| 1 | Supply and fix in replacement of on load automatic change over switch 415 V, 4 pole, 125 A as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 2 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 160 A as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 3 | Supply and fix in replacement on load change over switch 415 V, 4 pole,200 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 4 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 63 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 5 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 6 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 7 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 8 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 9 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 10 | Supply and fix in replacement MCB, 415 volts, 4 pole 10 KA, 63A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 11 | Supply and fix in replacement MCB, 415 volts, 4 pole 10 KA, 40A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 12 | Supply and fix in replacement MCB, 220 volts, DP 10 KA, 63A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 13 | Supply and fix in replacement MCB, 220 volts, DP 10 KA, 32A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 14 | Supply and fix in replacement MCB, 220 volts, SP 10 KA, 40 to 63A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 15 | Supply and fix in replacement MCB, 220 volts, SP 10 KA, 6 to 32A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 16 | M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of following size :-Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch. |
| 17 | 16 to 25 Sqmm 3.5 core |
| 18 | 35 to 70 Sqmm 3.5 core |
| 19 | 95 to 150 Sqmm 3.5 core |
| 20 | Supplying and laying in replacement of GI tubing medium grade for cable protection in trenches/duct/fixing to pole/wall or in such similar position of following size all as specified and directed:- |
| 21 | 100 mm dia |
| 22 | 80 mm dia |
| 23 | 50 mm dia |
| 24 | 40 mm dia |
| 25 | Taking up old unserviceable LT UG cables from trench/poles/wall etc of following size all as specified and directed:- |
| 26 | 10 Sqmm 2 core |
| 27 | 10 Sqmm 4 core |
| 28 | 16 Sqmm 4 core |
| 29 | 25 Sqmm 3.5 core |
| 30 | 35 Sqmm 3.5 core |
| 31 | 50 Sqmm 3.5 core |
| 32 | 95 Sqmm 3.5 core |
| 33 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes all as specified and directed. Note : Excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this items. |
| 34 | 10 Sqmm 2 core |
| 35 | 10 Sqmm 4 core |
| 36 | 16 Sqmm 4 core |
| 37 | 25 Sqmm 3.5 core |
| 38 | 35 Sqmm 3.5 core |
| 39 | 50 Sqmm 3.5 core |
| 40 | 95 Sqmm 3.5 core |
| 41 | M&L for re-laying and re ruiting of existing LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes and connections testing in new or old position after complete all as specified and directed.complete all as specified and directed by Engr-in-Charge. Note : Excavation, returning filling, removal of surplus soil, shall be measured and paid under relevant of this Items. |
| 42 | 50 Sqmm 3.5 core |
| 43 | 95 Sqmm 3.5 core |
| 44 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed |
| 45 | All as per item No 21 above but outer dia of 63 mm and inner dia 50 mm. |
| 46 | All as per item No 21 above but outer dia of 77 mm and inner dia 63 mm. |
| 47 | All as per item No 21 above but outer dia of 90 mm and inner dia 75 mm . |
| 48 | Excavation in soft / loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed. |
| 49 | Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms complete all as specified and directed. |
| 50 | Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point complete all as specified and directed. |
| 51 | Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 32 x 6mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 50mm dia 5 mtr long GI pipe connected to main control board and GI pipe light grade 20mm bore for watering and including funnel wire mesh, RCC pit cover 50mm thick with 10mm dia reinforcement 100mm c/c and PCC chamber pit with pcc 1:2:4 Type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part -I 2009. |
| 52 | M & L for repair of LT Panel board outdoor type repair/replace damaged door hinges set of three nos front and back side and legs 40x40x6mm MS angle and necessary cutting, welding drilling hole,pcc repairs,cables slevees with colour code,repairs old us wiring etc works required at site complete all as specified and directed. |
| 53 | Provide of services for finding out cable fault location for LT UG cable, XLPE insulated 1100 Volts, of any size with fault detector machine complete all as specified and as directed. |
| 54 | S&F in replacement of digital Volt meter (0-500) including connections and testing for proper functioning complete all as specified and directed. |
| 55 | S&F in replacement of digital ammeter including connections and testing for proper functioning complete all as specified and directed. |
| 56 | S&F in replacement of Indicating Lamp R. Y. B (LED) Type including connections and testing for proper functioning complete all as specified and directed. |
| 57 | S&F in replacement of selector switch for ammeter/ volt mete including connections and testing for proper functioning complete all as specified and directed. |
| 58 | S&F in replacement of CTs of required rating including connections and testing for proper functioning complete all as specified and directed. |
| 59 | Material & Labour for spray painting to feeder pillar box / LT panel & duct cover etc, including angle iron frame with two coats of synthetic enamel paint grey or colour as approved by GE / Engr in -Charge as per site suitability synthetic enamel paint including door welding with hinges ccomplete all as specified and directed. |
| 60 | Material and labour for fixing of PVC line spacers, spiral/ Hard PVC type with PVC screws provison complete all as specified and directed Please Enable Macros to View BoQ information |
| 61 | Material and labour for fixing of PVC line spacers, spiral/ Hard PVC type with PVC screws provison complete all as specified and directed Please Enable Macros to View BoQ information |