| 1 | Pipeline Work (Based on REVISED BSR 2023 of CE (Tech.) PHED Jaipur |
| 2 | Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work). Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. Supply may be in coil or straight length in 6 M/12 M. |
| 3 | HDPE PE-80 PN-10 |
| 4 | 90 mm dia |
| 5 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 6 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required .: |
| 7 | Ordinary rock |
| 8 | Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended up to date), with internal cement mortar lining suitable for potable water with rubber ring (EPDM) joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work). Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. |
| 9 | 100 mm |
| 10 | Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 11 | Providing and laying in position cement concrete in specified grade over prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, complete work as per technical specification and scope of work. |
| 12 | M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). |
| 13 | Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 14 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 15 | 80 mm dia |
| 16 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. |
| 17 | MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) |
| 18 | Construction of RCC Sluice valve chamber for different type of valves including earthwork excavation, 100mm PCC M15 as levelling course, RCC M25 grade for base slab, side wall & cover slab , including cost of steel reinforcement , form work, Pre-cast slabs, plastic encapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as per specifications and standard drawings and as per direction of Engineer-in-Charge. |
| 19 | For Class-AA loading |
| 20 | Sluice valve chamber of size 1.13 m x0.85 m x1.325 m-for pipe size-up to 100 mm |
| 21 | SITC of Bulk Flow Meter with removable mechanism class \\"B\\" confirming to ISO:4064:2005/ IS: 2373 of approved make of following dia sized pipelines and specifications complete: Media : Water (Clear ), Temp. 50 deg., Pr. rating: PN16, Protection type: IP- 68, Body Material : IS-210 Gr. FG-200, Accuracy Class :Class B (±2 % @ Nominal flow rate), Magnetic Drive, Dry Dial, Epoxy powder coated, Pulse out put option, Anti-magnetic protection including all materials and making connection with existing pipeline required for Bulk Flow Meter including cutting the existing pipeline etc. complete in all respect as per technical specification and as per direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 22 | BFM 80 mm |
| 23 | Supply & Instt. of P&M (Based on REVISED BSR 2023 of CE (Tech.) PHED Jaipur |
| 24 | Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected on C.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 25 | Centrifugal Monoblock Pump set (Single Stage) |
| 26 | 3.7 KW (5.0 HP) |
| 27 | DOL STARTER 3.7KW (5 HP ) - : For 2 motors (1 W+ 1S) I/C - MCB 32A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 30/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G- MCB 25A ,TP, 10 KA, C Curve (2), Power Cont 12A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 2 Kvar (2) |
| 28 | Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanised rubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367 (Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 29 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 |
| 30 | 80 mm dia |
| 31 | 100 mm dia |
| 32 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV) of approved make of following Pressure rating & dia complete, confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Cover & disc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body, cover and disc inside and outside . Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of SS- AISI- 410 ,Hinge Malleable cast iron / SS AISI 316 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, Gasket EPDM/NBR ,Nut-Bolt as per IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 33 | Class PN 1.0 |
| 34 | 100 mm dia |
| 35 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 |
| 36 | 80 mm dia |
| 37 | 100 mm dia. |
| 38 | Providing, lowering, aligning, fixing in position in pipe line, CI double flanged Dual plate check valve of approved make of following Pressure rating & dia complete, as per API: 594/ API: 598 and of following specifications: Body & Cover of Grey cast iron of IS:210/ FG200 , Disc / plates - Cast steel ,Disc seal ring of EPDM/ NBR (food grade quality) ,Body seat of SS ,Face to face dimensions as per API: 594 ,Flanges Drilled as per IS:1538. Epoxy (Non-Toxic & suitable for drinking water) applied on body & cover inside and outside . Shaft/Stop Pin of SS- AISI- 304/410 , Hinge SS AISI 316/304 / CS ,Spring SS AISI 316/304 , Bonnet Gasket EPDM ,Bush- Brass with EPDM/NBR \\"O \\"ring seal.Nut-Bolt confirming to IS:1363 and IS: 1367 (galvanised steel) ,Insertion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 39 | Class PN 1.0 |
| 40 | 80 mm dia |
| 41 | Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. |
| 42 | 3 core 4.0 Sq.mm |
| 43 | 3 core 6.0 Sq.mm |
| 44 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. |
| 45 | MS pipe specials up to 600mm dia (with minimum 5mm thickness sheet) |
| 46 | Water Connection Work Based on RUIDP BSR 2023 |
| 47 | Providing and making house service connections from water supply distribution HDPE pipe line upto water meter chamber inside the property using HDPE (Class-PE 80) PN 6 composite pipes for upto 5 metre length. The item consisting of composite pipes of HDPE pipe below the ground level and GI class B pipe above the ground level including supply and fixing of ferrules, electro fusion saddle, clamps, rubber sheets, tapping, compression fittings etc, complete including all material, labour, testing and commissioning as per Technical Specifications and as per direction of Engineer. |
| 48 | 32 mm Diameter HDPE below the ground & 25 mm GI pipe class B above the ground |
| 49 | Supply, fixing, testing and commissioning of Multi jet magnetic type domestic water meter Class-B confirming to IS:779-1996 / EEC/ MDIL with end coupling as per relevant technical specification and the direction of the Engineer - 50 mm size |
| 50 | Based on PWD BSR 2023 |
| 51 | P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make : |
| 52 | (-do-) 50mm nominal bore. |
| 53 | Making connection of G.I. distribution branch with G.I. main including all fitting. |
| 54 | Beyond 25mm & upto 100mm dia |
| 55 | 3 - Years O&M Work (Based on PHED O&M 2020 BSR of Region-I Jodhpur) |
| 56 | Maintenance of pipelines irrespective of size & material which includes Repairing of Bursts & leakages pollution control, survey & removal of choking, disconnection of illegal connections, Collection & recording minimum 10 nos. residual chlorine samples during daily supply timings, interconnections and all works related to pipeline network in existing distribution /rising main pipe lines of all sizes by digging out suitable size of pit in soft and loose soil/ hard soil including cutting of Black top, WBM & CC top of road of any size at work site. This will also include cutting of pipe ends, fixing of pipe piece with jointing material to make repair leak proof and then refilling of excavated tench / pit / road shall be done properly i.e after a layer of 20 cm with proper watering and ramming in layers. For entire job contractor will use their own T & P. Contractor with his own resources shall arrange de-watering,JCB & Tractor compressor if any and restore any amenity at his own cost damaged while performing the work in this item. The work includes daily patrolling and repair the leakages within stipulated time and complete maintenance of pipe line network of rising and distribution pipeline network within the scope of work for per km pipe line per month. Jointing material shall be provided by the department. |
| 57 | Minimum labour for a following kms pipelines to be deployed. |
| 58 | 1 km to 50 km - one fitter-II & one beldar(7.90 Km. Per Months x 36 Months = 284.40 Km.) |
| 59 | Running expenditure of pumphouses which includes complete operation of pumpmotor, maintenance of log-books as directed by Engineer-in-charge, general upkeeping of premises, security arrangements, Regular chemical dosing in CWR, cleaning and desilting of SR/ CWR/ SUMP once every six months, daily valve operation under the Campus of pump house and all other works as mentioned in scope of work in tender document for per pump house per month. (power supply up to 8 hrs). (excluding repairing of pumping machinery etc.) |
| 60 | Upto 50 HP(01 no. PH x 36 Months = 36) Please Enable Macros to View BoQ information |