| Sl. No. | Item Description |
| 1 | CIVIL WORKS |
| 2 | Construction of Sedimentation TankThe scope of work includes the Survey, Soil Testing, Design, Drawing, Supply, Construction, Installation, Testing, Commissioning, and Process Providing of a 14.40 MLD capacity Sedimentation Tank system and all associated ancillary works near Jawara Police Chawki, Agra Road, Etah, under the Jalesar Nagar Palika Reorganization Water Supply Scheme. The project encompasses all Civil, Mechanical, Electrical, Instrumentation, and allied works required to complete the facility in all respects as per the Engineer-in-Charge's directions. Civil and building works include the inlet channel, distribution chamber, distribution channel, inlet chamber, RCC jali, bypass channel, SS-304 railings, sedimentation tanks with RCC ramps and platforms, launders, outlet channels, and outlet chamber. Buildings include an office building with a laboratory, canteen, and control room, a DG set room, workshop and storage room, guest house, staff quarters , sanitary block, and a security gate with guard room. Site works include site clearance, earth filling, piling, grading, landscaping, campus development, approach and internal roads, fencing, internal drainage, plantation, and lighting. Mechanical works include manual screens (SS-316), sluice gates for inlet, bypass, and outlet channels (manually/electrically operated), adjustable weirs, steel platforms with ladders, decanting system with sluice valves, pipes and underdrainage valves for water transfer between tanks and sump, VT pumps with motors and delivery pipes, a monorail overhead crane, and associated workshop equipment. The potable water system includes bore pumps, Sintex tanks with auto ON/OFF flow controllers, and necessary pipes and valves. Electrical works include complete internal electrification, SCADA system with integration, and standby power arrangements to ensure uninterrupted operations. |
| 3 | Construction of CWR cum PumphouseThe scope of work include the survey, investigation, Soil Testing, Design and Drawing, Supply of all materials, labour T&P etc. provide by contractor all in accordance with all relevant IS code approved by engineer incharge as per condition of Bid Documents for construction of R.C.C M30 grade with cement OPC grade 43 & reinforcement steel bar required to construction of CWR cum pump house including meter room, panel room & scada room of following capacity :- 1250KL.Construction of a New CWR-cum-Pumping Station within the premises of the Sedimentation Tank Campus. |
| 4 | Construction of Break Pressure Tank (60 kl capacity)Survey,Design, Drawing & Supply of all materials,Labour T&P etc required for construction of specified capacity OHT (BPT) with specified staging as per following requirements:-Capacity -As Specified in Item No 1(i) to 1(xii)Grading of OHT (BPT) - M-35 GradeThe food grade epoxy coating of FOSROC / CIEBA GAIKI or reputated brand on the all inside surface area of water container after treatment of water tightness.Stair case - Seperate two column based RCC staircase and 1 m wide balcony with box type RCC structure at the entrance of the staircase to protect the entry of unwanted persons & locking arrangement with MS door.Railings - 20 mm dia G.I. Pipe (medium quality steel tubes as per IS 1239) railing consisting of 3 rows of with posts height (50x50x6 mm MS angle) (1.0 m) of same pipe around stair case (both sides), balcony & at the top dome periphery, including epoxy 3mm thick coating above base coat, 65mm dia GI pipe (medium quality steel tubes as per IS 1239) ladder with FRP coating from opening of top dome to inside the tank and top of bottom dome. Supply and fixing of CI man hole cover with locking device at opening on the top dome to go inside the tank.Ventilator and Water level indicator - RCC ventilator with SS grill (10 sqm at the spacing of 30 mm) with steel mosquito mesh, electronic digital water level indicator with ultrasonic sensor including supply & fixing of solar energy arrangements.Lightening conductor - A good quality lightening conductor covered with PVC casing.Vertical pipes - Inlet Pipe, outlet pipe, overflow & washout pipe, all requireed fittings as per specified design and drawing. |
| 5 | C.I. D/F pipe as per design criteria upto 1 m beyond the apron, IVC/Kirloskar sluice valve on inlet, out let & at wash out pipe, duck foot bend, puddle collers and bell mouths. 10 mm thick & 150 mm wide S S plate clamp for fixing of verticle pipes with RCC columns (minimum 2 clamps between ends of each pipe). It also includes bye pass arrangement of OHT. The velocity in the pipes shall not exceed 1.5 m/s.Flooring, Apron & Drain - 100 mm thick PCC of 1:2:4 & 100 mm thick CC of 1:1:2 with 6 mm thick glass strips not more than 1 sqm area upto 2 m from outer edge of the columns of OHT, drain of size 200 mm x 200 mm with 150 mm thick CC of 1:1:2 including necessary sluice valve chambers and pipe line required for proper drainage of rain water from the campus.Sluice valve chambers - 3 nos. of sluice valve chamber (minimum size 1.5 x 1.5 x 1.5 m or larger size as per requirements of site) of brick work with 200 mm thick RCC slab.Two coat apex painting over one coat primer of approved colour of asian / berger paints after fixing of RCC surface with grinder, repair of minor holes, unevenness etc. proper completion of work.Soil bearing capacity - Structure shall be design on the basis of bearing capacity of 8 tonne/sqm or minimum as per actual on the basis of test report of soil bearing capacity.Proposed OHT (BPT) of 60 KL, Staging 10.5 m.In the premises of the Sedimentation Tank campus near Jawara Police Chowki, Agra Road, Etah. |
| 6 | Construction of WTPThe work includes Survey, Soil Testing, Design& Drawing, Supply, Installation, Testing, Commissioning, and construction of 10 MLD Water Treatment Plant based on 22-hour operation, including all surveys such as topographical, geotechnical, and other required investigations, complete hydraulic, process, mechanical, electrical, ICA, structural, and architectural design, and obtaining statutory approvals with proper completion of all electrical, mechanical and civil works. The plant shall comprise an inlet chamber with mechanical/manual coarse and fine screens, aeration fountain/cascade, inlet channels with flow measurement arrangement (Parshall flume/magnetic flow meter), flash mixer, mixing channel, flocculator, clariflocculator and/or tube settlers with sludge draw-off, rapid sand gravity filters with complete backwash system including air blowers, wash water pumps, and backwash water tank, dirty wash water sump with recirculation pumps, sludge thickener with sludge pumps, centrifuge system housed in a centrifuge building with polymer preparation and dosing facilities, and recycling of recovered water to the headworks. The chemical treatment system shall include a chemical house, PAC or other coagulant storage and dosing arrangement, coagulant aid dosing (if required), and vacuum feed gas chlorination system with 100% standby, leak detection, and safety measures. The clear water system shall include a clear water reservoir/sump of specified capacity, pumping station with required number and capacity of pumps, motors, panels, starters, cables, and transformers, along with DG SET, complete internal electrification, SCADA & Its integration, and standby arrangements. Ancillary works include laboratory building with all specified lab equipment, administrative building, 08 Nos Staff quarter, sanitary block with water supply and drainage, campus roads, earth filling, piling, boundary wall etc and approach road, internal drainage, plantation and landscaping, fencing, lighting, and all other works required to complete the facility in all respects as per the direction of the Engineer-in-Charge. |
| 7 | Standby/Imponding Reservoir and Pump House |
| 8 | Excavation of foundation in ordinary soil (loam, clay or sand) including lift up to 1.5 m and lead up to 50 m including filling, watering and ramming of excavated earth into the trenches or into the space between the building and side of foundation trenches or into the plinth and disposal of surplus earth up to a distance of 50 m from the centre of the foundation trenches. |
| 9 | Providing dry trap/ granite/ quartzite/ gneiss, rubble stone soling in 15 cm to 20 cm thick layers including hand packing and compacting, etc. complete. (Bd-A-12/264) (below the impounding reservoir) |
| 10 | Concrete with 40 mm gauge stone ballast, coarse sand and cement in proportion of (12:6:1) in foundations and floors including supply of all materials, labour, t & p etc. Required for proper completion of the work (below the impounding reservoir). |
| 11 | R.C.C. with cement, coarse sand and 20 mm gauge approved stone ballast in proportion M30 in raft foundations & footings, including reinforcement and its cutting,bending, binding the same with 0.50 mm thick binding wire ( to be supplied by the contractor) and including necessary centering and shuttering, supply of all materials, labour, t&p etc. Required for proper completion of the work. |
| 12 | Supply of 600 mm dia K-9 of D.I. pipes Class K-9 including D.I. S/S or flanged Specials conforming to I.S. 8329/2000 conforming to latest I.S. 8329/2000 complete in all respect F.O.R. destination including all taxes and insurance . |
| 13 | From Impounding Reservoir to Pumping Station |
| 14 | From Pumping Station to Aerator |
| 15 | Supply of the following sizes DI D/F non-rising spindle soft seated glandless Hand Wheel operated with Sluice Valves destination including all taxes and insurance. |
| 16 | 600 mm dia.For Bye Pass Arrangment |
| 17 | Excavation for pipe line trenches in ordinary soil,(lime, clay or sand including lift up to 1.5m and lead up To 50m and refilling, watering, ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 18 | 600 mm dia K-9 |
| 19 | Carting from the store of the following sizes of D.I. double pipe k-9 and specials to the site of work lowering them in to trenches and laying true to alignment and gradient including jointing, testing of pipeline and including supply of jointing material such as nut & bolts, rubber insertion, white lead etc. com- plate but excluding cost of trenching and cutting of pipes etc. For making of lengths but including making joints. |
| 20 | 600 mm dia K-9 |
| 21 | Carting of D/F Sluice valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of jointing materials such as bolt nut, rubber insertion white lead complete with excluding values and specials required but including the testing etc. complete excluding values and specials required but including the testing etc. complete. |
| 22 | 600 mm dia.For Bye Pass Arrengment |
| 23 | Supply of all materials, labour T&P etc. required and construct masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete. |
| 24 | Thrust Block |
| 25 | Excavation in foundation in ordinary soil (loam, clay or sand) including lift up to 1.5 m and lead up to 50 m including filling, watering and ramming of excavated earth into the trenches or into the space between the building and side of foundation trenches or into the plinth and disposal of surplus earth up to a distance of 50 m from the centre of the foundation trenches. |
| 26 | 0.0m to 1.5m Depth. |
| 27 | 1.5m to 3.0m Depth. |
| 28 | 3.0m to 4.5m Depth. |
| 29 | 4.5m to 6.0m Depth. |
| 30 | Providing dry trap/ granite/ quartzite/ gneiss, rubble stone soling in 15 cm to 20 cm thick layers including hand packing and compacting, etc. complete. (Bd-A-12/264) |
| 31 | below the PCC Raft |
| 32 | Cement concrete with 20 mm gauge approved stone ballast, coarse sand and cement in the proportion of 6:3:1 including supply of all materials, labour, T&P etc. Required for proper completion of the work. |
| 33 | R.C.C. with cement, coarse sand and 20 mm gauge approved stone ballast in proportion M30 in raft foundations & footings, including reinforcement and its bending, fixing,cutting& binding the same with 0.50 mm thick binding wire ( to be supplied by the contractor) and including necessary centering, shuttering, supply of all materials, labour, T&P etc. Required for proper completion of the work. |
| 34 | Ist class brick work in 1:6 cement and local sand mortar in super structure including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 35 | 12mm thick plaster with cement, coarse sand and local sand mortar in 1:3 over brick work minimum thickness not to be less then 10mm including supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 36 | One Priming & Two Coat Of Apex Painting on new work including supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 37 | Supply & fixing of Window (1.2m x 1.5m) including supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 38 | Supply & fixing of Ventilator (1.2m x 0.55m) including supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 39 | Supply & fixing of Door (Closing Shutter/Rolling Shutter) including supply of all materials, labour, T & P etc. required for proper completion of the work. |
| 40 | Supply of the following sizes of D.I. pipes Class K-7 & 9 including D.I. S/S or flanged Specials conforming to I.S. 8329/2000 conforming to latest I.S. 8329/2000 complete in all respect F.O.R. destination including all taxes and insurance. |
| 41 | 600 mm dia K-7 (RAW WATER CARRIAGE MAIN) |
| 42 | 300 mm dia K-9 (MCWR TO OHT-1) |
| 43 | 300 mm dia K-9 (MCWR TO OHT-2) |
| 44 | 250 mm dia K-9 (MCWR TO OHT-3) |
| 45 | Supply of 900 mm ID & 924 mm OD of MS pipes 12 mm thick of specified dia conforming to latest I.S. 3589, including Epoxy coating inside and outside & complete in all respect F.O.R. destination including all taxes and insurance. |
| 46 | Supply of the following sizes DI D/F non-rising spindle soft seated glandless Hand Wheel operated with Sluice Valves destination including all taxes and insurance. |
| 47 | 250 mm dia |
| 48 | 300 mm dia |
| 49 | Supply of 100 mm dia of C.I. Double flanged scour valves as per latest I.S. code working pressure 10 kg/Sqcm F.O.R Destination including all taxes and insurance. |
| 50 | Supply of 25 mm dia screwed down type air valve with gun metal seat at site stone including all taxes. |
| 51 | Cleaning thick Bushes and thorny jungle without up rooting |
| 52 | Excavation for pipe line trenches in ordinary soil,(lime, clay or sand including lift up to 1.5m and lead up To 50m and refilling, watering, ramming of excavated earth in to trenches and disposal of surplus earth of the foundation trenches. |
| 53 | Carting from the store of the following sizes of D.I. double pipe k-9 and specials to the site of work lowering them in to trenches and laying true to alignment and gradient including jointing, testing of pipeline and including supply of jointing material such as nut & bolts, rubber insertion, white lead etc. complete and cutting of pipes etc. For making of lengths but including making joints. |
| 54 | 600 mm dia K-7 |
| 55 | 300 mm dia K-9 |
| 56 | 300 mm dia K-9 |
| 57 | 250 mm dia K-9 |
| 58 | Carting of D.I. D/F Sluice valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of jointing materials such as bolt nut, rubber insertion white lead including the testing etc. complete required for proper completion of the work. |
| 59 | 250 mm dia |
| 60 | 300 mm dia |
| 61 | Carting of 100 mm dia scour valves to the site of works lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete including the testing etc. complete required for proper completion of the work. |
| 62 | Carting of 25 mm dia screwed down air valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead including the testing etc. complete required for proper completion of the work. |
| 63 | Supply of all materials, labour T&P etc. required and construct masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete. |
| 64 | Surface box type |
| 65 | Supply of all materials, labour T&P Etc. required and construct 500 x 500 x 1000 mm size air valve chamber as per type design including supply and fixing the 500 mm dia CI manhole cover. |
| 66 | Dismantling of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials. |
| 67 | BITUMINOUS ROAD |
| 68 | C.C. ROAD |
| 69 | INTERLOCKING TILES |
| 70 | Reinstatement of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials. |
| 71 | BITUMINOUS ROAD |
| 72 | C.C. ROAD (Type-1) 10 CM-95% |
| 73 | INTERLOCKING TILES |
| 74 | Shifting of Electric pole in alignment of rising main/carrier main as per Departmental type design of UPPCL. |
| 75 | Installation of product pipe by Manual Pipe Jacking method including making of entry and exit pits upto 6.0 mtr depth, all related civil works like excavation, shoring/strutting, etc., manual shielded excavation, lowering of pipe segments in the jacking pit, laying and jointing of product pipeline through jacking process from the jacking pit after project completion as per the instructions of the Engineerin-Charge all complete including the cost of the pipe From 900mm & upto 1000 mm dia In Mixed Soil. |
| 76 | Thrust Block |
| 77 | Distribution System |
| 78 | Supply of the following sizes of DI K-7 pipes including AC/DI Specials conforming to I.S.- 8329/2000 confirming to latest relevant I.S.S with H.D.P.E/DI couplers etc complete in all respect F.O.R. destination including all taxes and insurance.IS -8329/2000 |
| 79 | 400 mm dia DI K-7 |
| 80 | 350 mm dia DI K-7 |
| 81 | 300 mm dia DI K-7 |
| 82 | 250 mm dia DI K-7 |
| 83 | 200 mm dia DI K-7 |
| 84 | Supply of the following sizes of HDPE pipes 6 kg/cm2 including confirming to latest relevant I.S.S with H.D.P.E/DI couplers etc complete in all respect F.O.R. destination including all taxes and insurance IS Code 4984:2016 HDPE GRADE-PE-100 |
| 85 | 160 mm dia HDPE Pipe PE-100 PN-6 |
| 86 | 140 mm dia HDPE Pipe PE-100 PN-6 |
| 87 | 110 mm dia HDPE Pipe PE-100 PN-6 |
| 88 | 90 mm dia HDPE Pipe PE-100 PN-6 |
| 89 | Supply of the following sizes DI D/F non-rising spindle soft seated glandless Hand Wheel operated with Sluice Valves destination including all taxes and insurance. |
| 90 | 300 mm dia |
| 91 | 250 mm dia |
| 92 | 200 mm dia |
| 93 | 150 mm dia |
| 94 | 100 mm dia |
| 95 | Supply of 100 mm dia of C.I. Double flanged scour valves as per latest I.S. code working pressure 10 kg/Sqcm F.O.R Destination including all taxes and insurance. |
| 96 | Supply of 25 mm dia screwed down type air valve with gun metal seat at site stone including all taxes. |
| 97 | Supply of underground sluice valves type fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site including all taxes. |
| 98 | Excavation for pipe line trenches in Ordinary soil,(lime, clay or sand Including lift up to 1.5m and lead up To 50m and refilling, watering, Ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 99 | Dismantling of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials. |
| 100 | BITUMINOUS ROAD |
| 101 | C.C. ROAD |
| 102 | INTERLOCKING TILES |
| 103 | Reinstatement of following type of surface including sorting out and staking of serviceable materials of disposal of unserviceable materials. |
| 104 | BITUMINOUS ROAD |
| 105 | C.C. ROAD (Type-1) 10 CM-95% |
| 106 | INTERLOCKING TILES |
| 107 | Carting from the store of the following sizes of HDPE/DI pipe and specials to the site of work lowering them in to trenches and laying true to alignment and gradient including jointing, testing of pipeline and including supply of jointing material such as nut & bolts, rubber insertion, white lead etc. com- plate but excluding cost of trenching and cutting of pipes etc. For making of lengths but including making joints. |
| 108 | 400 mm dia DI K-7 |
| 109 | 350 mm dia DI K-7 |
| 110 | 300 mm dia DI K-7 |
| 111 | 250 mm dia DI K-7 |
| 112 | 200 mm dia DI K-7 |
| 113 | 160 mm dia HDPE Pipe PE-100 PN-6 |
| 114 | 140 mm dia HDPE Pipe PE-100 PN-6 |
| 115 | 110 mm dia HDPE Pipe PE-100 PN-6 |
| 116 | 90 mm dia HDPE Pipe PE-100 PN-6 |
| 117 | Carting of D.I. D/F Sluice valves of Following sizes to the site of works Lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead including the testing etc. complete required for proper completion of the work. |
| 118 | 300 mm dia |
| 119 | 250 mm dia |
| 120 | 200 mm dia |
| 121 | 150 mm dia |
| 122 | 100 mm dia |
| 123 | Carting of 100 mm dia scour valves to the site of works lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete required but including the testing etc. complete. |
| 124 | Carting of 25 mm dia screwed down air valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete required but including the testing etc. complete. |
| 125 | Carting of 80 mm dia flanges fire hydrant of the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete required but including the testing etc. complete. |
| 126 | Supply of all materials, labour T&P etc. required and construct surface box/masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete. |
| 127 | Surface box type |
| 128 | Masonry type |
| 129 | Supply of all materials, labour T&P Etc. required and construct 500 x 500 x 1000 mm size air valve chamber asper type design including supply and fixing the 500 mm dia CI manhole cover. |
| 130 | Supply of all materials, labour T&P Etc. required and construct 900 x 900 x 1000 mm size fire hydrant chamber as per type design including supply and fixing the 500 mm dia CI manhole cover. |
| 131 | Road Crossing Large (7.0m Wide) |
| 132 | Road Crossing Small (3.5m Wide) |
| 133 | Provision of Nala/Culvert Crossing (Internal width Between 1 to 3m) |
| 134 | R.C.C Over Head Tank |
| 135 | Supply of all the materials, labour T&P and construction of a R.C.C. Over head tank above ground level with main components, based on IS- 3370 or liquid storage concrete in over head tank and foundation concrete as per specification in I.S. 2911. All Components of OHT will be casted in M-30 concrete with cement, coarse sand and approved stone grit as per I.S. 11682 and I.S. 456. Minimum depth of foundation below original ground level will be 2.0 M. Seismic effects and wind load should be taken into consideration as I.S. 1893 for earthquake resistance and I.S. 875 part-III for wind load on structure. The assumed bearing capacity of soil has been taken as 8 M.T. sqm. 1m wide Openwell Type RCC stair case from ground level to balcony. M.S. ladder made of 50 X 50 X 6 mm angle section and 20 mm plain M.S. bars (specification of M.S. should be as per IS 800-2007) with hand rails of 20 mm medium class G.I. pipes on both sides in three rows from balcony to top dome resting on an RCC platform (75 X 75 cm and 10 cm thick) projecting from top ring beam and one aluminium ladder inside the tank body ( from manhole in top dome to bottom dome). 1 m wide R.C.C. balcony around the tank at the junction point of vertical wall and conical wall. Proper R.C.C. railing and 20 mm dia medium class G.I. pipe (in 3 rows) on both sides of stair case, around the balcony at each landing from landing with top ring beam upto manhole on the top dome and at the periphery. |
| 136 | The G.I. pipes will be supported on R.C.C. posts of 100 mm dia or on the posts made of 50 X 50 X 6 mm M.S. angle section, spaced at intervals not more than 1.5 m. Proper ventilator at top dome in circular shape of 1.2 m dia along with an R.C.C. cover of minimum 1.50 m dia and 7.5 cm thickness, pillar of ventilator should be minimum 50 cm dia. The space between top dome and R.C.C. cover should be covered with mosquito net of standard quality along with expended metalled jail. Electro Magnetic Flow Meter. Lightening conductor as per I.S.S. 2309 of its latest amendments of latest electricity rules. It should consist proper elevation rod with 5 or more fork points proper down conductors of prescribed mental of proper size prescribed by ISS 2309-1969 and ISS 3013-1966. D.I. manhole of min 60 X 60 cm size made of M.S. channel section with adequate cover made of M.S. sheet of minimum 3mm thickness hinged with manhole with locking arrangement. This manhole should be fixe at top dome at proper place. |
| 137 | ZONE-1Inlet 300 mm, Outlet 400 mm, Over flow 300mm, Wash out 100 mm with Supply and Fixing of following sizes D.I. D/F sluice valves with hand wheels as per I.S.S. 700/1969 or its latest pressure 10 kg/sqcm including cartage from its store to the site of work, lowering them into trenches, fixing in position & testing etc. complete.ZONE-2Inlet 300 mm, Outlet 350 mm, Over flow 300mm, Wash out 100 mm with Supply and Fixing of following sizes D.I. D/F sluice valves with hand wheels as per I.S.S. 700/1969 or its latest pressure 10 kg/sqcm including cartage from its store to the site of work, lowering them into trenches, fixing in position & testing etc. complete.ZONE-3Inlet 250 mm, Outlet 300 mm, Over flow 250mm, Wash out 100 mm with Supply and Fixing of following sizes D.I. D/F sluice valves with hand wheels as per I.S.S. 700/1969 or its latest pressure 10 kg/sqcm including cartage from its store to the site of work, lowering them into trenches, fixing in position & testing etc. complete. |
| 138 | Construction of bed blocks in 1:2:4 PCC with cement, coarse sand and approved stone grit under each duck foot bend to support the vertical pipes. These bed blocks should supported on the raft not on the soil. Construction of surface box type Sluice valve chamber for above sluice valve (3 No.) as per departmental type design and drawing including supply and fixing of 150 mm x 150 mm size C.I. surface box including locking arrangement. Construction of washout/ overflow chamber as per departmental type design and drawing. Construction of P. C. C. Floor & Drain and all other necessary work as per departmental type drawing and design. Painting of all concrete surface and steel pipe works with three coats of approved cement paint and anticorrosive paints. Testing & Commission etc. all complete work. |
| 139 | 1500 KL / 20.0 M Staging (Zone-1) |
| 140 | 1500 KL / 18.0 M Staging (Zone-2) |
| 141 | 1000 KL / 24.0 M Staging (Zone-3) |
| 142 | Testing of bearing capacity of soil from a reorganized Govt. Engineering College or as directed by department. |
| 143 | Boundary wall gate and approach road |
| 144 | Construction of 1.8 m high and 230 mm thick boundary wall with 300 mmx300 mm thick pillar made in Brick masonry in 1 cement and 4coarse sand mortar, the spacing between two pillar should not be more than 3.5m c/c and the depth of foundation should not be less than 0.60m including piling where ever required, as per approved type design and drawing, and, as per specifications given in the bid document including plastering, painting & supply of all materials, labour T&P etc.for proper completion of work as per instructions of Engineer ‐in ‐ charge. |
| 145 | Provide all materials, labour T&P etc. required for proper completion of work and construct pillars as per type design 3.6 Main Gate 1.2 m wide wicket gate. |
| 146 | Provide all materials, labour T&P etc. required for proper completion of work and construct Interlocking approach road in water works campus |
| 147 | Provision for inside square drain including supply of all materials labour and T&P etc. complete. |
| 148 | 300MMX300MM SQUARE C.C DRAIN |
| 149 | Provision for Single Tap making ferrule house connection in following dia distribution main with fixing of saddle (electro fusion tapping saddle for making connection with HDPE distribution pipeline, DI strap saddle, ferrule for making connection with distribution pipe line other than HDPE), connection fittings, GM ferrule of 15mm dia including brass tape with welded, 20mm dia (OD) HDPE pipe (PE 100/PN 12.5) and 20 mm dia (OD) G.I. pipe class B upto house holder also including dismantling & reinstatement of roads, excavation of pit/trenches, supply of all fittings materials, labour, T&P etc. all work complete as per Type & Design Drawing direction of engineer in charge. |
| 150 | BOE Road |
| 151 | 110mm dia |
| 152 | For 125mm to 160mm dia |
| 153 | For 200mm to 250mm dia |
| 154 | For 300mm dia |
| 155 | CC Road |
| 156 | 110mm dia |
| 157 | For 125mm to 160mm dia |
| 158 | For 200mm to 250mm dia |
| 159 | For 300mm dia |
| 160 | For 350mm to 500mm dia |
| 161 | BITUMINOUS ROAD |
| 162 | 110mm dia |
| 163 | For 125mm to 160mm dia |
| 164 | For 200mm to 250mm dia |
| 165 | For 300mm dia |
| 166 | For 350mm to 500mm dia |
| 167 | Interlocking Tiles Road |
| 168 | 110mm dia |
| 169 | For 125mm to 160mm dia |
| 170 | For 200mm to 250mm dia |
| 171 | For 300mm dia |
| 172 | For 350mm to 500mm dia |
| 173 | Kachha Road |
| 174 | 110mm dia |
| 175 | For 125mm to 160mm dia |
| 176 | For 200mm to 250mm dia |
| 177 | For 300mm dia |
| 178 | For 350mm to 500mm dia |
| 179 | Construction of Staff Quarter |
| 180 | Rain Water Harvesting and Ground Water Rercharging Unit |
| 181 | Master Control Room (SIZE 8.0MX5.0MX4.0M) |
| 182 | Electrical & Mechanical Works |
| 183 | Raw Water Pumping Station Cum Intake well |
| 184 | PUMPING PLANT AND ACCESSORIES FOR RAW WATER PUMPING STATION CUM INTAKE WELL |
| 185 | Supply of Vertical type self-oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 21 mtr/suitable length column assembly, with vertical hollow shaft.Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows: (NOTE- Pump Discharge, Head & motor HP are tentative and may vary as per actual site condition at the time of execution.) |
| 186 | 4950 LPM / 32 Mtr. HEAD and coupled with suitable rating of motor (2w+2s) |
| 187 | MAIN PIPING AND SPECIALS :- |
| 188 | Cast iron pipes & specials. |
| 189 | Supply of galvanized nut- Bolt SS-304 and rubber packing material required for erection. |
| 190 | Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes |
| 191 | Valve actuator of size :- 250mm for pumps or as per site condition. |
| 192 | Valve actuator of size :- 300mm for common header or as per site condition. |
| 193 | Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing . |
| 194 | 250 mm Dia for pumps or as per site condition. |
| 195 | 300 mm Dia for common header or as per site condition. |
| 196 | CI Dismantling joints |
| 197 | 250 mm Dia for pumps or as per site condition. |
| 198 | 300 mm Dia for common header or as per site condition. |
| 199 | CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable. |
| 200 | Size 300mm for common header or as per site condition. |
| 201 | Power and control cables |
| 202 | Supply & Laying of 1100V grade, 3C/3.5C x50 mm2 or suitable rating XLPE insulated Copper Armoured Multistrand conductor cable from LT control panel to Starter Panel to respective motor with lugs. |
| 203 | Control cable 1*10C, 1.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc. for 03 Nos.pumps |
| 204 | ELECTRICAL SLUICE GATES: |
| 205 | Provision of CI Open Channel Sluice Gate with motor, actuator operated, Rising Spindle type. Sluice gates are as per IS 13349 Gate Size:1000mm(width)X 1000mm(depth)Suitable for max. seated water depth 700mmCL-PL Distance:2500mmFlush bottom closure, Rising spindle, Electrically operated, Closetop frame Complete in all respect. (Note : Size is tentative and may vary as per actual site conditions.) |
| 206 | Bar Coarse Screen |
| 207 | Provision of Manual Coarse Bar Screen: Channel width:600mm, Channel depth: 1000mm, Water depth: 800mm, Bar spacing: 20mm, Bar profile:10mmx50mm, MOC: SS316 Complete in all respect. (Note : Size is tentative and may vary as per actual site conditions.) |
| 208 | Supply of microprocessor based Automatic power factor correction relay panel, 440V ,IEC/EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , APFC relay in suitable steps, self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 60 KVAR or more suitable rating. |
| 209 | CE/UL Certified level transmitter for Sedimentation Tank :- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68 |
| 210 | CE/UL Certified Pressure transmitter for pumps and common header :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 211 | Complete earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with Copper Earth Plates, watering pipe and loop earthing (PS-702) 02 Nos. each of the equipment (3 Nos Pumps + 1 No. Starter Panel + 1 No. PLC Panel & other loads) size of earthing plate 600mm x 600mm x3 mm with salt and coal embodying 3 mtr. below the GL. |
| 212 | Tools & Plants-. As per requirments & specified in tender documents and Schedules or direction given by Engineer-Incharge. |
| 213 | E.O.T. crane of 5 Tonne capacity having span 9m. and lift 6 m. along with gantry girders, chain pulley block and geared trolley complete in all respect for pump house. |
| 214 | Rubber mats for electrical insulation purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness |
| 215 | Cable trench Chequerred plate |
| 216 | Fire fighting equipments 4.5 Kg such fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board. |
| 217 | Internal & External electrification of pumping station :- |
| 218 | Indoor Lighting |
| 219 | Internal electrification of Raw Water Pump House, Panel rooms with complete Wiring, Mid power SMD type 36W LED Light, fixture made from CRCA sheet steel housing, fittings etc.complete in all respect. |
| 220 | Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required. |
| 221 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 222 | Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required. |
| 223 | Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. |
| 224 | with regulator |
| 225 | Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. |
| 226 | 450mm sweep (900/1400 RPM) |
| 227 | Outdoor Lighting |
| 228 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 229 | Supply and fixing of HPSV/MV 125 watt fixture with lamp and its all accessories. |
| 230 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting system. |
| 231 | Supply and laying of 6 mm2 Al. unarmoured cable flat PVC insulated used for connection of lights fitted to junction boxes. |
| 232 | Earthing of street light pole (SOR-41) |
| 233 | Painting of street light (P5-634) |
| 234 | Outdoor Electrification with complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc. |
| 235 | Feeder pillar for lighting. |
| 236 | Installation of all above E/M equipments etc. complete. |
| 237 | Testing of all above E/M equipments at OEM Workplace & At Site complete at works & site as per direction given by Engineer-Incharge. |
| 238 | Commissioning of all above E/M equipments etc. complete |
| 239 | SUB STATION AT RAW WATER PUMPING STATION CUM INTAKE WELL |
| 240 | Supply of 12 KV, H.T. V.C.B. Panel with 01 incoming & 02 out going ,630 Amp. (25 KA) Rating have followings- 01 NO. INCOMER-: 3 O/C + 1 E/F IDMT Characteristics Relays based Incommer control panel equiped with over current & earth fault relay with core balance C.T., master trip relay, instantaneous under voltage realy & Auxilliary realy etc. C.T.ratio 30-20/5A Dual core, Class-1 for measurement core & 5P10 for protection core & PT 11KV/110 VAC. KWH meter, power factor meter, frequency meter. Amp. meter 0-20 & volt meter 0 to12 KV. All relays required separately conventioal type 24 to 30 VDC, 110 VAC. 02 NOS. OUTGOING -: outgoing feeder control panel equiped with triple pole 3 O/C + 1 E/F relay with IDMT & intantaneous characterisstics, mater trip relay & Auxilliary relay for Buchhloz alarm / trip, OTI alram / trip & WTI alram/trip, etc. C.T.ratio 30-15/5A, Class-1 for measurement core & 5P10 for protection core. DC SUPPLY-: SICT battery bank, exide make, consisting of 16 cells, 2 volt each for supply VDC 24 to 30 Volt with battery charger of approved make with suitable M.S. Stand / Trolley, equipment fittings with accessories etc. (03 sets means 01 composite Panel). |
| 241 | Supply of 3C x 95 Sq.mm or suitable rating size 11KV XLPE HT Copper cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to all transformers. |
| 242 | Supply of Oil immersed Outdoor type Power distribution transformer 11/0.433 KV rating of 200 KVA or more suitable rating double wound with copper winding, Level-2 or 3, vector group dyn 11, ONAN with OLTC tap changer operated for voltage variation + 5.0 % to - 10% at 07 tap positions in step of 2.5% along with its R.T.C.C. Panel complete with standard fitting & accessories incorporated with Marshall box for OTI,WTI & Buchholz relay etc. complete in all respect. |
| 243 | L.T. PCC Panel suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 1250 amps.or suitable Capacity. with Aluminium Bus Bar size of suitable capacity sectionalized through a bus section. The panel shall comprise of the following. (A) 02 No. incoming feeders from 02 Nos. from Transfomers with following details:- (i) 02 nos.Micro processor based 1000A,4P,EDO, 50 KA, A.C.B.or suitable rating for Incoming coming from 02 nos. Transformers with indication lamp mechanical on/off indicator. (ii) 01 nos.Micro processor based 1000A,4P,EDO, 50KA, A.C.B.or suitable rating motorised drawout type for Bus Coupler with Interlocking arrangements. (iii) One set of current transformer of suitable ratio (iv) One No. CT operated ammeter suitable ampere rating with ammeter (v) One No. Voltmeter 0-500 V with voltmeter (vi) One No. power factor meter 0.5 lag/ 1-0.5 lead (vii) One No. Surge arrestor Relay & One no. UV/OV Relay (viii) One No. Single phase preventor Relay (ix) One No. frequency meter. (B) The Followings Outgoing feeders as (i) 03 nos. 400A or suitable Microprocessor based MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for pumps.(ii) Ammeter with selector switch. (iii) Single phasing preventer. (iv) Sets of timer and relays for overload and underload. (v) level indicators with control cable from L.T. Panel to pumping plant for automatic level operation of pumping plants including moisture sensor and other protection (vi) One Nos. 63 Amps. MCCB for lighting. (vii) One Nos. 63 Amps. MCCB as Misc. load (viii) 02 Nos. 32 Amps. MCCB for spare.(ix) One Nos. 32 Amps. MCCB with auto operation. (x) 01 nos. 400A Microprocessor based MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for APFC Panel. |
| 244 | Supply and laying of 650/1100 volt grade 185sq mm 3½ core/ 4 core XLPE insulated Armoured Aluminium cable from transformers to L.T PCC panel. |
| 245 | Complete Double earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with Copper Earth Plates, wateringorpipe and loop earthing (PS-702) for (02 Nos for HT panel, 04 nos. for each Transformers + 02 No.for LT Panel & other loads) size of earthing plate 600mm x 600mm x3 mm with salt and coal embodying 3 mtr. below the GL. |
| 246 | Installation and Erection of all above substations equipments such as HT Panels , all Transformers with RCC Platform complete with Iron meshing around them and L.T. main control panel including all labor T&P complete in all respect. |
| 247 | Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core or suitable rating for 11 KV H.T. XLPE cable |
| 248 | Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core or suitable rating for 11 KV H.T. XLPE cable |
| 249 | NOC from Electrical safety department for all field installations such as pumping plants, substation etc. |
| 250 | Testing of all above E/M equipments at OEM Workplace such as transformer, HT Panels and main LT Panel as per direction given by Engineer-Incharge. |
| 251 | Commissioning of all above E/M equipments etc. complete |
| 252 | Automation For Raw Water Pumping Station Cum Intake Well |
| 253 | W.T.P with MCWR & Storage Pond Pumping Station |
| 254 | MAIN SUB STATION AT W.T.P INCLUDING MCWR & POND PUMPING STATION |
| 255 | Supply of 12 KV, H.T. V.C.B. Panel Indoor Type with 01 incoming & 02 out going ,1250 Amp. (25 KA) Rating have followings- 01 NO. INCOMER-: 3 O/C + 1 E/F IDMT Characteristics Relays based Incommer control panel equiped with over current & earth fault relay with core balance C.T., master trip relay, instantaneous under voltage realy & Auxilliary realy etc. C.T.ratio 50-40/5A Dual core, Class-1 for measurement core & 5P10 for protection core & PT 11KV/110 VAC. KWH meter, power factor meter, frequency meter. Amp. meter 0-20 & volt meter 0 to12 KV. All relays required separately conventioal type 24 to 30 VDC, 110 VAC. 02 NOS. OUTGOING -: outgoing feeder control panel equiped with triple pole 3 O/C + 1 E/F relay with IDMT & intantaneous characterisstics, mater trip relay & Auxilliary relay for Buchhloz alarm / trip, OTI alram / trip & WTI alram/trip, etc. C.T.ratio 50-40/5A, Class-1 for measurement core & 5P10 for protection core. DC SUPPLY-: SICT battery bank, exide make, consisting of 16 cells, 2 volt each for supply VDC 24 to 30 Volt with battery charger of approved make with suitable M.S. Stand / Trolley, equipment fittings with accessories etc. (03 sets means 01 composite Panel). |
| 256 | Supply of 3C x 185 Sq.mm or suitable size 11KV XLPE HT Copper cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to all transformers. |
| 257 | Supply of Oil immersed Outdoor type Power distribution transformer 11/0.433 KV rating of 800 KVA or more rating double wound with copper winding, Level-2 or 3, vector group dyn 11, ONAN with OLTC tap changer operated for voltage variation + 5.0 % to - 10% at 07 tap positions in step of 2.5% along with its R.T.C.C. Panel complete with standard fitting & accessories incorporated with Marshall box for OTI,WTI & Buchholz relay etc. complete in all respect. |
| 258 | MAIN LT PCC PANEL |
| 259 | Main L.T. PCC Panel suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 1250 amps.or suitable Capacity. with Aluminium Bus Bar size of suitable capacity sectionalized through a bus section. The panel shall comprise of the following. (A) Incoming feeders as:- (i) 02 nos.Micro processor based 1250A,4P,EDO, 50 KA, A.C.B. or suitable for Incoming coming from 02 nos. Transformers with indication lamp mechanical on/off indicator. (ii) 01 nos.Micro processor based 1250A,4P,EDO, 50KA, A.C.B.or suitable motorised drawout type for Bus Coupler with Interlocking arrangements. (iii) One set of current transformer of suitable ratio (iv) One No. CT operated ammeter suitable ampere rating with ammeter (v) One No. Voltmeter 0-500 V with voltmeter (vi) One No. power factor meter 0.5 lag/ 1-0.5 lead (vii) One No. Surge arrestor Relay & One no. UV/OV Relay (viii) One No. Single phase preventor Relay (ix) One No. frequency meter. |
| 260 | (B) The Followings Outgoing feeders as (i) 01 nos. 400A Microprocessor based MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for LT cum MCC Panel of MCWR (ii) 01 nos. 400A Microprocessor based MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for LT MCC Panel of WTP (iii) 01 nos. 250A MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for LT MCC Panel of Pumping Station of Storage Pond (iv) Ammeter with selector switch. (v) Single phasing preventer. (vi) Sets of timer and relays for overload and underload. (vii) 03 Nos. 63 Amps. MCCB for lighting. (viii) 03 Nos. 63 Amps. MCCB as Misc. load (ix) 03 Nos. 32 Amps. MCCB for spare. |
| 261 | Supply and laying of 650/1100 volt grade 400sq mm 3½ core/ 4 core or suitable rating XLPE insulated Armoured Aluminium cable from both transformers to Main L.T PCC panel at WTP campus. |
| 262 | LT cum MCC PANEL at MCWR |
| 263 | Main L.T. PCC Panel suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 500 amps.or suitable Capacity. with Aluminium Bus Bar size of suitable capacity sectionalized through a bus section. The panel shall comprise of the following. (A) Incoming feeders as:- (i) 01 nos.Micro processor based 400A,4P, 25 KA,or suitable capacity M.C.B.with indication lamp mechanical on/off indicator for 01 No. Incoming from Main LT PCC Panel (ii) One set of current transformer of suitable ratio (iii) One No. CT operated ammeter suitable ampere rating with ammeter (iv) One No. Voltmeter 0-500 V with voltmeter (v) One No. power factor meter 0.5 lag/ 1-0.5 lead (vi) One No. Surge arrestor Relay & One no. UV/OV Relay (vii) One No. Single phase preventor Relay (viii) One No. frequency meter. |
| 264 | (B) The Followings Outgoing feeders as (i) 02 nos. 125A MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for Pumps of Zone-1 (ii) 02 nos. 150A MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for Pumps of Zone-2 (iii) 02 nos. 100A MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for Pumps of Zone-3 (iv) Ammeter with selector switch. (v) Single phasing preventer. (vi) Sets of timer and relays for overload and underload. (vii) 03 Nos. 32 Amps. MCCB for lighting. & Misc. load (viii) 02 Nos. 150 Amps. MCCB for Automation. |
| 265 | Supply and laying of 650/1100 volt grade 120 sq mm 3½ core/ 4 core or suitable rating XLPE insulated Armoured Aluminium cable from Main L.T PCC panal to LT cum MCC PANEL at MCWR. |
| 266 | LT MCC PANEL at Pond Pumping Station |
| 267 | Main L.T. PCC Panel suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 500 amps.or suitable Capacity. with Aluminium Bus Bar size of suitable capacity sectionalized through a bus section. The panel shall comprise of the following. (A) Incoming feeders as:- (i) 01 nos.250A,4P, 25 KA,or suitable capacity M.C.B.with indication lamp mechanical on/off indicator for 01 No. Incoming from Main LT PCC Panel (ii) One set of current transformer of suitable ratio (iii) One No. CT operated ammeter suitable ampere rating with ammeter (iv) One No. Voltmeter 0-500 V with voltmeter (v) One No. power factor meter 0.5 lag/ 1-0.5 lead (vi) One No. Surge arrestor Relay & One no. UV/OV Relay (vii) One No. Single phase preventor Relay (viii) One No. frequency meter. |
| 268 | (B) The Followings Outgoing feeders as (i) 03 nos. 43A MCCB of 25KA capacity or suitable KA with indication lamp mechanical on/off indicator for Pumps (ii) Ammeter with selector switch. (iii) Single phasing preventer. (vi) Sets of timer and relays for overload and underload. (vii) 02 Nos. 32 Amps. MCCB for lighting. (viii) 01 Nos. 32 Amps. MCCB as Misc. load (ix) 01 Nos. 16 Amps. MCCB for spare. |
| 269 | Supply and laying of 650/1100 volt grade 25 sq mm 3½ core/ 4 core or suitable rating XLPE insulated Armoured Aluminium cable from Main L.T PCC panal to LT MCC PANEL at Pond Pumping Station. |
| 270 | LT MCC PANEL exclusively for WTP with required cabling shall be covered in the Lump-Sum Cost given in Budgetary Offer of 10 MLD W.T.P. with Civil & E/M works scope. So their separate inclusion in this estimate is denied. |
| 271 | Complete Double earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with Copper Earth Plates, wateringorpipe and loop earthing (PS-702) for (02 Nos for HT panel, 04 nos. for each Transformers + 06 No.for Main LT PCC Panel, MCWR Panel, Pond P.S. panel and other loads) size of earthing plate 600mm x 600mm x3 mm with salt and coal embodying 3 mtr. below the GL. |
| 272 | Installation of all above substations equipments such as HT Panels , all Transformers with RCC Platform complete with Iron meshing around them and all L.T. panels including all labor T&P complete in all respect. |
| 273 | Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core or suitable rating for 11 KV H.T. XLPE cable |
| 274 | Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core or suitable rating for 11 KV H.T. XLPE cable |
| 275 | NOC from Electrical safety department for all field installations such as pumping plants, substation etc. |
| 276 | Testing of all above E/M equipments at OEM Workplace such as transformer, HT Panels and main LT Panel as per direction given by Engineer-Incharge. |
| 277 | Commissioning of all above E/M equipments etc. complete |
| 278 | PUMPING PLANT AND ACCESSORIES FOR MCWR |
| 279 | Supply of Vertical type self-oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 21 mtr/suitable length column assembly, with vertical hollow shaft.Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-(NOTE- Pump Discharge, Head & motor HP are tentative and may vary as per actual site condition at the time of execution.) |
| 280 | Zone-1: 1750 LPM / 42Mtr. HEAD and coupled with suitable rating of MOTOR (2w+1s) |
| 281 | Zone-2: 1700 LPM / 68Mtr. HEAD and coupled with suitable rating of MOTOR (2w+1s) |
| 282 | Zone-3: 1100 LPM / 55Mtr. HEAD and coupled with suitable rating of MOTOR (2w+1s) |
| 283 | MAIN PIPING AND SPECIALS :- |
| 284 | Zone-1 |
| 285 | Cast iron pipes & specials. |
| 286 | Supply of galvanized nut- Bolt SS-304 and rubber packing material required for erection. |
| 287 | Zone-2 |
| 288 | Cast iron pipes & specials. |
| 289 | Supply of galvanized nut- Bolt SS-304 and rubber packing material required for erection. |
| 290 | Zone-3 |
| 291 | Cast iron pipes & specials. |
| 292 | Supply of galvanized nut- Bolt SS-304 and rubber packing material required for erection. |
| 293 | Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes |
| 294 | Zone-1 |
| 295 | Valve actuator of size :- 150mm for pumps or as per site condition. |
| 296 | Valve actuator of size :- 200mm for common header or as per site condition. |
| 297 | Zone-2 |
| 298 | Valve actuator of size :- 150mm for pumps or as per site condition. |
| 299 | Valve actuator of size :- 200mm for common header or as per site condition. |
| 300 | Zone-3 |
| 301 | Valve actuator of size :- 100mm for pumps or as per site condition. |
| 302 | Valve actuator of size :- 150mm for common header or as per site condition. |
| 303 | Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing . |
| 304 | Zone-1 |
| 305 | 150mm dia or as per site condition. |
| 306 | 200mm dia or as per site condition |
| 307 | Zone-2 |
| 308 | 150mm dia or as per site condition. |
| 309 | 200mm dia or as per site condition |
| 310 | Zone-3 |
| 311 | 100mm dia or as per site condition. |
| 312 | 150mm dia or as per site condition. |
| 313 | CI Dismantling joints |
| 314 | Zone-1 |
| 315 | Valve actuator of size :- 150mm for pumps or as per site condition. |
| 316 | Valve actuator of size :- 200mm for common header or as per site condition. |
| 317 | Zone-2 |
| 318 | Valve actuator of size :- 150mm for pumps or as per site condition. |
| 319 | Valve actuator of size :- 200mm for common header or as per site condition. |
| 320 | Zone-3 |
| 321 | Valve actuator of size :- 100mm for pumpsor as per site condition. |
| 322 | Valve actuator of size :- 150mm for common header or as per site condition. |
| 323 | CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable. |
| 324 | Zone-1: 200mm. Dia or as per site condition. |
| 325 | Zone-2: 200mm. Dia or as per site condition. |
| 326 | Zone-3: 150mm. Dia or as per site condition. |
| 327 | POWER & CONTROL CABLES: |
| 328 | Supply & Laying of 1100V grade, 3C/3.5C x25 mm2 or suitable rating XLPE insulated Copper Multistrand conductor Armoured cable from LT MCC control panel to Starter Panel to respective motor with lugs for Zone-1. |
| 329 | Supply & Laying of 1100V grade, 3C/3.5C x35 mm2 or suitable rating XLPE insulated Copper Multistrand conductor Armoured cable from LT MCC control panel to Starter Panel to respective motor with lugs for Zone-2. |
| 330 | Supply & Laying of 1100V grade, 3C/3.5C x25 mm2 or suitable rating XLPE insulated Copper Multistrand conductor Armoured cable from LT MCC control panel to Starter Panel to respective motor with lugs for Zone-3. |
| 331 | Control cable 1*10C, 2.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc. for 06 Nos. Total pumps. |
| 332 | A.P.F.C PANEL : |
| 333 | Supply of microprocessor based Automatic power factor correction relay panel, IEC/EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , APFC relay in suitable steps, self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 100 KVAR or suitable rating. |
| 334 | CE/UL Certified level transmitter for MCWR:- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68 |
| 335 | CE/UL Certified Pressure transmitter for Total pumps delivery (09nos.)and common header(03 nos.) :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 336 | Complete earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with Copper Earth Plates, watering pipe and loop earthing (PS-702) for the 09 nos. Pumps/equipment & other loads of MCWR. Size of earthing plate 600mm x 600mm x3 mm with salt and coal embodying 3 mtr. below the GL. |
| 337 | Tools & Plants-. As per requirments & specified in tender documents and Schedules or direction given by Engineer-Incharge. |
| 338 | E.O.T. crane of 3 Tonne capacity having span 9m. and lift 6 m. along with gantry girders, chain pulley block and geared trolley complete in all respect for pump house. |
| 339 | Rubber mats for electrical insulation purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness |
| 340 | Cable trench Chequerred plate |
| 341 | Fire fighting equipments 4.5 Kg such fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board. |
| 342 | Internal & External electrification of MCWR pumping station :- |
| 343 | Indoor Lighting |
| 344 | Internal electrification of MCWR Pump House& other rooms with complete Wiring, Mid power SMD type 36W LED Light, fixture made from CRCA sheet steel housing, fittings etc.complete in all respect. |
| 345 | Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required. |
| 346 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 347 | Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required. |
| 348 | Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. |
| 349 | with regulator |
| 350 | Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. |
| 351 | 450mm sweep (900/1400 RPM) |
| 352 | Outdoor Lighting |
| 353 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 354 | Supply and fixing of HPSV/MV 125 watt fixture with lamp and its all accessories. |
| 355 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting system. |
| 356 | Supply and laying of 6 mm2 Al. unarmoured cable flat PVC insulated used for connection of lights fitted to junction boxes. |
| 357 | Earthing of street light pole (SOR-41) |
| 358 | Painting of street light (P5-634) |
| 359 | Outdoor Electrification with complete wiring of Pump house, and room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc. |
| 360 | Feeder pillar for lighting. |
| 361 | Installation of all above E/M equipments and Pumps etc. complete. |
| 362 | Testing of all above E/M equipments at OEM Workplace & At Site complete at works & site as per direction given by Engineer-Incharge. |
| 363 | Commissioning of all above E/M equipments etc. complete |
| 364 | PUMPING PLANT AND ACCESSORIES FOR STORAGE POND PUMPING STATION |
| 365 | Supply of Vertical type self-oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 21 mtr/suitable length column assembly, with vertical hollow shaft.Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :- |
| 366 | 3450 LPM / 11 Mtr. HEAD / 20 HP MOTOR (2w+2s) |
| 367 | MAIN PIPING AND SPECIALS :- |
| 368 | Cast iron pipes & specials. |
| 369 | Supply of galvanized nut- Bolt SS-304 and rubber packing material required for erection. |
| 370 | Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes |
| 371 | Valve actuator of size :- 200mm for pumps or as per site condition. |
| 372 | Valve actuator of size :- 300mm for common header or as per site condition. |
| 373 | Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing . |
| 374 | Valve actuator of size :- 200mm for pumps or as per site condition. |
| 375 | Valve actuator of size :- 300mm for common headeror as per site condition. |
| 376 | CI Dismantling joints |
| 377 | Valve actuator of size :- 200mm for pumps or as per site condition. |
| 378 | Valve actuator of size :- 300mm for common headeror as per site condition. |
| 379 | CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable. |
| 380 | 300mm. Dia or as per site condition. |
| 381 | POWER & CONTROL CABLES: |
| 382 | Supply & Laying of 1100V grade, 3C/3.5C x10 mm2 or suitable rating XLPE insulated Aluminium Multistrand conductor Armoured cable from LT MCC control panel to Starter Panel to respective motor with lugs. |
| 383 | Control cable 1*10C, 2.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc. for 03 Nos. Total pumps. |
| 384 | A.P.F.C PANEL : |
| 385 | Supply of microprocessor based Automatic power factor correction relay panel, IEC/EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , APFC relay in suitable steps, self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 15 KVAR |
| 386 | CE/UL Certified level transmitter for Pumping Station:- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68 |
| 387 | CE/UL Certified Pressure transmitter for Total pumps delivery (03nos.)and common header(01 nos.) :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68 |
| 388 | Complete earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with Copper Earth Plates, watering pipe and loop earthing (PS-702) for the 03 nos. Pumps/equipment & other loads of MCWR. Size of earthing plate 600mm x 600mm x3 mm with salt and coal embodying 3 mtr. below the GL. |
| 389 | E.O.T. crane of 2 Tonne capacity having span 7m. and lift 6 m. along with gantry girders, chain pulley block and geared trolley complete in all respect for pump house. |
| 390 | Rubber mats for electrical insulation purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness |
| 391 | Cable trench Chequerred plate |
| 392 | Fire fighting equipments 4.5 Kg such fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board. |
| 393 | Internal & External electrification of pumping station :- |
| 394 | Indoor Lighting |
| 395 | Internal electrification of Pump House & others with complete Wiring, Mid power SMD type 36W LED Light, fixture made from CRCA sheet steel housing, fittings etc.complete in all respect. |
| 396 | Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required. |
| 397 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 398 | Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required. |
| 399 | Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. |
| 400 | with regulator |
| 401 | Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. |
| 402 | 450mm sweep (900/1400 RPM) |
| 403 | Outdoor Lighting |
| 404 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 405 | Supply and fixing of HPSV/MV 125 watt fixture with lamp and its all accessories. |
| 406 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting system. |
| 407 | Supply and laying of 6 mm2 Al. unarmoured cable flat PVC insulated used for connection of lights fitted to junction boxes. |
| 408 | Earthing of street light pole (SOR-41) |
| 409 | Painting of street light (P5-634) |
| 410 | Outdoor Electrification with complete wiring of Pump house & room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc. |
| 411 | Feeder pillar for lighting. |
| 412 | Installation of all above E/M equipments and Pumps etc. complete. |
| 413 | Testing of all above E/M equipments at OEM Workplace & At Site complete at works & site as per direction given by Engineer-Incharge. |
| 414 | Commissioning of all above E/M equipments etc. complete |
| 415 | Automation For Raw Water Pumping Station Cum Intake Well |
| 416 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each ZPS/ OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. ( 02 RTUs working in module of 01 working & 01 standby so that during the fault in one RTU will not hamper the automatic operation of pumps.) |
| 417 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 418 | CE & UL certified Inteligent Smart Energy Meter for each pump |
| 419 | Soft starter with RS-485 port-400V Class suitable rating for each pump |
| 420 | Auto Phase reversal unit with inbuilt time delay suitable rating for pump |
| 421 | CE & UL certified Surge protector for control panel |
| 422 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 423 | Complete cabling of CWR including all power and control cables of all equipment at CWR and OHT . |
| 424 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) complete with all necessary switchgears inclusive of provision of separate incoming and outgoing for both RTUs distinguishably) |
| 425 | Security Survelliance IP Camera with recorder. |
| 426 | Installation, commissioning & testing for CWR |
| 427 | Trial run for three month period for one CWR |
| 428 | MASTER CONTROL STATION (M.C.S.) AT W.T.P. CAMPUS |
| 429 | CE & BIS approved manufacturer's industrial grade LED monitor size 65\\" with latest configuration as per specification mentioned in tender documents. |
| 430 | Desktop/PC with i7 processor as per specification mentioned in tender documents. |
| 431 | CE/UL approved manufacturer's 5 KVA UPS with batteries as per specification mentioned in tender documents. |
| 432 | Full development version of required TAGS SCADA software suitable for digital and analog input/output features with customization of software as per requirement as per spec. mentioned with unlimited digital and analog Input/Output features specified in detailed technical document with customization of software as requirement |
| 433 | CE & UL approved manufacturer's control room PLC with Redundant CPU & power supply at MCS in IP54 enclosure as per specification mentioned in tender documents. |
| 434 | CE/UL certified field gateway agent for transfering data from MCS to Central control room(C.C.R.) Lucknow. |
| 435 | GSM based wireless / broadband/Equipment communication system for PLC capable to transfer and retreive data & gather data from remote sites to control stations, including all accessories complete. All accessories included signal enhancer antenna along with running expenses till DLP. |
| 436 | CE/UL approved manufacturer's Firewall for network protection |
| 437 | Surge protector for ethernet communication protection |
| 438 | CE/UL approved manufacturer's industrial grade ethernet switch |
| 439 | Mobile App facility system architecture complete.( industries internet based & viewed through mobile apps for increased local & remote visibility) |
| 440 | Canon/HP/equivalent latest Laser printer |
| 441 | Security Survelliance IP camera with DVR. |
| 442 | Installation, testing and commissioning with required furniture,Air Conditioner etc. |
| 443 | Test and trial run of whole system. |
| 444 | AUTOMATION FOR MCWR CONTAINING TOTAL 09 NOS. PUMPS |
| 445 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each ZPS/ OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. ( 01 RTU for 03 nos. Pumps) |
| 446 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 447 | CE & UL certified Inteligent Smart Energy Meter for each pump |
| 448 | Soft Starter- |
| 449 | Soft starter with RS-485 port-400V Class suitable rating for each pump of Zone-1 |
| 450 | Soft starter with RS-485 port-400V Class suitable rating for each pump of Zone-2 |
| 451 | Soft starter with RS-485 port-400V Class suitable rating for each pump of Zone-3 |
| 452 | Auto Phase reversal unit with inbuilt time delay and enclosure (125Amp.) |
| 453 | CE & UL certified Surge protector for control panel |
| 454 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 455 | Complete cabling of CWR including all power and control cables of all equipment at CWR and OHT . |
| 456 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) complete with all necessary switchgears etc. |
| 457 | Security Survelliance IP Camera with recorder. |
| 458 | Installation, commissioning & testing for ZPS |
| 459 | Trial run for three month period for one ZPS |
| 460 | AUTOMATION FOR STORAGE POND PUMPING STATION CONTAINING TOTAL 03 NOS. PUMPS |
| 461 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each ZPS/ OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. ( 01 RTU for 02 nos. Pumps) |
| 462 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 463 | CE & UL certified Inteligent Smart Energy Meter for each pump |
| 464 | Soft starter with RS-485 port-400V Class suitable rating for each pump. |
| 465 | Auto Phase reversal unit with inbuilt time delay suitable rating for pump |
| 466 | CE & UL certified Surge protector for control panel |
| 467 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 468 | Complete cabling of CWR including all power and control cables of all equipment at CWR and OHT . |
| 469 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) complete with all necessary switchgears . |
| 470 | Security Survelliance IP Camera with recorder. |
| 471 | Installation, commissioning & testing for ZPS |
| 472 | Trial run for three month period for one ZPS |
| 473 | Trial Run & Maintenance of Three Months including operation,staff and chemical charges for Raw Water Pumping Station Cum Intake Well & WTP with MCWR(excluding electricity charges) . Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail