| 1 | Dismantling and taking down air break gang operated switch vertical / horizontal mounted including insulators and operating mechanism / replacement of old unserviceable air break switches of 200 Amps complete all as specified and directed by Engineer-in-charge. |
| 2 | Supplying and fixing, installing, commissioning and testing HT 11KV, 3 phase system, outdoor type gang operated switch, air break type suitable for vertical mounting complete with necessary insulators and separators, set of drop out fuses (12 insulators) and operating handle of GI pipe 25 mm dia, medium grade rod of suitable length (mechanically operating arrangements), locking arrangement with lock and two keys complete of rating 200 Amp complete all as specified and directed by Engineer-in-charge. |
| 3 | M&L for repair of air break gang operated switch vertical / horizontal mounted including required accessories like moving contact assembly, fixed contact assembly, insulators, arching horn,roller bearing assembly, blade stopper, AL Jumper, counter balancing spring, Nuts & Bolts, clamp, GI pipe, handle and operating mechanism of any capacity complete all as specified and directed by Engr-in-Charge. |
| 4 | Dismantling insulators any type, any size from its original position and removing from site complete all as specified and directed by Engineer-in-charge. |
| 5 | S&F pin type composite/polymer brown insulator incl one galvanised MS spindle, two washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade fixed on poles/cross arms of upto 9 m long complete all as specified and directed by Engineer-in-charge. |
| 6 | S&F Disc type insulator, porcelain, vitreous 150 mm high and 150 mm dia ball and socket type, white, brown or green with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed by Engineer-in-charge. |
| 7 | S & F of Disc type insulator composite/polymer one galvanised MS spindle, two GI washers and one GI nut, for 11000 volts grade, complete all as specified and directed by Engineer-in-charge. |
| 8 | Material and labour for Scrapping rusted portion of steel pole and applying one coat of primer after that applying two coats of aluminium paint including channels existed on Two pole structure complete all as specified and directed by the Engr-in-Charge. |
| 9 | Material and labour for Scrapping rusted portion of old surface of steel pole including channels and applying onr coat of primer after that applying two coats of aluminium paint including making five no. alternative yellow & black strips 30 cm height each (upto 1.50 metre height from top of PCC coping & numbering to the poles with synthetic enamel paint complete all as specified and directed by the Engr-in-Charge. |
| 10 | Supplying, laying, jointing and testing in replacement of XLPE insulated heavy duty multi stranded armoured and PVC sheathed HT cable 11000 volts grade with aluminium conductor cross sectional area 95 sqmm 3 core conforming to IS- 1554 laid in trenches/ ducts/ along poles/ through pipes complete all as specified & directed by Engineer-in- charge.Note: Excavation & earth work shall be measured & paid separately under appropriate item of this Schedule. |
| 11 | S&F in repair end termination joint 11 KV Outdoor type, end termination heat shrinkable of size 95 sqmm including thimbling, nut/bolts & washers, HV insulating tape etc. complete all as specified and as directed and directed by Engineer-in-charge. |
| 12 | Dismantling and taking out the old stay assembly complete incl demolition of plain cement complete all as specified and directed by Engineer-in-charge. Note : (i) Unit rate of this item includes the loose/disconnect the all accessories which are connected to stay assy includng necessary excavation as directed. (ii) Existing stay assy are fixed on the LT/HT pole of PCC or steel tubular pole, nothing extra shall be paid on this account. |
| 13 | Material and Labour Stay assembly complete with accessories as shown in electrical plate No 1 incl GI Adjustable Stay Rod of 20 mm Dia, GI Stay wire of size 7/4 mm incl stay clamps, loop type insulator, excavation in any strata and PCC 1:3:6 concrete all as specified and directed by Engineer-in-charge. Note:- Unit rate of this item includes the cost of earthwork, loop type insulator, PCC and stay wire. |
| 14 | S & F in replacement of lightning Arrestor Expulsion type Transmission Class 65 Kilo Amps 11000 V Grade including connecting complete all as specified and directed by Engineer-in-charge. Please Enable Macros to View BoQ information |
| 15 | S & F in replacement of lightning Arrestor Expulsion type Transmission Class 65 Kilo Amps 11000 V Grade including connecting complete all as specified and directed by Engineer-in-charge. Please Enable Macros to View BoQ information |