Tender For Configuration, Restoration & Integration Of Rtu Cum Gateway Work With Existing Scada (Siemense Make) At 132Kv S/S Pddu Nagar Under Etd-Iii, Sahupuri For Real Time Data Transmission To Sldc Lucknow And Backup Data To Modipuram, Varanasi-Uttar Pradesh
TDR : 54767224
Tender Notice
BOQ
19 Days Left
Varanasi
Uttar Pradesh
Tender For Configuration, Restoration & Integration Of Rtu Cum Gateway Work With Existing Scada (Siemense Make) At 132Kv S/S Pddu Nagar Under Etd-Iii, Sahupuri For Real Time Data Transmission To Sldc Lucknow And Backup Data To Modipuram
Name of Work:- CONFIGURATION, RESTORATION & INTEGRATION OF RTU CUM GATEWAY WORK WITH EXISTING SCADA (SIEMENSE MAKE) AT 132kV S/S PDDU NAGAR UNDER ETD-III, SAHUPURI FOR REAL TIME DATA TRANSMISSION TO SLDC LUCKNOW AND BACKUP DATA TO MODIPURAM
Sl. No.
Item Description
1
Configuration and refurbishment of existing old SCADA system. The work shall include Fallowing services for ensuring smooth & healthy SCADA operation: A.Checking of all required events alarms dates & signals to SCADA from various bays and BCUs. B. Modification of SCADA system of old & existing bays as per requirement. C. Checking of defective FO cables & its healthiness. D. Checking healthiness of all protection relays communication with SCADA
2
Supply of 2no's of Manage Ethernet Switches for the network device BCPU/PROT Relays communication.
3
Supply of LC-LC Patch Cord 5 Meter
4
A- Supply & installation of FO cables/patch cord/LIU and its related hardware as per site requirement – 1. Checking healthiness and rectifications of faults/issues of FO network. 2. Splicing and termination of FO cable of each kiosk. 3. Checking & modification work to complete the network .4.communication for smooth functioning of SCADA system.
5
All 132/33KV BCU and Protection IED ICD/SCD/IID/CID File configuration or Extraction from the existing BCU and Relay File. For all 132kV & 33kV Feeders
6
SLDC Configuration/Communication of 33KV Bays, Lucknow & Modipuram Over IEC-61805-104 Protocol.
7
SLDC Configuration/Communication of 132KV Bays, Lucknow & Modipuram Over IEC-61805-104 Protocol
8
Repairing of Main & Standby Server /CPU Not Power up Need to be check hardware and Change the useless Part.
9
Supply of 2 No’s 27 Inch Monitor & Mouse, Keyboard for main & Standby Server.
10
Note- a) Any additional requirement of works, minor consumables,T&P, manpower etc not mentioned shall be met by contractor at his own cost. b) The contractor shall ensure safety of the manpower involved in the job by providing proper safety equipments. c) Working of all operation of equipments/ bays with SAS, aquisition of all readings and log book will treated as completed work. d) Any License/Software required for configuration & restoration of existing SCADA system shall be in scope of contractor. Please Enable Macros to View BoQ information