| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division JPDCL Reasi Name of Work:- Supply, Installation, Testing and Commissioning for creation of 63KVA Sub Station along with HT Tap line and LT Network at Sankhi Pyt Thangriote under UT CAPEX (SCA to TSS) under the jurisdiction of Electric Division JPDCL Reasi. Contract No: e-NIT No. 49 of 2025-26 dt. 21.03.2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Erection of 11 KV Line |
| 4 | ST Pole 9 mtr ( ST 410 SP-33) |
| 5 | GI V cross-arm with top Bracket including clamp and GI Channel X-arm including clamps and braces |
| 6 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 7 | ACSR Weasel Conductor |
| 8 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 9 | 11kV Polymeric composite Disc Insulator with GI fitting 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm. |
| 10 | Galvinized Nuts and Bolts |
| 11 | Danger Plates with Clamps |
| 12 | Anti-Climbing Device with Clamps |
| 13 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25X3) mm. |
| 14 | Aluminium Paint |
| 15 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 16 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete. |
| 17 | Erection of LT Line |
| 18 | 8 mtr long Pole ST-410, SP15 |
| 19 | GI M Clamp for shackle Insulator |
| 20 | ACSR Weasel Conductor |
| 21 | 16 KN Polymer Shackle Insulators |
| 22 | Galvanised Nuts & Bolts |
| 23 | Danger Plates with clamps |
| 24 | Red Oxide |
| 25 | Aluminium Paint |
| 26 | Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip |
| 27 | Anti-Climbing Device with Clamps |
| 28 | Cement bottoming 1:2:4 mix as per REC standards .45cum/Pole |
| 29 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete. |
| 30 | Creation of 63 kVA sub station |
| 31 | 11/0.433KV, 3-phase 63 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate |
| 32 | 9 mtr long Pole ST-410, SP33 |
| 33 | Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type |
| 34 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 35 | 11kV Horn Gap Fuse set 3-phase, 200 Amp |
| 36 | 70 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type |
| 37 | 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 38 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 39 | GI Channel/Angle/Flat of different sizes including clamps |
| 40 | Galvanised Nuts & Bolts |
| 41 | Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. |
| 42 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 43 | Wedge Connectors / PG Clamps |
| 44 | Danger Plates with Clamps |
| 45 | GI Barbed Wire for Anti Climbing |
| 46 | LT Distribution Box for 63 KVA DTR with MCCB for Incomer & SFUs for outgoing Circuits |
| 47 | Cement bottoming 1:2:4 mix as per REC standards .5cum/Pole |
| 48 | Galvanised Stay setwith 50x8mm stay clamp, Guy Insulator (2 Nos), Anchor Plate (200x200x6mm) nuts and Bolts, 2Nos Turn Buckles, 1.8 long, 16mm diameter solid GS Stay rod & 7/3.15mm dia GI Standard wire complete Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |