| 1 | Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in any type of soil (i.e. soft/ loose or hard/ dense soil) complete all as specified and as directed. |
| 2 | Returning, filling in trenches, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soil complete all as specified and as directed. |
| 3 | Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed. |
| 4 | M&L for cement concrete 1:3:6 type C1, using 20mm graded crushed stone aggregate as in copings, kneelers, apex stones, bed plates, pedestal of electric poles and the like including weathering, slightly rounded, chamfered angle and throating as directed including use and waste of form work (straight or curved) all exposed surface of concrete finished fair complete all as specified & as directed.Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment. |
| 5 | M&L for cutting of existing road for removing / laying UG Cables/ pipe line, depth of cutting not exceeding 90cm and width 45cm and filling the trench of road i.e. excluding top 20cm with existing aggregate obtained from cutting, watered and properly rammed to satisfaction of EIC and finally provide with & including 20 cm thick PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate to entire width of trench & finally match the top surface to road & disposal of debris to a distance not exceeding 250 metre and depositing where directed complete all as directed. |
| 6 | M&L for filling approved dry river sand for cushioning and cover for protection of under ground electric cable in trenches 8 cm before laying cable and 15 cm deep over the cable and punning to 18 cm total thickness complete all as specified and as directed. Notes :-(i) Approved dry sand free from vegetations, grass and other deleterious substances shall be used.(ii) For the purpose of payment, only punned thickness shall be measured. |
| 7 | Taking down carefully old existing HT PCC Cable Cover of Class EHV / HVP / HV of any type & size complete all as specified & as directed. |
| 8 | Laying only HT PCC cable covers of any type & size for protection of UG HT electric cables in trenches, obtained serviceable from serial item No. 7 here-in-above, complete all as specified & as directed. |
| 9 | Supplying and laying un-reinforced precast cement concrete cable covers, Class HV, Type-1, Flat, size 300 mm x 180 mm x 40mm for protection of underground electric cable in trenches complete all as specified and as directed. |
| 10 | Taking down carefully old existing LT PCC Cable Cover of Class LV of any type & size complete all as specified & as directed. |
| 11 | Laying only LT PCC cable covers of any type & size for protection of UG LT electric cables in trenches, obtained serviceable from serial item No. 10 here-in-above, complete all as specified & as directed. |
| 12 | Supply and laying un-reinforced precast concrete cable cover, Class LV, Type-1, Flat, size 250mm x 150mm x 40mm for protection of underground electric cable in trenches complete all as specified and as directed. |
| 13 | Supply and laying/fixing 40 mm bore High Density Polyethylene (HDPE) Pipes of Grade ‘PE 100’, Pressure Class ‘PN 8’, ‘SDR-17’, ISI marked, with all fittings, laid in trenches, under floors or roads/ along poles etc for protection of electric cables, fixed in repairs, complete all as directed. |
| 14 | Supply and laying/fixing 20 mm bore High Density Polyethylene (HDPE) Pipes of Grade ‘PE 100’, Pressure Class ‘PN 8’, ‘SDR-17’, ISI marked, with all fittings, laid in trenches, under floors or roads/ along poles etc for protection of electric cables, fixed in repairs, complete all as directed. |
| 15 | M&L for Galvanized iron tubing, 100mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls etc with required size of flat iron (minimum 25mmx3mm) clamps, bolts, nuts and washers for protection of HT/LT electric cable including taking down old unserviceable protection pipe with clamps complete all as specified & as directed.Note :- Excavation & earthwork shall be measured & paid for separately. |
| 16 | All as per serial item No. 15 here-in-above, but 80mm bore. |
| 17 | Supply, laying, jointing and testing HT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium stranded conductor 11000 Volt (Earthed) grade of cross sectional area 95 Sqmm, 3 Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc, including dismantling & taking out old unserviceable HT cable, complete all as specified & as directed.Note : Sand cushioning, cable protection covers, protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately. |
| 18 | Supply, laying, jointing and testing LT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with aluminium stranded conductor 1100 Volt grade cross sectional area 120 sqmm 3½ Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including dismantling & taking out old unserviceable LT cable complete all as specified & as directed.Note : Sand cushioning, cable protection covers, protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately. |
| 19 | All as per serial item No. 18 here-in-above, but cross-sectional area 70 Sqmm 3½ Core. |
| 20 | All as per serial item No. 18 here-in-above, but cross-sectional area 50 Sqmm 3½ Core. |
| 21 | All as per serial item No. 18 here-in-above, but cross-sectional area 35 Sqmm 3½ Core. |
| 22 | All as per serial item No. 18 here-in-above, but cross-sectional area 16 Sqmm 4 Core. |
| 23 | Supply, laying, jointing and testing LT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with copper stranded conductor 1100 Volt grade cross sectional area 2.5 sqmm 3 core (ISI marked) fixed on wall/ pole or laid in trenches/ floor etc including dismantling & taking out old unserviceable cable complete all as specified & as directed. |
| 24 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 25 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 26 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 27 | M&L for cable jointing kit for 1100 V grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 4 core PVC/XLPE armoured aluminium conductor cable of size 16 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 28 | M&L for cable jointing kit for 1100 V grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 50 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 29 | All as per serial item No. 28 here-in-above, but size 70 Sqmm to 95 Sqmm. |
| 30 | All as per serial item No. 28 here-in-above, but size 120 Sqmm to 185 Sqmm. |
| 31 | All as per serial item No. 28 here-in-above, but size 240 Sqmm to 300 Sqmm. |
| 32 | All as per serial item No. 28 here-in-above, but size 400 Sqmm to 500 Sqmm. |
| 33 | S&F Danger notice plate of 25x20cm size, 1.6mm thick mild steel sheet, vitreous enameled white, with letters (in English, Hindi & Gujarati), figures and conventional skull and bones in signal red colour for HT 11000 Volts and fixed with suitable MS clamps made out of flat iron 25x3mm, bolts and nuts of approved size, fixed in repairs, complete all as specified & as directed. |
| 34 | M&L for servicing and repair to HT RMU/ VCB of size up to 630 Amp complete by taking the shutdown with prior intimation and cleaning the contacts & servicing of HT fuses, bushes, all type of coils, contactors, springs, motors, relays, limit switches, CTs, etc and put the trolley in position and testing complete all as specified and as directed by Engineer-in-Charge. |
| 35 | M&L for servicing and repair to HT load break switch of RMU/ VCB of size upto 630 Amp complete by taking the shutdown with prior intimation and cleaning the contracts, terminals, insulators, lagging pins, etc and testing after completion complete all as specified and as directed by Engineer-in-Charge. |
| 36 | M&L for servicing and repair to operating mechanism and gear box oil leakage of RMU of size upto 630 Amp complete by taking the shutdown with prior intimation and testing after completion complete all as specified and as directed by Engineer-in-Charge. |
| 37 | S&F in repairs Shunt trip coil for HT VCB of make C&S/ ABB/ Seimens |
| 38 | S&F in repairs closing coil for HT VCB of make C&S/ ABB/ Seimens |
| 39 | S&F in repairs spring charging motor for HT VCB of make C&S/ ABB/ Seimens |
| 40 | S&F in repairs Limit switch of type LSMS11, AC 15 A, 3A/400 V for HT VCB of make C&S/ ABB |
| 41 | S&F in repairs Limit switch of type MU25-I/l 2, 16 A/250 V AC for HT VCB make C&S/ ABB/ Seimens |
| 42 | S&F in repairs Breaker control switch 10A, spring return to neutral 3 position & label trip-neutral-close for HT VCB/ RMU of make C&S/ ABB |
| 43 | S&F in repairs Hand reset master trip relay, aux-110V DC (CLR-H-3). Make: C&S/ ABB/ Seimens |
| 44 | S&F in repairs IDMT non directional O/C & E/F relay aux.-110V DC (IRI-PRO-3I-EI-5-5) complete all as directed. |
| 45 | S&F in repairs HT HRC fuse of 10 to 63 Amp as per sample. Make: L&T/ C&S/ ABB/ Bussmann/ Siemens or equivalent as approved by GE. |
| 46 | S&F in repairs CT's 200-100/5-5A dual core, resin cast, core 1:- metering-15VA CL-1, core2:- protection-15VA CL-5P10, STC-18. 4kA for 3s |
| 47 | S&F in repairs CT's 100-50/5-5A dual core, resin cast, core1:- metering-15VA CL-1, core2:- protection-15VA CL-5P10, STC-18.4kA for 3s |
| 48 | S&F in repairs VT 11kv/ √3/110 vac/√3, 200VA, CL-1, 1 phase resin cast |
| 49 | S&F in repairs digital HTCT Meter (Trivector Meter), Class 0.5s (Base Mounting), 3 Phase 4 wire, 4 Quadrant measurement, Anti-tamper features, with CT 200-100/5A including all accessories complete all as specified & as directed.Make : L&T Model ‘ER300P’ Cat No. WR300BB5200 or equivalent in makes mentioned in Appendix 'B' here-in-after, as approved by GE). |
| 50 | S&F in repairs Analog Ammeter 0-100-200A CTR-200-100/5A CL-1 size 144x144mm |
| 51 | S&F in repairs Analog Ammeter 0-50-100A CTR-100-50/5A CL-1 size 144x144mm |
| 52 | S&F in repairs 0-15kV analog Voltmeter PTR-11kv/110 vac. Size - 144x144mm |
| 53 | S&F in repairs HT fuse 11kV/3.15A, length - 195mm, diameter - 25.4mm |
| 54 | S&F in repairs LED type indication lamp red, yellow, blue colour 63.5V AC, dia - 22.5mm |
| 55 | S&F in repairs LED type indication lamp red, green, blue, white colour 110V AC, dia - 22.5mm |
| 56 | S&F in repairs Space heater 80W 230V AC for 11kV HT electric VCB |
| 57 | S&F in repairs Thermostat 0-110°C 15A 230V AC for 11kV HT electric VCB |
| 58 | S&F in repairs VCB breaker mechanism for 11 kV HT electric VCB |
| 59 | S&F in repairs Spout of VCB/RMU of 11kV |
| 60 | S&F in repairs PT Spout of VCB/ RMU of 11kV |
| 61 | S&F in repairs Power pack suitable for VCB with Input Voltage 230V, AC, O/P -110 V DC, with LED indication showing Main ON, Battery Mode, Battery Low, Out Put O/Load etc complete all as per existing type. |
| 62 | S&F in repairs 26AH 12Volt Lead acid battery (Maintenance free battery with minimum 2 years manufacturer’s warranty) for RMU including necessary connection complete. Make: Exide Powersafe plus or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 63 | S&F in repair smart coil/ opening coil/ relay trip coil/ under voltage coil/ blocking coil of RMU by shutdown with prior intimation and testing after completion complete all as specified and as directed. |
| 64 | Disconnecting/ Taking out the existing transformer of the capacity upto 400 kVA from site for repairing and transporting to workshop for servicing and repairing including loading, unloading and handling to carry out the necessary repairs and refixing the same after & including checking of all parts for repair/ replacement, repairing, installation, testing and commissioning at its original/ new location, decanting the transformer oil, etc, for smooth functioning, complete all as directed by Engineer-in-Charge.Notes :- (i) Necessary spare parts required replacement shall be replaced only after prior inspection & approval of Engineer-in-Charge and replacement shall be measured & paid for separately under relevant items of this Schedule. (ii) Unit rate quoted by the tenderer shall be deemed to include for minor spares/extras. The decision of Accepting officer regarding minor spares/extras shall be final, conclusive and binding. (iii) All T&P & transportation shall be arranged by contractor and rates for the same shall deemed to be included in rate quoted. |
| 65 | Disconnecting/ Taking out the existing transformer of the capacity upto 1250 kVA from site for repairing and transporting to workshop for servicing and repairing including loading, unloading and handling to carry out the necessary repairs and refixing the same after & including checking of all parts for repair/ replacement, repairing, installation, testing and commissioning at its original/ new location, decanting the transformer oil, etc, for smooth functioning, complete all as directed by Engineer-in-Charge.Notes :- (i) Necessary spare parts required replacement shall be replaced only after prior inspection & approval of Engineer-in-Charge and replacement shall be measured & paid for separately under relevant items of this Schedule. (ii) Unit rate quoted by the tenderer shall be deemed to include for minor spares/extras. The decision of Accepting officer regarding minor spares/extras shall be final, conclusive and binding. (iii) All T&P & transportation shall be arranged by contractor and rates for the same shall deemed to be included in rate quoted. |
| 66 | Rewinding of coils all as per its original specifications by new copper conductor and with HT/ LT necessary insulation materials. |
| 67 | Replacement of HT 11 KV bushing assembly with brass terminal, neoprene rubber gasket and washers etc complete with accessories for transformer of capacity upto 1250 KVA. |
| 68 | Replacement of LT bushing assembly with brass terminal, neoprene rubber gasket and washers etc complete with accessories for transformer of capacity upto 1250 KVA. |
| 69 | Supply and filling new Transformer oil up to conservator level marking as per IS-335 having dielectric strength not less than 40 kV at 2.5mm gap complete all as specified and as directed. Make : Electrol, Power Oil, Indian Oil, Savita or equivalent as approved by GE. |
| 70 | Replacement of Silica Gel blue in crystal in existing transformer breathers for transformer of capacity upto 1250 KVA. |
| 71 | Replacement of HT 11 KV off-load Tap changing assembly complete for transformer of capacity upto 1250 KVA. |
| 72 | M&L for preparation of external surfaces of distribution transformer of capacity upto 1250 KVA including cleaning and removing oil spots from the body and painting with one coat of synthetic enamel paint (first quality) of approved tint with gun sprayer including marking of SM/MES No etc. on transformer with synthetic enamel paint (white) complete all as specified and as directed. |
| 73 | M&L for filtration / dehydration of old/existing transformer oil including topping up of transformer oil as required in the transformers of different capacity, installed at various locations with suitable capacity of filtration machine to achieve dielectric strength minimum 60 KV complete all as specified and as directed.Notes: (i) All necessary T&P / testing equipment shall be provided by the contractor at his own cost. No extra payment shall be made to the contractor. (ii) New Transformer Oil required for topping up shall be paid for separately under relevant item of this Schedule. |
| 74 | M&L for trip relay setting as per ground requirement by testing of the transformer at site by providing filtration machine at RMU/ VCB relay setting report complete all as directed by Engineer-in-Charge. |
| 75 | M&L for preparation of old painted steel surfaces by cleaning, removing rust, grease and apply one coat of 1st quality synthetic enamel paint of approved tint (Spray painting outside /inside surfaces) by removing and re-fitting of switch gears/ busbar of the feeder pillar box/ LT Panels Outdoor/ Indoor type of any size complete with prior permission of Engineer in Charge. Base frame shall be painted with Black synthetic enamel paint and including writing the SM No. / MES No. on Panel/ Feeder pillar box in white synthetic enamel paint complete all as specified and as directed. |
| 76 | S&F locking arrangement with MS aldrop bolt set (mild steel sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet) complete of size 225 mm to existing feeder pillar box by welding including taking down old worn out locking arrangement complete all as specified. |
| 77 | S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal head screws, enclosed in suitable PVC box, complete all as specified & as directed. |
| 78 | M&L for Air termination, single pointed aluminium rod 12mm dia and 300mm long fix to aluminium strip, nut, bolts and washers including taking down existing air termination complete all as specified & as directed. |
| 79 | M&L for precast PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate as in bed blocks, anchorage blocks, foundation blocks, kneelers, apex stones, bed plates, cover slabs, mangers, shelves and similar articles with plain faces including placing in position over roof etc and set in CM (1:4) complete all as specified & as directed. |
| 80 | M&L for Galvanized iron tubing, 32mm bore, light grade, ISI marked, with & including all fittings and fixed to walls / ceilings or laid in floors complete all as specified & as directed. |
| 81 | M&L for aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground including taking out existing aluminium strip complete all as specified & as directed. |
| 82 | M&L for galvanised iron strip 32 x 6mm earth continuity conductor or main earthing lead buried in ground / fixed on wall with suitable porcelain insulators including taking out existing GI strip complete all as specified and as directed. |
| 83 | M&L for galvanised iron strip 25 x 4mm earth continuity conductor or main earthing lead buried in ground / fixed on wall with suitable porcelain insulators including taking out existing GI strip complete all as specified and as directed. |
| 84 | S&F in repair copper strip 20mm x 3.15mm complete with saddles and fixing screws for fitting the strip or fixing with & including suitable porcelain insulators, complete all as specified & as directed. |
| 85 | M&L for Earthing with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to Panel / transformer / GOD / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover reinforced with 8 mm dia TMT bars reinforced at 100 mm C/C both ways and handle of 6 mm dia MS bar made to shape complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. |
| 86 | S&F in repairs Cast Iron Cable route marker of size 100mm dia & 6mm thickness duly embossed ‘HT’ welded to & including 25x25x3mm angle iron support 600mm long and embedded in PCC 1:2:4 type B1 (using 20mm graded crushed stone aggregate) block of size 20x20x20cm including necessary excavation & earthwork with & including painting with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer complete all as specified & as directed. |
| 87 | S&F in repair MCCB with thermal magnetic protection unit rating 400 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4220 07 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 88 | S&F in repair MCCB with thermal magnetic protection unit rating 320 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4220 06 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 89 | S&F in repair MCCB with thermal magnetic protection unit rating 250 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4202 19 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 90 | S&F in repair MCCB with thermal magnetic protection unit rating 160 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 57 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 91 | S&F in repair MCCB with thermal magnetic protection unit rating 125 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 16 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 92 | S&F in repair MCCB with thermal magnetic protection unit rating 100 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 15 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 93 | Disconnecting/ Taking out the existing transformer of capacity more than 100 kVA but upto 500 kVA with all electrical HT/LT connections, earthing of body & neutral and shifting of transformer to another location in INS Valsura and installing on existing 2/4 pole structure or platform with necessary fixing arrangement including connecting up electrically, earthings, etc, commissioning and testing complete all as specified and as directed.Notes : (i) All T&P/Vehicle required for shifting, connection, loading, unloading, etc including necessary petty items like bolts, nuts etc shall be arranged by contractor and rates for the same shall deemed to be included in rate quoted. (ii) If transformer or any connected equipment/part is lost or damaged while in the custody of the contractor, the same shall be provided / repaired by the contractor at his own cost complete to the entire satisfaction of GE. |
| 94 | Disconnecting/ Taking out the existing OCB/ VCB of any capacity with all electrical HT/LT connections, earthing of body & neutral and shifting of OCB/ VCB to another location in INS Valsura and installing on existing platform with necessary fixing arrangement including connecting up electrically, earthings, etc, commissioning and testing complete all as specified and as directed.Notes : (i) All T&P/Vehicle required for shifting, connection, loading, unloading, etc including necessary petty items like bolts, nuts etc shall be arranged by contractor and rates for the same shall deemed to be included in rate quoted. (ii) If OCB/ VCB or any connected equipment/ part is lost or damaged while in the custody of the contractor, the same shall be provided/ repaired by the contractor at his own cost complete to the entire satisfaction of GE. |
| 95 | M&L for laying of plain Navy blue colour HT insulating mat of minimum thickness 3mm, shock proof complete all as specified & as directed. |
| 96 | M&L cold applied bushing boot kit Set of Three for 11 kV transformer on incomer side of HT supply, fixed in repairs, complete all as specified & as directed. Please Enable Macros to View BoQ information |