 48 | B.O.E. surface |
| 49 | Bituminous surface |
| 50 | Interlocking Road |
| 51 | C.C. Road |
| 52 | Sluice Valve PN 1.0 dia 200mm ( By Pass Arrangement) (Motor Operated Actuators with Sluice Valve) |
| 53 | Sluice Valve PN 1.0 dia 150 mm ( By Pass Arrangement) (Motor Operated Actuators with Sluice Valve) |
| 54 | Sluice valve chamber (Massonary Type) - dia 150mm & 200 mm |
| 55 | Design and construct Thrust Block made in R.C.C. with cement coarse sand & 20 mm gauge stone ballast in proportion of 1:1.5:3 for pipe line including supply of MS reinforcement wrought to required shape as necessary its bending fixing & binding the same with 0.50 mm thick binding wire in position & necessary centering & shuttering including curing and supply of all materials labour T & P etc. required for proper completion of the work and as per specifications for RCC work as per instructions of Engineer -in -charge. |
| 56 | Distribution System |
| 57 | Supply of following sizes (pipes for rising main/distribution system conforming to latest/relevant I.S. 8329/2000 Specifications conforming to latest /relevant I.S. specifications, suitable for D.I pipes and I.S. 4984/2016 Specifications conforming to latest /relevant I.S. specifications, suitable for HDPE pipes including F.O.R. destination and all taxes and insurance etc. with loading, unloading but excluding the cost of trenches).all complete as per instructions of Engineer -in -charge. |
| 58 | 110 mm dia HDPE PN-6 PE-100 |
| 59 | 140 mm dia HDPE PN-6 PE-100 |
| 60 | 160 mm dia HDPE PN-6 PE-100 |
| 61 | 200 mm dia DI K-7 |
| 62 | 250 mm dia DI K-7 |
| 63 | 300 mm dia DI K-7 |
| 64 | 350 mm dia DI K-7 |
| 65 | 400 mm dia DI K-7 |
| 66 | 450 mm dia DI K-7 |
| 67 | Supply, carting laying and jointing with fixing in proper position of the following sizes of C.I. Double flanged sluice valves and tail peace as per I.S. 780/1969 class-1 working pressure 10kg/sqcm F.O.R destination including lowering, fixing in position and jointing then with pipe line etc comlete including all jointing material and specials of following sizes. |
| 68 | 400 mm |
| 69 | 350 mm |
| 70 | 300 mm |
| 71 | 250 mm |
| 72 | 200 mm |
| 73 | 150 mm |
| 74 | 125 mm |
| 75 | 100 mm |
| 76 | Same as above but for Scour Valve |
| 77 | 80 mm |
| 78 | Supply and installation, testing etc. of single/double ball type air valve conforming to latest/relevent I.S. specifications including all taxes and insurance(including supply of jointing materials and Valve fittings etc complete) as per instructions of Engineer. |
| 79 | 50 mm |
| 80 | Supply and installation of underground sluice valves type fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site including lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with including values and specials, testing etc. complete. |
| 81 | Excavation of earth in ordinary soil (loam, clay or sand) for pipe line and rising main trenches including lift upto 1.50 m and lead upto 50 m and refilling watering, ramming of the excavated earth into the trench and also disposal of surplus earth upto 50m from the center of the trenches including supply of all material labour, T&P etc complete as per instructions of Engineer -in -charge. |
| 82 | Carting from (up to 8 Km) the following sizes of ISI marked DI pipes and specials to the site of working lowering them into trenches and laying true to alignment and gradient including testing of pipe line excluding cutting of pipes etc. for, making of lengths and making of joints. |
| 83 | 110 mm dia HDPE PN-6 PE-100 |
| 84 | 140 mm dia HDPE PN-6 PE-100 |
| 85 | 160 mm dia HDPE PN-6 PE-100 |
| 86 | 200 mm dia DI K-7 |
| 87 | 250 mm dia DI K-7 |
| 88 | 300 mm dia DI K-7 |
| 89 | 350 mm dia DI K-7 |
| 90 | 400 mm dia DI K-7 |
| 91 | 450 mm dia DI K-7 |
| 92 | Provision for following types of Culvert crossing along the alignment of pipe line complete as per instructions of Engineer -in -charge. (casing of pipe is done by concreting) |
| 93 | Crossing of Culvert for laying pipe line including supply and materials labour, T&P etc. complete. |
| 94 | Crossing of Nala/drain for laying pipe line including supply and materials labour, T&P etc. complete. |
| 95 | Crossing of Road for laying pipe line including supply and materials labour, T&P etc. complete. |
| 96 | Through trenchless |
| 97 | Dismantling of the following type of road surface for laying of pipe line including sorting out and stacking of serviceable materials and disposal of unserviceable materias upto a distance of 50 m. as per instructions of Engineer -in -charge. |
| 98 | B.O.E. surface |
| 99 | Bituminous surface |
| 100 | Interlocking Road |
| 101 | C.C. Road |
| 102 | Reinstatement of the following type of road surface with old and new materials including supply of all materials labour T&P etc. required for proper completion of the work as per instructions of Engineer -in -charge. |
| 103 | B.O.E. surface |
| 104 | Bituminous surface (ULBs Road) |
| 105 | Bituminous surface (PWD Road) |
| 106 | Interlocking Road |
| 107 | C.C. Road |
| 108 | Making new House Connection with 20 mm hdpe pipe up to 5m in length in 90-600 mm dia of DI / HDPE Distribution main including dismantling and reinstatement of road, excavation of earth, supply, carting of e-fusion specials, lowering them into trenches, fixing them including bailing out water necessary excavation for connection, G.I. pipe minimum class 2 m, Efusion clamp, water tap ferrule and all other material required heavy duty brass bib cock as per type design . Including all labour, T&P etc. required for proper completion of the works as per design and satisfaction of engineer incharge. |
| 109 | For 90mm to 110mm dia |
| 110 | For 125mm to 160mm dia |
| 111 | For 200mm to 250mm dia |
| 112 | For 300mm dia |
| 113 | For 350mm to 600mm dia |
| 114 | Construction of following type chambers as per department type design and drawing including Heavy duty M.S. Manhole Cover and all materials, labour, T&P etc complete for proper completion of work as per instructions of Engineer -in -charge. |
| 115 | Sluice valve chamber (masonry Type) - dia above 150 mm - 1000 (L) x 1200 (W) x 1300 (H) mm as per departmental drawing |
| 116 | Sluice valve chamber (surface box Type) - dia upto 125 mm as per departmental drawing |
| 117 | Fire Hydrant chamber (750 (L) X 450 (W) X 1000 (H) mm) as per departmental drawing |
| 118 | Air Valve Chamber 350 (L) x 350 (W) x 500 (H) mm as per departmental drawing |
| 119 | Scour Valve Chamber dia upto 200 mm - 1000 (L) x 1200 (W) x 1300 (H) mm as per departmental drawing |
| 120 | Design and construct Thrust Block made in R.C.C. with cement coarse sand & 20 mm gauge stone ballast in proportion of 1:1.5:3 for pipe line including supply of MS reinforcement wrought to required shape as necessary its bending fixing & binding the same with 0.50 mm thick binding wire in position & necessary centering & shuttering including curing and supply of all materials labour T & P etc. required for proper completion of the work and as per specifications for RCC work as per instructions of Engineer -in -charg |
| 121 | Interconnection of proposed new pipeline with old pipe including supply of all materials, labour, T&P bailing out of water etc. required to complete the work. |
| 122 | Construction of Pump House,Boundary wall and site Development |
| 123 | Provide all materials labour T&P etc. complete and construct Pump house size (3.6x3.0x3.0)m Chlorinating room size (2.5x1.8x3.0)m as per departmental type design and drawing and as per the specifications for civil work given in the bid document including supply of all material labour and T&P etc complete as per instructions of Engineer -in - charge. |
| 124 | Zone-2 (Lamhi) |
| 125 | Zone-3 (Madhwa) |
| 126 | Zone-4 (Aidhe) |
| 127 | Zone-5 (Sarsarwa ) |
| 128 | Zone-6 (Lodhan) |
| 129 | Zone-7 (Chhatripur) |
| 130 | Zone-8 (Basdevpur) |
| 131 | Zone-9 (Tarna) |
| 132 | Zone-10 (Pissaur) |
| 133 | Construction of new Master Control station (4.50x3.50)m with lab and Toilet as per departmental type design and drawing, and, as per specifications given in the bid document including supply of all materials, labour T&P etc.for proper completion of work as per instructions of Engineer -in -charge. |
| 134 | Construction of 1.80 m high and 115mm thick boundary wall with 230 mmx230 mm thick pillar made in Brick masonry in 1 cement and 4 sand mortar, the spacing between two pillar should not be more than 3.0 m c/c and the depth of foundation should not be less than 0.60m, at the site of water works as per departmental type design and drawing, and, as per specifications given in the bid document including supply of all materials, labour T&P etc.for proper completion of work as per instructions of Engineer -in -charge. |
| 135 | Supply and fixing of 3.6 m x 1.20 m MS gate along with Fixing 1.2 m for water work including fabrication and supply of steel and construction of bounary wall pillars of size 1.35mx0.23mx0.23m with ornamental brick work 115mm th. around RCC, as per departmental type design and drawing (Drawing No. D-1) and as per specifications laid down in the bid document, including supply of all material, labour,T&P etc.required for proper completion of work as per instructions of Engineer-in-charge. |
| 136 | Construction of Coloured Interlocking road with for approach kerb stones on side for water works, as per departmental type design and drawing and as per specifications laid down in the bid document, including supply of all materials , labour, T&P etc.required for proper completion of work as per instructions of Engineer -in -charge. |
| 137 | Earth filling work for proper leveling of water work site, in accordance with the contour map and Grid map of existing site enclosed, including leveling, dressing, excavation and filling of earth where necessary and also including all labour, materials, T&P etc.required for proper completion of works and also including carriage of earth from within a distance of about 8 km. from the site of works as per instructions of Engineer -in -charge. |
| 138 | Supply of all material labour T&P etc required for Construction of Cemicurcular 250 mm dia drain along boundry wall as per instructions of Engineer -in -charge. |
| 139 | Provision for arboroculture of water works compound including green grass, show tree etc. |
| 140 | Provide of all material labour, T&P etc and Construt of two room staff quarter/ office room at water works site identified by the Engineer -incharge as per department type design and rawing and specifications of civil work laid down in the bid document, including all material, labour, T&P etc complete for proper completion of work as per instruction of Engineer-in-charge |
| 141 | Provide all materials labour and T&P etc required for proper completion of Construction of ground water recharge mechanism |
| 142 | E/M Work |
| 143 | Transportation,Erection of rig machine including Loading , unloading, Dismantling & labour etc complete in all respect . |
| 144 | Supply of Tubewell Assembly |
| 145 | M.S.Tubewell assembly with all required parts like plain pipe, Slotted pipe (as required upto 50% of plain pipes) rings, well cap bail plug, clamp reducer, central guide, suport structure etc. as required & as per typed design complete in all respect.(Note- Axial Length of Reducer without Ring shall be measured with casing pipe) |
| 146 | 300 mm dia M.S. Pipe |
| 147 | 200 mm dia M.S. Plain/slotted |
| 148 | CONSTRUCTION OF TUBE WELL -Leveling and dressing of site and camp equipage etc for Rig machine at pin point and drilling up to 200 metre deep. |
| 149 | ERECTION OF RIG MACHINE AND DRILLING WORK- |
| 150 | Drilling of 600mm dia bore from G.L. to 65 m BGL. |
| 151 | Drilling of 500mm dia bore from 65m BGL to 100m BGL. |
| 152 | Drilling of 500mm dia bore from 100m BGL to 200m BGL. |
| 153 | LOWERING OF TUBE WELL ASSEMBLY AND SHROUDING OF T.W. BY GRAVEL- |
| 154 | Lowering of 300mmx200mm dia tube well assembly in bore hole and shrouding of pea Gravel between annular space of bore hole and T.W. assembly from G.L. to 180m BGL. |
| 155 | Lowering of 300 mm dia M.S. Housing pipe from GL to 60 m.BGL |
| 156 | Lowering of 200 mm dia M.S. Plain/slotted pipe 60 m. BGL to 100 m. BGL |
| 157 | Lowering of 200 mm dia M.S. Plain/slotted pipe 100 m. BGL to 180 m. BGL |
| 158 | PEA-GRAVEL- |
| 159 | 1.60 mm to 4.80 mm. size pea gravel of Lalkuwan quarry duly screened, washed and proper stacking at site. |
| 160 | DEVELOPMENT OF TUBE WELL |
| 161 | Development of tube well by 350 PSI air compressor |
| 162 | Transportation,Installation, Dismantling of compressor including levelling & dressing of site and camp equipage. |
| 163 | Development of tube well by 350 PSI air compressor. |
| 164 | Sodium Hexametaphasphate |
| 165 | Development of tube well by 3 cusec O.P. unit |
| 166 | Transportation,Installation & Dismantling of O.P. unit including levelling & dressing of site and camp equipage. |
| 167 | Development of tube well by 3 cusec O.P. unit. |
| 168 | TEST :- |
| 169 | Chemical and bacteriological test. |
| 170 | Yield and verticality test of tube well. |
| 171 | Logging of tube well. |
| 172 | NEW PUMPING PLANT FOR Lamahi Zone -2,Madhwa Zone -3,Aidhede Zone -4,Sarsawan Zone -5,Lodhaan Zone -6,Chataripur Zone -7 |
| 173 | SITC of Submersible pumpset having capacity 1200 LPM, 56 to 60 mtr Head with 24 mtr Column Pipe Assembly, NRV, CIDF Bend 90°, CF A/F Tee, D/F Pipe ( 1.5 m long 2 No.s and 1 m long 1 No.), Earthing, Painting, Toolset, Power wiring of pump house internal & external, Chainpulley block and all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 174 | SITC of Soft Starter with RS485 Port-400V Class 15 kW rating for the above pumpset |
| 175 | Supply, Installation and Commissioning of automatic servo voltage Stabilizer-30 KVA(Input Voltage 230V±450V) to Output Voltage 415V± 1% As per IS 9815-1994 |
| 176 | Additional Column Pipe 3 mtr long |
| 177 | Internal Electrification of pump house. |
| 178 | CE/UL certifeid Intelligent Smart Energy Meter |
| 179 | Moter Operated Actuater with Valves 150 mm size |
| 180 | Main Switch Incomer Panel |
| 181 | Actuator Panel |
| 182 | CE/UL Certifeid Electromagnetic Flow Meter 150 mm size |
| 183 | 150 mm dia C.I. dismantling joint PN 1.0 |
| 184 | Auto Phase reversal unit with inbuilt delay and enclosure control panel etc. |
| 185 | CE/UL Certifeid Hydrostatic type sub soil water level transmitter for tubewell |
| 186 | CE/UL certifeid 3 phase Surge Protecter for control panel. |
| 187 | CE/UL certifeid Pressure Transmiter with local display |
| 188 | CE/UL Certifeid 7 HMI touch screen suitable to communication with PLC/RTU for display & control of process parameters |
| 189 | Complete cabling including power cables of all equipment. |
| 190 | Control panel with IP54 protection ,industrial grade for all equipments.separate for control (24V) and power equipment |
| 191 | Installation, commissioning & testing trial for tubewell |
| 192 | Earthing work of all equipments of pumping plant and scada system |
| 193 | Automatic Chlorination System compatible to SCADA system with level switch |
| 194 | NEW PUMPING PLANT FOR TARNA ZONE-9 |
| 195 | SITC of Submersible pumpset having capacity 1500 LPM, 58 mtr Head or as per site requirement with 24 mtr Column Pipe Assembly 150mm mm size , NRV, CIDF Bend 90°, CF A/F Tee, D/F Pipe ( 1.5 m long 2 No.s and 1 m long 1 No.), Earthing, Painting, Toolset, Power wiring of pump house internal & external, Chainpulley block and all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 196 | SITC of Soft Starter with RS485 Port-400V Class 22.5 kW for the above pumpset |
| 197 | Supply, Installation and Commissioning of automatic servo voltage Stabilizer-40 KVA(Input Voltage 230V±450V) to Output Voltage 415V± 1% As per IS 9815-1994 |
| 198 | Additional Column Pipe 3 mtr long |
| 199 | Internal Electrification of pump house. |
| 200 | CE/UL certifeid Intelligent Smart Energy Meter |
| 201 | Moter Operated Actuater with Valves 150 mm size |
| 202 | 150 mm dia C.I. dismantling joint PN 1.0 |
| 203 | Main Switch Incomer Panel |
| 204 | Actuator Panel |
| 205 | CE/UL Certifeid Electromagnetic Flow Meter 150 mm size |
| 206 | Auto Phase reversal unit with inbuilt delay and enclosure control panel etc. |
| 207 | CE/UL Certifeid Hydrostatic type sub soil water level transmitter for tubewell |
| 208 | CE/UL certifeid 3 phase Surge Protecter for control panel. |
| 209 | CE/UL certifeid Pressure Transmiter with local display |
| 210 | CE/UL Certifeid 7 hmi touch screen suitable to communication with PLC/RTU for display & control of process parameters |
| 211 | Complete cabling including power cables of all equipment. |
| 212 | Control panel with IP54 protection ,industrial grade for all equipments.separate for control (24V) and power equipment |
| 213 | Installation, commissioning & testing trial for tubewell |
| 214 | Earthing work of all equipments of pumping plant and scada system |
| 215 | Automatic Chlorination System compatible to SCADA system with level switch |
| 216 | NEW PUMPING PLANT FOR Pissaur Zone-10 |
| 217 | SITC of Submersible pumpset having capacity 1200 LPM, 28 mtr Head or as per site requirement with 24 mtr Column Pipe Assembly 150mm mm size, NRV, CIDF Bend 90°, CF A/F Tee, D/F Pipe ( 1.5 m long 2 No.s and 1 m long 1 No.), Earthing, Painting, Toolset, Power wiring of pump house internal & external, Chainpulley block and all Pumping Plant accessories with nut bolts and rubber packing etc. |
| 218 | SITC of Soft Starter with RS485 Port-400V Class 7.5 kW for the above pumpset |
| 219 | Supply, Installation and Commissioning of automatic servo voltage Stabilizer-15 KVA(Input Voltage 230V±450V) to Output Voltage 415V± 1% As per IS 9815-1994 |
| 220 | Additional Column Pipe 3 mtr long |
| 221 | Internal Electrification of pump house. |
| 222 | CE/UL certifeid Intelligent Smart Energy Meter |
| 223 | Moter Operated Actuater with Valves 150 mm size |
| 224 | 150 mm dia C.I. dismantling joint PN 1.0 |
| 225 | Main Switch Incomer Panel |
| 226 | Actuator Panel |
| 227 | CE/UL Certifeid Electromagnetic Flow Meter 150 mm/100 mm size |
| 228 | Auto Phase reversal unit with inbuilt delay and enclosure control panel etc. |
| 229 | CE/UL Certifeid Hydrostatic type sub soil water level transmitter for tubewell |
| 230 | CE/UL certifeid 3 phase Surge Protecter for control panel. |
| 231 | CE/UL certifeid Pressure Transmiter with local display |
| 232 | CE/UL Certifeid 7 hmi touch screen suitable to communication with PLC/RTU for display & control of process parameters |
| 233 | Complete cabling including power cables of all equipment. |
| 234 | Control panel with IP54 protection ,industrial grade for all equipments.separate for control (24V) and power equipment |
| 235 | Installation, commissioning & testing trial for tubewell |
| 236 | Earthing work of all equipments of pumping plant and scada system |
| 237 | Automatic Chlorination System compatible to SCADA system with level switch |
| 238 | 350 mm dia OHT Scada work for Zone-2,3,5,6 & 7 |
| 239 | SITC OF CE/UL certifeid Radar Type level sensor with transmitter for OHT |
| 240 | SITC OF Control valve with Actuator of 350 mm dia size for OHT ,throtlled at any position at any instant, inbuilt with positioning card and panel |
| 241 | SITC OF CE/UL certifeid Electromagnetic Flowmeters for OHT.size 350 mm |
| 242 | 350 mm dia C.I. dismantling joint PN 1.0 |
| 243 | SITC of UPS of suitable capacity (3 KVA) for operation of actuators installed at outlet line, in case of power failure at the time of distribution water supplywith cabinet, with minimum 3 Hrs power backup |
| 244 | Complete wiring, cabling, earthing & arrangement of power and communication with PLC if power and PLC is not nearby and arrangement of protection for these intruments/equipments- complete in all respect |
| 245 | 400 mm dia OHT outlet for Zone-4 & 8 |
| 246 | SITC OF CE/UL certifeid Radar Type level sensor with transmitter for OHT |
| 247 | SITC OF Control valve with Actuator of 400 mm dia size for OHT ,throtlled at any position at any instant, inbuilt with positioning card and panel |
| 248 | SITC of CE/UL certifeid Electromagnetic Flowmeters for OHT.size 400 mm |
| 249 | 400 mm dia C.I. dismantling joint PN 1.0 |
| 250 | SITC of UPS of suitable capacity (5 KVA) for operation actuators installed at outlet line, in case of power failure at the time of distribution water supply with cabinet,with minimum 3 Hrs power backup |
| 251 | Complete wiring, cabling, earthing & arrangement of power and communication with PLC if power and PLC is not nearby and arrangement of protection for these intruments/equipments- complete in all respect |
| 252 | 450 mm dia OHT outlet for Zone-9 & 10 |
| 253 | SITC OF CE/UL certifeid Radar Type level sensor with transmitter for OHT |
| 254 | SITC OF Control valve with Actuator of 450 mm dia size for OHT ,throtlled at any position at any instant, inbuilt with positioning card and panel |
| 255 | SITC of CE/UL certifeid Electromagnetic Flowmeters for OHT.size 450 mm |
| 256 | 450 mm dia C.I. dismantling joint PN 1.0 |
| 257 | SITC of UPS of suitable capacity (5 KVA) for operation actuators installed at outlet line, in case of power failure at the time of distribution water supply with cabinet,with minimum 3 Hrs power backup |
| 258 | Complete wiring, cabling, earthing & arrangement of power and communication with PLC if power and PLC is not nearby and arrangement of protection for these intruments/equipments- complete in all respect |
| 259 | SCADA /AUTOMATION WORK OF PUMPING PLANT FOR All ZONES -2 to 10 |
| 260 | CE & UL Certifeid PLC/RTU in IP 54 enclousure suitable to communicate with GSM based modem unit with CPU and power supply with analog and digital parameter and features as specifeid for tubewell to store and transmit data on GSM backbone RTU/PLC designed with logic to transfer data at multiple stations specifeid. |
| 261 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer & gather data from remote site to control station all accessoreis included with signal enhancer antenna made for pumping plant internet charges as specifeid |
| 262 | Local Control Station |
| 263 | CE/UL certified local conrol room PLC with redundant CPU& power supply at LCS in IP 54 enclouser as per spec mentioned in technical bid documents. |
| 264 | Full development version of required TAGS SCADA Software with coustomization of software for LCS as per spec mentioned in tachnical bid documents. |
| 265 | CE / UL Certified industrial grade 65\\" LED MONITOR with latest configuration as per technical specification. |
| 266 | Video wall media player of same OEM |
| 267 | Internet connection with Static IP |
| 268 | Desktop/PC with i5/i7 processor for as per spec mentioned in technical bid documents. |
| 269 | CE/UL Certified 3 KVA UPS with batteries as per spec mentioned in tachnical bid documents.with minimum 3 Hrs power backup |
| 270 | GSM based wireless/Broadband/Equivalent communication system for PLC capable to transfer & receive data & gather data form remote sites to control station,All accessories include signal enhancer antenna along with running expences till DLP. |
| 271 | Mobile App facility system architecture ( Industria internet based & viewed through mobile apps for increased local & remote visibility) |
| 272 | CE/UL certified Firewall for network protection. |
| 273 | Surge protector for Ethernet communication protection. |
| 274 | Industrial grade Ethernet Switch. |
| 275 | Canon/hp Laser printer1018 or equivalent |
| 276 | Installation,Commissioning ,testing including required furniture as 2 Tables, 10 Chair, Control Desk & other necessary Furniture items for LCS room internal wiring,PVC panelling of walls/false ceiling work etc. |
| 277 | Model of Water Supply Scheme for Presentation with table top |
| 278 | Split AC suitable for the control room 1.5 tonnes |
| 279 | Security Survelliance IP Camera with required hard drive to store data of atleast 15 Days |
| 280 | CLEAR WATER PUMPING PLANT |
| 281 | Supply,installation ,testing and commissioning of VT Clear water pump (as per civil structure) and appurtenant / related accessories ,etc complete. to lift 2700 LPM discharge 42 m head complete with column Pipe of size 200mm, Suitable length , Delivery Size of 200mm and Common Header of 300 mm size.(2W+1S) WITH Flange Mounted Solid Shaft Motor, 1475/985 RPM(preferable 985 rpm) , LT Type of motor with arrangement suitable to operate on 415 volt, 3 Phase 50 HZ AC supply. |
| 282 | Main Piping & Valves with Actuator |
| 283 | sluice Valve 200 mm dia with actuator having specification confirming (as per IS 14446-2000) |
| 284 | Kirloskar/IVC make 200 mm dia Reflax Valve confirming to IS - 5312 part -1) |
| 285 | Kirloskar/IVC make sluice Valve 300 mm dia with actuator having specification confirming (as per IS 14446-2000) for common header and bypass side |
| 286 | Kirloskar/IVC make 300 mm dia Reflax Valve confirming to IS - 5312 part -1) |
| 287 | D/F 90º Bend of size 200 mm dia. |
| 288 | Tee of size 200x300x200 mm dia. |
| 289 | M.S.distance piece of 200 mm dia 1.0 M. long 2 Nos and 1.5 M. long 1 No. |
| 290 | M.S. Enlarger/Reducer of suitable size. |
| 291 | Supply of 3 Ton Capacity Gantry Crane Having 6 Metre lift, suitable span as per CWR size with girder & Mono Rail Trolley, Chain pulley Block all electrically operated. |
| 292 | Electromagnetic Flowmeter 300 mm Diameter |
| 293 | 300 mm dia C.I/D.I. dismantling joint PN 1.6 |
| 294 | 3 HP Dewatering Pump with complete piping |
| 295 | Internal Electrification and Campus Lighting |
| 296 | SITC of 2 KW Solar Power Plant for Internal & external Lighting |
| 297 | Power Wiring & Earthing material. |
| 298 | Rubber resistance sheet. |
| 299 | Erection of Pumping plant. |
| 300 | Commissioning & Testing of pumping plant |
| 301 | ELECTRIC SUB STATION |
| 302 | L.T. Panel- 2mm thick CRCA sheet fabricated factory wired dust, damp and vermin proof metal clad cubical and floor mounted single row type control panel for system voltage 400+10%, 50 Hz, comprising of following items-L.T. control panel having 2 Nos. incoming having 400 amp,36 KA ACB draw out type & outgoing Panels (3 No.) 125 amp MCCB, 03 Nos 63 Amp MCCB for aux light & suitable to operated on 400 ± 6 % volt , 3 Phase , 50 Hz, AC supply ,with C.Ts,P.T AVF Meter,KWH meter P.F Meter, Bus Bar chamber, Relays and other Protective Devices Complete in all Respects.Control panel is also suitable to meet the basic requirements of motor protection such as No volt and under voltage protection and thermal over load protection. Panel will be connected with PLC/RTU. including APFC panel with suitable capacity of capacitor bank having suitable MCCB and Discharge system with all necessary relays,instruments & wiring etc. Complete. |
| 303 | 11 KV /.410 kv HT Panel with 1 incomer 2 outcomer |
| 304 | 35 HP (26.50 kw) VFD Starter Panel of Suitable Capacity |
| 305 | 160 KVA LT Transformer |
| 306 | Supplying and laying of Power cable of 70 sq mm/ suitable size size of 11000 Volt grade 3 core armoured XLPE sheathed Al conductor from from UPPCL metering panel to HT Panel |
| 307 | Supply and making end termination/joints of the above cable |
| 308 | Supplying and laying of Power cable of 2R x 120 sq. mm/suitable size of 440 Volt grade 3.5 core Al armoured XLPE sheathed Al conductor for HT panel to transformer & T/F to LT panel |
| 309 | Supply and making end termination of the above cable |
| 310 | Supplying and laying of Power cable of 25 sq. mm/suitable size of 440 Volt grade 3.5 core armoured XLPE sheathed Cu conductor from LT Panel to Motor JB. |
| 311 | Earthing of electrical equipments as per IS/ IER |
| 312 | Proper fencing of sub-station portion as per IE Rules |
| 313 | Charges of Electrical safety clearance. |
| 314 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher. |
| 315 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 316 | Erection H.T./L.T. panels, transformers, laying of cables & filling H.T., L.T. Cable end boxes as detailed above. |
| 317 | Exhaust fans of suitable sweep/capacity |
| 318 | Commissioning and testing including type test of the sub station equipment including first filling and centrifuging of oil in the installed equipment wherever necessary. |
| 319 | AUTOMATION OF CWR PP |
| 320 | CE & UL Certifeid PLC/RTU in IP 54 enclousure suitable to communicate with GSM based modem unit with CPU and power supply with analog and digital parameter and features as specifeid for tubewell to store and transmit data on GSM backbone RTU/PLC designed with logic to transfer data at multiple stations specifeid. |
| 321 | GSM/GPRS based wireless communication with 4G modem for RTU/PLC capable to transfer & gather data from remote site to control station all accessoreis included with signal enhancer antenna made for pumping plant internet charges as specifeid |
| 322 | Intelligent energy meter |
| 323 | Smart Pressure transmitter |
| 324 | Auto phase reversal unit/Automatic transfer switch with inbuilt time delay and enclosure (Conforming to IEC 60947-1 & IEC 60947-6-1) of suitable for 630 Amp. rating |
| 325 | complete Cabling work for pumping plant & instrument |
| 326 | Security survelliance IP camera |
| 327 | Radar type level transmitter with RTU communication |
| 328 | Control Panel with IP 65 protection, industrial grade 24 V power supply and other required items |
| 329 | 3 phase Surge protector for all AC control supplies to all the equipment |
| 330 | CE & BIS approved H.P or equvalent local control station hardware with latest configuration i- 7 processor, 1TB - HDD , 8 GB RAM , DVD , Minimum 32\\" LED LG/Samsung or equivalent , mouse & key board, UPS & other Required item: |
| 331 | 7\\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 332 | Installation, testing and commissioning |
| 333 | double Earthing work of all equipments of pumping plant and scada system |
| 334 | SITC of UPS of suitable capacity (5 KVA) for operation actuators installed at outlet line, in case of power failure at the time of distribution water supply with cabinet |
| 335 | Three Month Trial & Run |
| 336 | Three Month Trial & Run of CWR PP & their allied works in all Zone Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail