Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | OVER HEAD TANK |
| 2 | Submission of design, drawing and supply of all material, labour T&P etc. to construction of as per tenderer's own seismic proof design and drawings (approved by the department) complete intz type R.C.C. Over Head Tank with following capacity and staging on raft or pile or pile cum raft foundation with columns and braces of staging from made up ground level at site to the top of bottom ring beam of tank, with a minimum free board of 15cm. The design of the tank shall be based on safe bearing capacity of soil at site i.e. 8.0 T/m2 (datum) and depth of foundation as 2.50m (datum) from existing ground level on pile/raft foundation. Made up level of OHT will be taken as 0.60 m above existing gound level. Extra earth for filling of made up level will be arranged by the contractor at his own cost. The height of staging will be considered from the made up ground level to the ring beam (Top Face) of bottom dome. B.C. above given is tentative, contractor will have to test the B.C. and design of O.H.T. will be on actual B.C. found or 8.0 T/m2 which ever is less . All other details of tank not covered here shall also be as per specifications enclosed. The specifications for O.H.T. will be as follows :- |
| 3 | Submission of detailed design and drawing from any recognized University such as I.I.T. etc. or as per direction of Engineer in-charge.1. Minimum grade of concrete for whole structure-M30 2. Minimum grade of Steel for whole structure-Fe 550 TMT bars |
| 4 | R.C.C. O.H.T. as per approved design including fixing various pipes and ventilator at top and fixing of M.S. sheet of 8 mm gauge around manhole cover of 60cm x 60cm size with frame and locking arrangement and railing in three rows with 20mm OD medium quality GI pipe including supply of all material,labour,T&P etc.all complete. |
| 5 | Two column based R.C.C. vertical stair case with 1.0 m minimum clear width as an access to Balcony and Top Dome of tank from ground level as per design & drawing with 1.25 m high railling in three rows with 20mm OD medium quality GI pipe and gate with cabin made up of 60mmx60mmx6mm angle iron and 25mmx25mm square iron jali as per specification including supply of all materials. |
| 6 | Supply and fixing of S.S-316 ladder 60mmx60mmx6mm angle iron and 20mm dia bar from top of roof of top dome to inside the tank in a slope of 3:1 (3 vertical : 1 horizontal) with railing as specified and supply & fixing of SS bar cover for pipe opening inside the tank with all labour, T&P etc. complete. |
| 7 | Railing on staircase & its landings, all around balcony & top dome for access up to ventilator as specifications including supply of all material. Railing shall be provided in three rows of medium class G.I. pipe of 20mm dia and MS angle iron (60x60x6mm) should be provided in 1.25 m height with 1.2 m centre to centre on both sides of the stair case with embedded in concrete 1:1:2, MS gate should be provided as entrance of stair case with locking arrangement. |
| 8 | Supply and fixing of lightening conductor and earth plate etc. as per specifications. |
| 9 | Testing of tank for water tightness as per specifications enclosed including supply of water. If water for testing is made available by department, the cost of Rs. 100.00 per KL will be deducted from the contractor's bill. |
| 10 | Supply of all materials and construction of 80mm thick R.C.C. floor 1:1 1/2:3, R.C.C. apron and 20 cm dia semi circular drain around apron in a slope towards wash out chamber on 75 mm thick base concrete in 1:2:4 (cement:coarse sand: 40 mm stone ballast). |
| 11 | Three coats of approved quality and shade of Apex Painting as per direction of Engineer incharge over exposed surface of tank work including supply of all material, labour, T&P complete as required. |
| 12 | Three coats of anti corrosive / aluminum / black Japan paint of approved quality on all iron work including supply of all material, labour and T&P etc. |
| 13 | Suplly of all materials, labour, T&P and construction of brick masonry sluice valve chambers including fixing R.C.C. cover as per deptt. Type design for the all inlet, outlet and washout pipes. The R.C.C. cover shall be casted in M.S. Channel section with handles on both sides. (Sluice valve chamber for over flow & wash out may be combined) |
| 14 | The words U.P. Jal Nigam, year of construction of , capacity of O.H.T., Logo of AMRUT 2.0 and slogan approved by Engineer in charge shall be painted prominently in letter not less than 30 cm. in height.(1 Nos.) |
| 15 | Maintenance for 12 months inclucding supply of all materials etc. complete. |
| 16 | Other specifications which are required for construction of O.H.T., given by UP Jal Nigam Engineer In-charge time to time will be followed by contractor. |
| 17 | Zone 11100 KL/24.0 M Staging Supply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 300 mm diaOutlet Pipe 400 mm dia Overflow Pipe 400 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 400 mm dia Washout Pipe 100 mm dia |
| 18 | Zone 2900 KL/24.0 M StagingSupply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 150 mm diaOutlet Pipe 350 mm dia Overflow Pipe 300 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 350 mm dia Washout Pipe 100 mm dia |
| 19 | Zone 3800 KL / 22 m Staging Supply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 150 mm diaOutlet Pipe 300 mm dia Overflow Pipe 300 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 300 mm dia Washout Pipe 100 mm dia |
| 20 | Zone 51100 KL / 22 m Staging Supply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 300 mm diaOutlet Pipe 400 mm dia Overflow Pipe 400 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 400 mm dia Washout Pipe 100 mm dia |
| 21 | Zone 6600 KL / 22 m Staging Supply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 150 mm diaOutlet Pipe 250 mm dia Overflow Pipe 200 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 250 mm dia Washout Pipe 100 mm dia |
| 22 | Zone 7500 KL / 22 m Staging Supply, carting and fixing of following sizes D.I. D/F pipes (K-9) with required specials such as reducers, duck foot bend, bell mouth etc. from water container body as per norms upto the sluice valve chamber in the tank including supply of M.S. clamps, rubber insertion sheet, nut bolts, washer etc. complete as per specifications, (details given below). It also includes the provision of making byepass arrangement from CWR to all outlets of OHT including supply & fixing of all required materials & specials etc complete.Inlet Pipe 150 mm diaOutlet Pipe 250 mm dia Overflow Pipe 200 mm diaWashout Pipe 100 mm diaSupply and fixing of following sizes D.I. D/F sluice valves as per relevent latest I.S. specifications including supply of all jointing and other materials such as rubber insertion sheet, nut bolts, washer etc. complete as per specifications.(details given below)Outlet Pipe 250 mm dia Washout Pipe 100 mm dia |
| 23 | For every one meter increase or decrease of height of staging of O.H.T. |
| 24 | (i) for increase |
| 25 | (ii) for decrease |
| 26 | For every 0.5 meter increase or decrease in depth of foundation of O.H.T. from natural G.L. (specific/datum depth is 2.5 m from G.L.) |
| 27 | (i) for increase |
| 28 | (ii) for decrease |
| 29 | REPAIRING OF EXISTING OVER HEAD TANK |
| 30 | Providing and erection of scaffolding and shuttering material like challi, gurra, nail, bans, ballia, patra etc. required for complete of work on all surface area of OHT from top dome to G.L. so as to give strong and safe plateform to workers to work on all part of OHT for repair and strengthning as per direction of engineer in-charge. |
| 31 | Cleaning of exposed concrete surface of loose and foreign materials by means of sand blasting with coarse sand and including cleaning with all blast upto a height of 18 M above plinth level. |
| 32 | Provide semi circular drain of 200 mm dia all around the O.H.T. flooring consisting of cement concrete with 20mm gauge approved stone grit, coarse sand, cement in proportion of 1:2:4 including supply of all material, labour, T&P etc. required for proper completion of the work as per direction and satisfaction of Engineer Incharge. |
| 33 | Supply and fixing ventilator jali at O.H.T. including repairing of the ventilator and fixing the same properly including supply of all material, labour, T&P etc. required for proper completion of the work. |
| 34 | Supply and fixing of fabricated M.S. angle iron ladder consisting of 50x50x6mm angle iron and 20mm dia plain M.S. bar of 45 cm wide for a required length and painted with anti corrosive paint and fixing the same in the tank body including supply of all materials, labour, T&P etc. required for proper completion of the work as per direction of Engineer Incharge. |
| 35 | Supply and fixing of 20mm dia medium quality of G.I. pipe railing with M.S. angle iron post of section 50x50x6mm and 1.00 M height including grouting the angle iron post properly and fixing the pipe railing including supply of all material, labour, T&P etc. required for proper completion of the work as per direction of Engineer Incharge. |
| 36 | New Pipe Railing ¾\\" (20mm) dia medium quality. |
| 37 | Repair of Old Railing. |
| 38 | M.S. angle iron for single row post 50x50x6x1.25m height |
| 39 | Supply and fixing of following devices of the O.H.T. including cutting of hole for cleats to fix the same properly and including supply of all material, labour, T&P etc. and fixing the appliances in the cleats with screw or nails etc. |
| 40 | Water level indicator complete with marked scale. |
| 41 | Lightening Conductor. |
| 42 | Injection grouting in vertical surface/wall placing and fixing nozzle by drilling machine in tank wall having minimum dia of nozzle 15mm and provide on a regular interval not exceeding 1m including construction joints. Injection of pidicrete AM (Ploymer based on shrinkage high strength grout) admixed with cement through nozzle under pressure by sump @ 250gms per bag of cement sealing the nozzle after grouting with Ploymer product mixed with cement, making tank body in working and seapage free condition. |
| 43 | Painting the iron work in small area with one coat of anti corrosive primer coat and two coat of approved enamel paint including supply of all material, labour, T&P etc. required for proper completion of the work as per satisfaction of Engineer Incharge. |
| 44 | Railing of stair case and balcony with iron post and two rows of G.I. pipe 20mm dia. |
| 45 | Painting with approved quality Black Japan paint, inlet, outlet, washout pipe, over flow, pipe 100mm dia to 350mm dia. |
| 46 | Painting of outer surface of OHT with weather proof paint (like apex etc.) as per direction of engineer in-charge. |
| 47 | Zone-4 |
| 48 | 150KL/22M Staging |
| 49 | Supply of all material. Labour and T&P for repairing of OHT of 150 kl/22 m capacity including all items as per following. |
| 50 | CWR with ZONAL PUMPING STATION (ZPS) |
| 51 | Supply of all materials, labour and T&P etc. complete for the construction of Ground RCC CWR of following capacity & with 1.00m wide P.C.C. appron around with 20 cm semi circular C.C.(1:2:4) drain M.S. ladder with hand rails out side and inside the tank body proper ventilators at top, water level sensor, Lightening conductor as per latest I.S.I. or electricity rules, 1150mm dia medium pattern M.S. Manhole cover hinged with locking arrangement fixing and jointing vertical DI D/F, pipes, specials and duck foot bends of required size for inlet. |
| 52 | Supply and fixing of outlet sluice valve and wash out sluice valves with all jointing materials for proper completion and other appurtenant works including excavation in all type of soil & in rock etc. painting on exposed weather coat paint, painting of pipes and ladder with approved anticorrosive paints also including testing of the CWR including carriage of construction of materials by truck/ head load etc. upto site of work on 8 t/sqm tentative bearing capacity of soil (testing of BC of soil included) including fixing of overflow pipe |
| 53 | Supply and laying of pipe upto a suitable place and including construction of drainage system for emptying of CWR for cleaning & repairs and maintenance.construction of R.C.C. framed Pump house with Supply of all materials labour T&P etc. over CWR as per approved design, drawing and standard specifications with 1 m wide PCC appron around along with 15 cm semicircular CC (1:2:4) drains, RCC wall upto plinth level, to roof of pump house. |
| 54 | RCC floor, foundation and roof, 2m wide RCC plateform at plinth level, stair case from plateform to floor of pump house, railing on the stair case and CWR Walls and plateform foundation block of pumping plant RCC columns with bracket and longitudinal RCC beams to support moving gantry crane, plastering in the inner and outer brick masonry wall, flooring supply and fixing of doors, windows ventilators, painting on explosed surface with three coats of approved weather coat paint, acrylic emulsion in the inner surface, painting of door, windows ventilators, etc. supply and fixing of DI down pipes from roof to GL and other appurtenant works required to complete the pump house in all respect. |
| 55 | Zone 1 , 300 KL |
| 56 | Zone 5 , 300 KL |
| 57 | Testing of bearing capacity of soil from a reorganized Govt. Engineering College or as PER directed by department. |
| 58 | RISINGMAIN & DISTRIBUTION SYSTEM |
| 59 | Dismantling/Cutting of following types of road surface including sorting out of serviceable material and its stacking at a suitable place. |
| 60 | B.O.E. Road |
| 61 | Bituminous Road |
| 62 | C.C./R.C.C. Road |
| 63 | Interlocking Tiles Road |
| 64 | Excavation for pipe line trenches in ordinary soil,(lime, clay or sand including lift up to 1.5m and lead up To 50m and refilling, watering, ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 65 | Excavation for pipe line trenches in Mixed soil,(Bajri,Kankar & Moorum including lift up to 1.5m and lead up To 50m and refilling, watering, ramming of excavated earth in to trenches and disposal of surplus earth up to 50 m from the center of the foundation trenches. |
| 66 | Supply of High Density Polyethelene Pipes (HDPE (PN-6) /PE-100)), conforming to IS 4984 / 14151 / 12786 / 13488 in coils / standard lengths F.O.R. desination rates per meter, inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation unloading & stacking the same etc. complete. |
| 67 | 110 mm dia HDPE pipe 6 Kg/Sqcm. |
| 68 | 140 mm dia HDPE pipe 6 Kg/Sqcm. |
| 69 | 160 mm dia HDPE pipe 6 Kg/Sqcm. |
| 70 | Supply of ISI mark DI pipes (push on joints pressure pipes of D.I of following class and diameters confirming to the I.S. specification inclusive cost of jointing materials (Rubber gasket of EPDM Quality) including Third party inspection charges, Transit insurance, Railway Freight, Unloading from railway wagon, Loading into Truck, Transportation to departmental store / site of work, unloading, stacking etc. completed as directed by Engineer –in-charge (IS 1536 / 2001 for pipes and IS 158 / 1969 and IS 12820 / 1989 or latest edition / revision with amendments for Rubber Gaskets. |
| 71 | D.I. Pipe (Class K-7) |
| 72 | 200 mm dia D.I. K-7 |
| 73 | 250 mm dia D.I. K-7 |
| 74 | 300 mm dia D.I. K-7 |
| 75 | 350 mm dia D.I. K-7 |
| 76 | 400 mm dia D.I. K-7 |
| 77 | D.I. Pipe (Class K-9) |
| 78 | 150 mm dia D.I. K-9 |
| 79 | 300 mm dia D.I. K-9 |
| 80 | Supply of the following sizes of D.I. D/F Sluice Valves conforming to latest/ relevant I.S. Specifications destination including F.O.R. destination and all taxes and insurance etc. with loading, unloading and carting up to site of work. |
| 81 | 400 mm dia |
| 82 | 350 mm dia |
| 83 | 300 mm dia |
| 84 | 250 mm dia |
| 85 | 200 mm dia |
| 86 | 150 mm dia |
| 87 | 125 mm dia |
| 88 | 100 mm dia |
| 89 | Supply of the following sizes of C.I. Double flanged scour valves as per I.S. 780 class-1 working pressure 10 kg/Sqcm F.O.R Destination including Transit insurance, Railway Freight, Unloading from railway wagon, Loading into Truck, Transportation to departmental store / site of work, unloading, stacking etc. |
| 90 | 100 mm dia |
| 91 | Supply of 50mm dia Single ball type air valve with gun metal seat at site store including Transit insurance, Railway Freight, Unloading from railway wagon, Loading into Truck, Transportation to departmental store / site of work, unloading, stacking etc. |
| 92 | Supply of Sluice valve type fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete at site including Transit insurance, Railway Freight, Unloading from railway wagon, Loading into Truck, Transportation to departmental store / site of work, unloading, stacking etc. |
| 93 | Laying & Jointing of the following types and sizes of pipes including supply of all electrofusion fittings, D.I. Specials & jointing materials as per site requirement . All jointing work in HDPE Pipe must be carried out using electrofusion process ( Including availability of electrofusion jointing apparatus & supply of electricity using generator etc ) conforming to IS 4984/2016, IS 8329/2000 or their amendment including railway freight, insurance charges F.O.R. up to destination. |
| 94 | H.D.P.E. PIPE (6kg/cm2) PE-100 |
| 95 | 110 mm dia |
| 96 | 140 mm dia |
| 97 | 160 mm dia |
| 98 | D.I. Pipe (Class K-7) |
| 99 | 200 mm dia D.I. K-7 |
| 100 | 250 mm dia D.I. K-7 |
| 101 | 300 mm dia D.I K-7 |
| 102 | 350 mm dia D.I. K-7 |
| 103 | 400 mm dia D.I. K-7 |
| 104 | D.I. Pipe (Class K-9) |
| 105 | 150 mm dia D.I. K-9 |
| 106 | 300 mm dia D.I K-9 |
| 107 | Carting of D.I. D/F Sluice valves of Following sizes to the site of works Lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete Excluding valves and specials Required but including the testing etc. complete. |
| 108 | 400 mm dia |
| 109 | 350 mm dia |
| 110 | 300 mm dia |
| 111 | 250 mm dia |
| 112 | 200 mm dia |
| 113 | 150 mm dia |
| 114 | 125 mm dia |
| 115 | 100 mm dia |
| 116 | Carting of D.I. D/F Scour valves to the site of works lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding valves and specials Required but including the testing etc. complete |
| 117 | 100 mm dia |
| 118 | Carting of 50 mm dia Signle ball type air valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding valves and specials Required but including the testing etc. complete. |
| 119 | Carting of 80 mm dia flanges fire hydrant of the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding valves and specials Required but including the testing etc. complete. |
| 120 | Supply of all materials, labour T&P etc. required for construction of of sluice valve / scour valve chamber with proper working space, including excavation of earthwork, Ist class brickwork, plaster (1:4 cement, coarse sand mortar), heavy duty M25 grade RCC Cover ( 200 mm thick with double reinforcement), as per instructions of engineer-incharge. |
| 121 | Surface box type |
| 122 | Masonry type |
| 123 | Supply of all materials, labour T&P etc. required and construction of 350 x 350 x 500 mm size air valve chamber as per type design including supply and fixing the 500 mm dia MS manhole cover. |
| 124 | Supply of all materials, labour T&P etc. required and construction of 750 x 750 x 1000 mm size fire hydrant chamber as per type design including supply and fixing the 500 mm dia MS manhole cover. |
| 125 | Road Crossing By Trenchless Method (HDD) ‐ Excavation in foundation of trench of proper size in soil mixed with moorum, Shingle, Kankar, soft rock, hard rock, including refilling, dressing and ramming earth or sand or bajri, ballast, including providing, supply, carting, lowering, laying and jointing of casing pipe of M.S. with appropriate size, with rubber ring joint, sand filling in gap inside M.S. pipe, insertion of distribution pipe into the encasing pipe including supply of T&P, including concrete of 150 mm thick in with 40mm gauge brick ballast local sand and cement in proportion of 8:4:1, provision for barricading, labour for traffic diversion etc. Complete for proper completion of work as per instruction of Engineer. |
| 126 | 200mm dia MS pipe upto 2 mtr depth |
| 127 | 300mm dia MS pipe upto 2 mtr depth |
| 128 | 400mm dia MS pipe upto 2 mtr depth |
| 129 | Provision for crossing (1.5m-3.0 m width) of nala & culverts including shiftijng of telephone cabel etc.along the alignment of pipe line including supply, laying & jointing of D.I. casing pipe of 150mm dia and special and also jointing material, their laying and jointing testing etc. complete |
| 130 | Provision for Large crossing (1.5m-3.0 m width) of nala & culverts including shiftijng of telephone cabel etc.along the alignment of pipe line including supply, laying & jointing of D.I. casing pipe of 200mm dia and special and also jointing material, their laying and jointing testing etc. complete |
| 131 | Construction of house connections |
| 132 | Making of ferrule connection in 50 to 400 mm nominal dia. distribution mains with electrofusion saddle piece having electro fused adapter, service connections, fittings and fixing of ferrule of 15mm size including tapping of the main and cost of bailling out of water. The above work includes supply, carting, laying & jointing/fitting of 20 mm G.I. Pipe , 20 mm H.D.P.E. Pipe (as per site required length) ,G.I. elbows for jointing of G.I. pipe, 1 No. HDPE saddle (for HDPE dia of existing pipe upto 200 mm) /MS clamp (for dia of existing pipe DI/CI above 200 mm), 1 No. 15 mm brass ferrule /F.C.V. SS - 316 conforming to relevant IS Specifications and 1 No. HDPE adopter, 1 Nos. FTPP Compressor Elbow, 1 No. PTMT Bib Cock along with all labour, T&P etc. required for proper completion of work Including excavation (Excluding dismantling / reinstatement of roads) and also submission of single set of GPS locationwise house connections photographs in soft & hard copy. |
| 133 | For New Pipe Line |
| 134 | Up to 110mm dia |
| 135 | For 125 mm to 140mm dia |
| 136 | For 160 mm to 180mm dia |
| 137 | For 200mm to 250mm dia |
| 138 | For 300mm to 350mm dia |
| 139 | Supply of all materials, labour, T & P etc. required and construct thrust blocks at the bends and below the Valves. |
| 140 | Permanent reinstatement of roads including all material, labour, T&P etc. complete work. |
| 141 | B.O.E. roads by 40% new bricks and 60% used old brick including all material labour, T&P etc. complete.as per direction of Engineer-In-Charge |
| 142 | Bitumen Road complete as per PWD specification for ODR and direction of Engineer In-charge. |
| 143 | C.C. Road with 150 mm thick CC work (1:2:4) cement, coarse sand & 20mm stone grit over 100 mm thick PCC base (1:4:8) cement, coarse sand & 40mm stone ballast after washing the trench and application of neat cement coat over the edges where ever necessary as per site requirement upto satisfaction of Engineer-In-Charge |
| 144 | Interlocking tiles roads by 40% new Interlocking tiles over 25 mm thick sand bedding including its base preparation with 75 mm thick PCC base (1:4:8) cement, coarse sand & 40mm stone ballast after washing the trench and application of neat cement coat over the edges and locks filled by fine sand and edge gapping filled by CC work (1:2:4) cement, coarse sand & 10mm stone grit where ever necessary as per site requirement upto satisfaction of Engineer-In-Charge. |
| 145 | BUILDING WORKS |
| 146 | Excavation in foundation & plinth in ordinary soil (sand, loam or clay) or kankar mixed soil with lift up to 1.50M and lead up to 50M including refilling watering ramming of excavated earth into the trenches, or into the space between the building and sides of foundation trenches or into the plinth and disposal of surplus earth upto a distance of 50m from the center of foundation trenches. |
| 147 | Laying Plain Cement concrete with 40mm gauge stone ballast, coarse sand and cement in ratio of 12:6:1 in foundation including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 148 | 1st classbrick work in cement & coarse sand sand mortar in ratio 1:6 in foundation and plinth including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 149 | 1st classbrick work in cement & coarse sand mortar in ratio 1:4 in foundation and plinth including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 150 | 20 mm thick damp proof course with cement,approved coarse sand & Stone grit in 1:2:4 cement and coarse sand mortar including 5% water proofing material or as specified. |
| 151 | Sand filling in plinth including supply of necessary quantity of sand from the site of work including loading, unloading and cartage of earth, filling watering, ramming, dressing & leveling, labour, T&P etc. complete as per direction of Engineer Incharge. |
| 152 | 1st Class brick work in 1:6 with cement & coarse sand sand mortar in super structure in one brick thick wall including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 153 | 1st Class brick work in 1:4 with cement & coarse sand mortar in super structure in one brick thick wall including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 154 | Supply and fixing of all materials, labour, T&P etc. required for making door shutters by M.S. sheet 18 gauge, M.S. angle 50x50x6mm size also including angle iron chaukhat with hold fast as instructed by Engineer Incharge including cement, concrete for fixing the same in the walls complete. |
| 155 | R.C.C. work with cement, approved coarse sand and 20mm gauge stone grit in proportion of 1:1.5:3 in the following works excluding supply of reinforcement and its bending but including 0.50mm gauge wire and fixing in position also centering, shuttering, all materials, labour, T&P etc. required for proper completion of work. |
| 156 | Beams |
| 157 | Lintel, Sunshade & Slabs |
| 158 | Columns |
| 159 | Reinforcement work with Fe 550 TMT bars in R.C.C. work wrought to required shape as necessary including its bending and wastage including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 160 | 12mm thick plaster in cement & coarse sand mortar in ratio of 1:6 over brick work minimum thickness not to be less than 10mm including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 161 | On smooth surface |
| 162 | On Rough Surface |
| 163 | 12 mm thick plaster in Cement & Coarse sand mortar in ratio of 1:4 over brick work minimum thickness not to be less than 10mm including supply of all materials, labour, T&P etc. required for proper completion of work. |
| 164 | 12 mm thick cement plaster to ceiling of mix 1:4 cement, coarse sand mortar including supply of all materials, labour, T&P etc. required for completion of work. |
| 165 | 25 mm thick 1:2:4 plain cement concrete floor with cement, coarse sand and 20mm gauge approved stone grit, laid in panels, finished with 3mm thick floating coat of neat cement over 7.5cm thick base concrete consisting of cement and fine sand and first class brick ballast 40mm gauge in proportion of 1:6:12 and removing any over lapping mortar in the joints of the panels if any and giving an uniform finish including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 166 | construction of semi circular C.C. drain 200mm dia as per departmental drawing over 100 mm thick base concrete in 1:4:8 (Cement: Coarse Sand: 40 mm nominal size Coarse Aggregate) with finishing of 3 mm thick floating coat of neat cement including supply of all material, labour, T&P etc. |
| 167 | Supply of all materials, labour, T&P etc. and construction of 80 mm thick Interlockig tiles approach road over 25 mm thick sand bedding including its base preparation with 100 mm thick PCC base (1:4:8) cement, coarse sand & 40mm stone ballast and locks filled by fine sand and edge gapping filled by CC work (1:2:4) cement, coarse sand & 10mm stone grit where ever necessary as per site requirement upto satisfaction of Engineer-In-Charge. |
| 168 | Supply and laying complete 4 cm thick insulation layer of sand and clay over reinforecement concrete roof and 40 mm thick 1:2:4 plain cement concrete floor with cement, coarse sand and 20 mm gauge approved stone grit, laid in panels, finished with 3mm thick floating coat of neat cement over insulation layer including supply of all materials, labour, T&P etc. |
| 169 | Supply & fixing of rolled steel joist 250mm x 125mm and 10mm thick size including its black painting with approved paint and also one coat of primer with all materials, labour, T&P etc. required for proper completion of work. |
| 170 | Provide all materials, labour T&P etc. required for proper completion of work and construct pillars as per type design and fixing of gate 3.6 m wide gate and 1.2 m wide wicket gate.as per type design & drawing |
| 171 | Provide all materials, labour T&P etc. required for proper completion of work and construct pillars as per type design and fixing of gate 3.6 m wide gate.as per type design & drawing |
| 172 | Supply and fixing of rain water P.V.C. Pipe 110 mm 6 Kg/cm2 with bend and clamp etc. complete. |
| 173 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 174 | Apex paint (approved quality) in two coats of approved shade over one primary coat including supply of all materials, labour, T&P etc. required for proper completion of the work. |
| 175 | Painting or varnishing of new iron work with one coat of primer and two coat of approved paint and varnish including supply of all materials, labour, T&P etc. complete in all respect in all floors. |
| 176 | Earth filling including supply of necessary quantity of soil from the site of work including loading, unloading and cartage of earth, filling watering, ramming, dressing & leveling, labour, T&P etc. complete as per direction of Engineer Incharge. |
| 177 | Construction of MCS ROOM as per type Approved design & drawing etc. and (all works will be done as per unit estimate of DPR ) including supply of all materials, labour, T&P etc. required for proper completion of the work. As per direction of engineer-In- incharge. |
| 178 | Construction of Rain Water Harvesting and Ground Water Recharge Unit. As per departmental type design. Including supply of all material, labour, T&P etc. complete in all respects. As per direction of E/I. |
| 179 | E&M WORKS: |
| 180 | New Tubewell |
| 181 | Drilling of borehole for Tubewell contruction by RC Rig Machine including transportation, erection, dismantling of Rig and assoiated T & P complete in all respect including required all material, labour etc. |
| 182 | Transportation, Erection and Dismantling of Rig Machine |
| 183 | Drilling of 500mm size bore from |
| 184 | (i) GL to 100MBGL |
| 185 | (ii) 100M BGL to 120MBGL |
| 186 | Zone testing in water quality problem areas including all required material, labour, T&P etc. complete in all respect. |
| 187 | Tubewell AssemblyM.S. tubewell assembly with all required parts like plain pipe, slotted pipe (as required upto 50% of plain pipes) rings, well cap, bail plug, clamp, reducer, central guide, support structer etc. as required & as per typed design complete in all respect. |
| 188 | 200 mm. Dia MS ERW slotted/ casing pipe having wall thickness of 7.1mm. |
| 189 | Supply of pea gravel |
| 190 | Logging of bore hole by departmental / approved electric logger. |
| 191 | Lowering of Tube well assembly duly welded including welding electrode and shurounding of pea gravel complete in all respect. |
| 192 | Lowering of 200mm dia pipe from GL to 100m deep BGL. |
| 193 | Lowering of 200mm dia pipe from 100 to 110m deep BGL. |
| 194 | Development of Tubewell by compressor |
| 195 | Transportation, Installation and Dismantling of Air Compressor |
| 196 | Development of Tubewell by 250 PSI or requisite Capacity of Air compressor |
| 197 | Development of Tubewell by O.P. Unit |
| 198 | Transportation, Installation and Dismantling of O.P. Unit & Yield Test. |
| 199 | Development of Tubewell by 2 Cusec or requisite Capacity of O.P. Unit |
| 200 | Chemical and Bacterological test of water sample from depaprtmental/ approved lab. |
| 201 | Provision of failed attempt of tubewell construction due to various reasons such as poor strata, less aquifer volume, quality problem area or any other reasons whatsoever encountered during work execution solely subjected to final decision taken by competent authorities. |
| 202 | PUMPING PLANT OVER NEW TUBEWELL WITHOUT CHLORINATING PLANT AT TUBEWELL |
| 203 | SITC of Submersible pumpset (700 LPM discharge 46/47 mtr.head coupled with suitable rating of Motor A.C. Three phase) with 24 m. column pipes, NRV,CI D/F Bend 90*, CI A/F Tee, D/F pipe ( 1.5 m. long 02 nos., 1.0m. Long), Earthing, Painting , Toolset, Wiring of pumphouse internal & external, Chainpulley Block and all Pumping Plant accessories with nut bolts and Rubber packing etc.complete in all respect with all required material, T&P labour etc.(Both discharge & head are tentative may very as per actual site condition) |
| 204 | Servo volltage stabilizer (240-500 v) suitable rating for motor |
| 205 | Motor operated Actuators with Sluice valve of size 100 mm. or suitable size at Main line and Bye-pass line as well. |
| 206 | CE & UL certified Electromagnatic Flowmeter suitable for above line size 100 mm. or suitable size. |
| 207 | Soft starter with RS-485 port-400V Class suitable rating for motor |
| 208 | 3 Mtr. long heavy duty column pipe same as above item no.-1 taken as spare.( 01 No. set has 02 nos. column pipes) |
| 209 | Supply & Laying of Additonal XLPE insulated Copper flat cable size 1x3cx4 sq mm. or suitable size required for above motor for submersible pump set. |
| 210 | Supply & Laying of PVC insulated Al. armoured cable size 1x 3.5/4C x 16 sq mm. or suitable size required from transformer LV side to meter panel and meter panel to starter. |
| 211 | PUMPING PLANT OVER NEW TUBEWELL WITH CHLORINATING PLANT AT TUBEWELL |
| 212 | SITC of Submersible pumpset (700 LPM discharge 66/69 mtr. head coupled with suitable rating of Motor A.C. Three phase) with 24 m. column pipes, NRV,CI D/F Bend 90*, CI A/F Tee, D/F pipe ( 1.5 m. long 02 nos., 1.0 m. Long), Earthing, Painting , Toolset, Wiring of pumphouse internal & external, Chainpulley Block and all Pumping Plant accessories with nut bolts and Rubber packing etc.complete in all respect with all required material, T&P labour etc. (Both discharge & head are tentative may very as per actual site condition) |
| 213 | Servo volltage stabilizer (240-500 v) suitable rating for motor |
| 214 | Motor operated Actuators with Sluice valve of size 100 mm. or suitable size at Main line and Bye-pass line as well. |
| 215 | CE & UL certified Electromagnatic Flowmeter suitable for above line size 100 mm. or suitable size. |
| 216 | Soft starter with RS-485 port-400V Class suitable rating for Motor |
| 217 | 3 Mtr. long heavy duty column pipe same as above item no.-1 taken as spare.( 01 No. set has 02 nos. column pipes) |
| 218 | Supply & Laying of Additonal XLPE insulated Copper flat cable size 1x3cx6 sq mm. or suitable size required for above motor for submersible pump set. |
| 219 | Supply & Laying of PVC insulated Al. armoured cable size 1x 3.5/4C x 16 sq mm. or suitable size required from transformer LV side to meter panel and meter panel to starter. |
| 220 | SITC of Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-6 LPH ( pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 200 ltr capacity HDPE tank (02 nos., 1W+1S) ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution.,chlorine test kit. |
| 221 | S.I.T.C OF SCADA SYSTEM ON A TUBEWELL |
| 222 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each tubewell/ OHT & stand alone OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. |
| 223 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 224 | CE & UL certified Inteligent Smart Energy Meter |
| 225 | Auto Phase reversal unit with inbuilt time delay and enclosure suitable rating of motor. |
| 226 | CE & UL certified Hydrostatic type sub soil water level transmitter for tubewell. |
| 227 | CE & UL certified pressure transmitter |
| 228 | CE & UL certified Surge protector for above control panel |
| 229 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 230 | Complete cabling of tubewell including all power and control cables of all equipment at pump house and OHT . |
| 231 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) |
| 232 | Installation, commissioning & testing for one tubewell |
| 233 | Trial run for three month period for three nos for one tubewell |
| 234 | Trial Run & Maintenance of 03 Months including liquid chlorine & necessary staff required for operation. (excluding electricity charges) |
| 235 | S.I.T.C. OF PUMPING PLANTS & OTHER E/M ITEMS IN PROSPECTIVE TO NEW C.W.R., ZONE-1 |
| 236 | PumpSet at C.W.R: |
| 237 | Supply of Electric Driven self water lubricated V.T. pump 1700 LPM 39 mtr. Head with suitable column pipe complete in all respect with discharge head assembly and strainer complete & coupled with suitable rating of motor VHS induction 50 hz 3 phase AC supply 415+6%-10% volts at speed 1470 RPMMOCSuction Case : CI FG 260 IS: 210 Line Shaft : Stainless Steel AISI 410Casing : CI FG 260 IS: 210Impeller : Stainless Steel CF8MImpeller Shaft : Stainless Steel AISI 410 Shaft Sleeves : Stainless Steel AISI 410 Bearing Retainer : CI FG 260 IS: 210 (a) Capacity 28.33 LPS/1700 LPM(b)Total head 39 Mtrs. Total nos. of 03 Pumpsets are proposed in module of operation in 2nos. are working , 1 Pump is standby . (Both discharge & head are tentative may very as per actual site condition) |
| 238 | Cast iron pipes & specials. |
| 239 | Supply of galvanized nut- Bolt SS-304 and rubber packing material for erection of above. |
| 240 | Reflex Valve |
| 241 | CIDF double flanged single/multi door swing check valves PN 1.0 FG200 Grade having body comprising inlet & outlet sheets in gradeed cast iron diaphragm fitted woth st. steel, faces,diaphragm plate and door , sub pins and shall be of following sizes: |
| 242 | 150 mm dia or as per site condition |
| 243 | 200 mm dia or as per site condition |
| 244 | CI Dismantling joints |
| 245 | 150 mm dia or as per site condition |
| 246 | 200 mm dia or as per site condition |
| 247 | E.O.T with Monorail Travelling trolley with chain pulley block. |
| 248 | E.O.T with Monorail Travelling Trolley with spur gear and 3.0 tonne capacity chain pulley block with 16 m lift. |
| 249 | Automatic type Chlorinating Plant |
| 250 | SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-20 LPH , pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 500 ltr capacity HDPE tank ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution 40 ltrs.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%). |
| 251 | L.T. Panel Board |
| 252 | L.T. Panel Board suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 400 amps. Capacity, Bus Bar size of 50*10 mm. or suitable size and neutral of half the capacity and neutral of half the capacity sectionalized through a bus section. The panel shall comprise of the following. |
| 253 | 02 No. incoming feeder from two Nos. Transformer with following details:- |
| 254 | 02 nos. MCCB of 400 amps, or suitable rating 50 KA Micro processor type for Two seperate Transformers incomer preferably schneider/ABB with indication lamp mechanical on/off indicator. |
| 255 | One set of current transformer of ratio 400/5A |
| 256 | One No. CT operated ammeter 0-400A with ammeter |
| 257 | One No. Voltmeter 0-500 V with voltmeter |
| 258 | One No power factor meter 0.5 lag/ 1-0.5 lead |
| 259 | One No Surge arrestor Relay & One no. UV/OV Relay |
| 260 | One No frequency meter. |
| 261 | Total Nos. of Outgoing feeder as follows- |
| 262 | MCCB of 100 amps,50KA capacity with indication lamp mechanical on/off indicator. -03 nos. |
| 263 | Ammeter with selector switch. |
| 264 | Single phasing preventer. |
| 265 | Sets of timer and relays for overload and underload. |
| 266 | 01 Nos. 63 Amps. MCCB for RTU/PLC Panel. |
| 267 | 01 Nos. 63 Amps. MCCB as Misc. load |
| 268 | 02 Nos. 32 Amps. 4P MCCB for lighting & spare one. |
| 269 | 01 No. required KVAr APFC Panel with capacitor bank and feeder SFU & MCCB 63 Amp., 25 KA with APFC relay & other acceessories. |
| 270 | Power and control cables & Others |
| 271 | 1100 V grade, 3.5 core 35mm2 or suitable rating of PVC insulated PVC sheathed Aluminium Armoured conductor cable from LT panel to starters.(1x3x50 mtr.) |
| 272 | 1100V grade, 3C x16 mm2 or suitable rating of PVC insulated PVC sheathed submersible copper flat cable from junction box to motor 3 Nos pumps. (2x3x25 mtr.) |
| 273 | Control cable 1x10C, 1.5 mm2 PVC insulated PVC sheathed Copper conductor cable for moisture sensor Reverse protection thermistor relay etc. |
| 274 | Junction box in SS304, IP65 with instruments for pumps. |
| 275 | EARTHING |
| 276 | Complete earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with G.I Plates, watering pipe and loop earthing with adequate size of G.I/ Al. strip etc. (PS-702) 02 Nos. each of the equipment (3 Nos Pumps + 1 No. LT Panel + 1 No. PLC Panel & other loads) size of earthing plate 600mm x 600mm x6 mm with salt and coal. |
| 277 | Lighting system: |
| 278 | Supply & erection of M.S. Tubular Poles SP-36, 9.5m. height. |
| 279 | Supply & Fixing of 72 watt LED with lumen reflector in a decorated fixtures as per required illumination level. |
| 280 | Feeder pillar for lighting with Distribution Board. |
| 281 | Supply and laying of 4Cx16mm2 or suitable rating Al. armoured cable. |
| 282 | Supply and laying of 6 mm2 or suitable rating Al. unarmoured cable flat PVC insulated used for connection of lights fitted to junction boxes. |
| 283 | Internal electrification of Panel rooms with fixtures and wires etc.complete in all respect. |
| 284 | Supply & Fixing of 1200 mm ceiling Fan for Panel Room |
| 285 | Supply & Fixing of exhaust Fan for Panel Room and other room. |
| 286 | Earthing of street light pole (SOR-41) |
| 287 | Painting of street light (P5-634) |
| 288 | Supply and installation of ABC type of 6 Kg. Fire existinguisher (Store pressure type) Dry powder agent. |
| 289 | 12 mm thick rubber mating for safe working on at Panel room. |
| 290 | Tools |
| 291 | Hydrulic crimping tools- Crimping range: 300 sq.mm. |
| 292 | Mannual crimping tools- Crimping range: 400 sq.mm. |
| 293 | Tong tester (AC/DC-1000A), Multimeter (AC/DC-1000A), Megger (AC/DC-500V), Screwdriver (6\\"x 12\\"), Plier (250mm) |
| 294 | Chain wrench (12\\"x18\\"), Pipe wrench (1200mm) |
| 295 | Installation of all above E/M equipments etc. complete. |
| 296 | Testing of all above E/M equipments etc. complete at works & site as per direction given by Engineer-Incharge. |
| 297 | Commissioning of all above E/M equipments etc. complete |
| 298 | Chequered plate of required size so as to cover all trenches. |
| 299 | Power Distribution Transformer : |
| 300 | Supply of Oil immersed Outdoor type Power distribution transformer 11/0.433 KV rating 125 KVA or more suitable rating double wound with copper winding, Level-2 or 3, vector group dyn 11, ONAN with manually operated ± 5.0 % off load tap changer in step of 2.5% and complete with standard fitting & accessories. |
| 301 | Supply and laying of 1100 voltage grade ,1x3.5Cx 95 mm2 or more suitable rating Aluminium conductor, XLPE armoured cable from Transformers to LT Panel. |
| 302 | Double Earthing of Transformers consisting of 04 nos. Earthing Pit (two for each neutral and body) with Al/GI. strip size 25X6mm, the minimum distance between to earthing pits, Double Earthing works and all electrical equipments shall be as per IS and IER. |
| 303 | Installation , testing and Commissioning of Transformer complete. |
| 304 | H.T. Switch Gear Panel : |
| 305 | Supply of 12 KV, H.T. V.C.B. Panel with one incoming & two out going ,630 Amp. (25 KA) Rating have followings- |
| 306 | Incommer Feeder- 01 No. |
| 307 | 3 O/C + 1 EF IDMT Characteristics Relays based Incommer control panel equiped with over current & earth fault relay with core balance C.T., master trip relay, instantaneous under voltage realy & Auxilliary realy etc. C.T.ratio 30-20/5A Dual core, Class-1 for measurement core & 5P10 for protection core & PT 11KV/110 VAC. KWH meter, power factor meter, frequency meter. Amp. meter 0-20 & volt meter 0 to12 KV. All relays required separately conventioal type 24 to 30 VDC, 110 VAC. |
| 308 | Outgoing Feeder- 02 Nos. |
| 309 | outgoing feeder control panel equiped with triple pole 3 O/C + 1 E/F relay with IDMT & intantaneous characterisstics, mater trip relay & Auxilliary relay for Buchhloz alarm / trip, OTI alram / trip & WTI alram/trip, etc. C.T.ratio 30-15/5A, Class-1 for measurement core & 5P10 for protection core. |
| 310 | DC Supply |
| 311 | SICT battery bank, exide make, consisting of 16 cells, 2 volt each for supply VDC 24 to 30 Volt with battery charger of approved make with suitable M.S. Stand / Trolley, equipment fittings with accessories etc. |
| 312 | Supply and laying of 1x3Cx70 mm 2 or more suitable rating, 11 KV HT Al. XLPE cable from metering panel to H.T. Panel and from H.T. Panel to both transformers. |
| 313 | S/F of XLPE cable End termination box of 120mm2 : |
| 314 | Indoor end termination box. |
| 315 | Earthing of H.T Panel as per IS & IER. |
| 316 | Installation of HT Panel. |
| 317 | Testing & Commissioning of HT Panel etc. |
| 318 | Erection of All sub staion equipments and fencing with iron mesh etc. complete in all respect. |
| 319 | Commissioning of All sub station equipments etc. complete in all respect. |
| 320 | S.I.T.C. OF PUMPING PLANTS & OTHER E/M ITEMS IN PROSPECTIVE TO NEW C.W.R., ZONE-5 |
| 321 | PumpSet at C.W.R: |
| 322 | Supply of Electric Driven self water lubricated V.T. pump 1700 LPM 39 mtr. Head with suitable column pipe complete in all respect with discharge head assembly and strainer complete & coupled with suitable rating of motor VHS induction 50 hz 3 phase AC supply 415+6%-10% volts at speed 1470 RPMMOCSuction Case : CI FG 260 IS: 210 Line Shaft : Stainless Steel AISI 410Casing : CI FG 260 IS: 210Impeller : Stainless Steel CF8MImpeller Shaft : Stainless Steel AISI 410 Shaft Sleeves : Stainless Steel AISI 410 Bearing Retainer : CI FG 260 IS: 210 (a) Capacity 28.33 LPS/1700 LPM(b)Total head 39 Mtrs. Total nos. of 03 Pumpsets are proposed in module of operation in 2nos. are working , 1 Pump is standby . (Both discharge & head are tentative may very as per site conditioon) |
| 323 | Cast iron pipes & specials. |
| 324 | Supply of galvanized nut- Bolt SS-304 and rubber packing material for erection of above. |
| 325 | Reflex Valve |
| 326 | CIDF double flanged single/multi door swing check valves PN 1.0 FG200 Grade having body comprising inlet & outlet sheets in gradeed cast iron diaphragm fitted woth st. steel, faces,diaphragm plate and door , sub pins and shall be of following sizes: |
| 327 | 150 mm dia or as per site condition |
| 328 | 200 mm dia or as per site condition |
| 329 | CI Dismantling joints |
| 330 | 150 mm dia or as per site condition |
| 331 | 200 mm dia or as per site condition |
| 332 | EOT with Monorail Travelling trolley with chain pulley block. |
| 333 | EOT with Monorail Travelling Trolley with spur gear and 3.0 tonne capacity chain pulley block with 16 m lift. |
| 334 | Automatic type Chlorinating Plant |
| 335 | SITC of SCADA Compatible Automatic type chlorinating plant solenoid driven dosing pump of capacity 0-20 LPH , pressure 4kg/cm2 with ORP sensor to check and regulate the dosing along with 500 ltr capacity HDPE tank ,standard fittings, wall/floor mountings MS bracket for dosing pump with GM Valve ,cock valve & sodium hydro chloride solution 40 ltrs.,chlorine test kit with O.T. Solution complete with all respect.( suitable for 100-220V and 30-60 Hz , suction lift- 1.5 m., injection pressure 4 bars, steadt state accuracy +-3% repeatability +-3%). |
| 336 | L.T. Panel Board |
| 337 | L.T. Panel Board suitable for operation on 400 V, 3 Phase 50 Hz. A.C. supply in sheet steel enclosure in cubical pattern floor mounting with following fitted on the phase of the panel with bus incomer bar of 400 amps. or suitable rating Capacity, Bus Bar size of 50*10 mm. and neutral of half the capacity and neutral of half the capacity sectionalized through a bus section. The panel shall comprise of the following. |
| 338 | 02 No. incoming feeder from two Nos. Transformer with following details:- |
| 339 | 02 nos. MCCB of 400 amps,50 KA Micro processor type for Two seperate Transformers incomer preferably schneider/ABB with indication lamp mechanical on/off indicator. |
| 340 | One set of current transformer of ratio 400/5A |
| 341 | One No. CT operated ammeter 0-400A with ammeter |
| 342 | One No. Voltmeter 0-500 V with voltmeter |
| 343 | One No power factor meter 0.5 lag/ 1-0.5 lead |
| 344 | One No Surge arrestor Relay & One no. UV/OV Relay |
| 345 | One No frequency meter. |
| 346 | Total Nos. of Outgoing feeder as follows- |
| 347 | MCCB of 100 amps,50KA capacity with indication lamp mechanical on/off indicator. -03 nos. |
| 348 | Ammeter with selector switch. |
| 349 | Single phasing preventer. |
| 350 | Sets of timer and relays for overload and underload. |
| 351 | 01 Nos. 63 Amps. MCCB for RTU/PLC Panel. |
| 352 | 01 Nos. 63 Amps. MCCB as Misc. load |
| 353 | 02 Nos. 32 Amps. 4P MCCB for lighting & spare one. |
| 354 | 01 No. required KVAr APFC Panel with capacitor bank and feeder SFU & MCCB 63 Amp., 25 KA with APFC relay & other acceessories. |
| 355 | Power and control cables & Others |
| 356 | 1100 V grade, 3.5 core 35mm2 or suitable rating of PVC insulated PVC sheathed Aluminium Armoured conductor cable from LT panel to starters.(1x3x50 mtr.) |
| 357 | 1100V grade, 3C x16 mm2 or suitable rating of PVC insulated PVC sheathed submersible copper flat cable from junction box to motor 3 Nos pumps. (2x3x25 mtr.) |
| 358 | Control cable 1x10C, 1.5 mm2 PVC insulated PVC sheathed Copper conductor cable for moisture sensor Reverse protection thermistor relay etc. |
| 359 | Junction box in SS304, IP65 with instruments for pumps. |
| 360 | EARTHING |
| 361 | Complete earthing of all the equipments as detailed above shall be done as per IS/IER/PWD specification with G.I Plates, watering pipe and loop earthing with adequate size of G.I/ Al. strip etc. (PS-702) 02 Nos. each of the equipment (3 Nos Pumps + 1 No. LT Panel + 1 No. PLC Panel & other loads) size of earthing plate 600mm x 600mm x6 mm with salt and coal. |
| 362 | Lighting system: |
| 363 | Supply & erection of M.S. Tubular Poles SP-36, 9.5m. height. |
| 364 | Supply & Fixing of 72 watt LED with lumen reflector in a decorated fixtures as per required illumination level. |
| 365 | Feeder pillar for lighting with Distribution Board. |
| 366 | Supply and laying of 4Cx16mm2 or suitable rating Al. armoured cable. |
| 367 | Supply and laying of 6 mm2 or suitable rating Al. unarmoured cable flat PVC insulated used for connection of lights fitted to junction boxes. |
| 368 | Internal electrification of Panel rooms with fixtures and wires etc.complete in all respect. |
| 369 | Supply & Fixing of 1200 mm ceiling Fan for Panel Room |
| 370 | Supply & Fixing of exhaust Fan for Panel Room and other room. |
| 371 | Earthing of street light pole (SOR-41) |
| 372 | Painting of street light (P5-634) |
| 373 | Supply and installation of ABC type of 6 Kg. Fire existinguisher (Store pressure type) Dry powder agent. |
| 374 | 12 mm thick rubber mating for safe working on at Panel room. |
| 375 | Tools |
| 376 | Hydrulic crimping tools- Crimping range: 300 sq.mm. |
| 377 | Mannual crimping tools- Crimping range: 400 sq.mm. |
| 378 | Tong tester (AC/DC-1000A), Multimeter (AC/DC-1000A), Megger (AC/DC-500V), Screwdriver (6\\"x 12\\"), Plier (250mm) |
| 379 | Chain wrench (12\\"x18\\"), Pipe wrench (1200mm) |
| 380 | Installation of all above E/M equipments etc. complete. |
| 381 | Testing of all above E/M equipments etc. complete at works & site as per direction given by Engineer-Incharge. |
| 382 | Commissioning of all above E/M equipments etc. complete |
| 383 | Chequered plate of required size so as to cover all trenches. |
| 384 | Power Distribution Transformer : |
| 385 | Supply of Oil immersed Outdoor type Power distribution transformer 11/0.433 KV rating 125 KVA or more suitable rating double wound with copper winding, Level-2 or 3, vector group dyn 11, ONAN with manually operated ± 5.0 % off load tap changer in step of 2.5% and complete with standard fitting & accessories. |
| 386 | Supply and laying of 1100 voltage grade ,1x3.5Cx 95 mm2 or suitable rating Aluminium conductor, XLPE armoured cable from Transformers to LT Panel. |
| 387 | Double Earthing of Transformers consisting of 04 nos. Earthing Pit (two for each neutral and body) with Al/GI. strip size 25X6mm, the minimum distance between to earthing pits, Double Earthing works and all electrical equipments shall be as per IS and IER. |
| 388 | Installation , testing and Commissioning of Transformer complete. |
| 389 | H.T. Switch Gear Panel : |
| 390 | Supply of 12 KV, H.T. V.C.B. Panel with one incoming & two out going ,630 Amp. (25 KA) Rating have followings- |
| 391 | Incommer Feeder- 01 No. |
| 392 | 3 O/C + 1 EF IDMT Characteristics Relays based Incommer control panel equiped with over current & earth fault relay with core balance C.T., master trip relay, instantaneous under voltage realy & Auxilliary realy etc. C.T.ratio 30-20/5A Dual core, Class-1 for measurement core & 5P10 for protection core & PT 11KV/110 VAC. KWH meter, power factor meter, frequency meter. Amp. meter 0-20 & volt meter 0 to12 KV. All relays required separately conventioal type 24 to 30 VDC, 110 VAC. |
| 393 | Outgoing Feeder- 02 Nos. |
| 394 | outgoing feeder control panel equiped with triple pole 3 O/C + 1 E/F relay with IDMT & intantaneous characterisstics, mater trip relay & Auxilliary relay for Buchhloz alarm / trip, OTI alram / trip & WTI alram/trip, etc. C.T.ratio 30-15/5A, Class-1 for measurement core & 5P10 for protection core. |
| 395 | DC Supply |
| 396 | SICT battery bank, exide make, consisting of 16 cells, 2 volt each for supply VDC 24 to 30 Volt with battery charger of approved make with suitable M.S. Stand / Trolley, equipment fittings with accessories etc. |
| 397 | Supply and laying of 1x3Cx70 mm 2 or suitable rating,11 KV HT Al. XLPE cable from metering panel to H.T. Panel and from H.T. Panel to both transformers. |
| 398 | S/F of XLPE cable End termination box of 120mm2 : |
| 399 | Indoor end termination box. |
| 400 | Earthing of H.T Panel as per IS & IER. |
| 401 | Installation of HT Panel. |
| 402 | Testing & Commissioning of HT Panel etc. |
| 403 | Erection of All sub staion equipments and fencing with iron mesh etc. complete in all respect. |
| 404 | Commissioning of All sub station equipments etc. complete in all respect. |
| 405 | S.I.T.C OF SCADA SYSTEM FOR NEW C.W.R- ZONE-1 HAVING 03 NO. PUMPS |
| 406 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each ZPS/ OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. |
| 407 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 408 | CE & UL certified Inteligent Smart Energy Meter for each pump |
| 409 | Motor operated Actuators with Sluice valve of size 150 mm. or as per actual site condition at Delivery line of each pump.(2W+1S) |
| 410 | Motor operated Actuators with Sluice valve of size 200 mm. or as per actual site condition at common header. |
| 411 | CE & UL certified Electro magnatic flow Meter for line size 200 mm. or as per actual site condition. |
| 412 | Soft starter with RS-485 port-400V Class suitable rating for Motor |
| 413 | Auto Phase reversal unit with inbuilt time delay and enclosure suitable rating for motor |
| 414 | CE & UL certified Radar type water level transmitter for OHT as well as CWR. |
| 415 | CE & UL certified pressure transmitter for each pump |
| 416 | CE & UL certified Surge protector for control panel |
| 417 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 418 | Complete cabling of CWR including all power and control cables of all equipment at CWR and OHT . |
| 419 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) |
| 420 | Installation, commissioning & testing for CWR |
| 421 | Trial run for three month period for one CWR |
| 422 | S.I.T.C OF SCADA SYSTEM FOR NEW C.W.R- ZONE-8 HAVING 03 NO. PUMPS |
| 423 | CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each ZPS/ OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations. |
| 424 | G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges. |
| 425 | CE & UL certified Inteligent Smart Energy Meter for each pump |
| 426 | Motor operated Actuators with Sluice valve of size 150 mm. or as per actual site condition at Delivery line of each pump.(2W+1S) |
| 427 | Motor operated Actuators with Sluice valve of size 200 mm. or as per actual site condition at common header. |
| 428 | CE & UL certified Electro magnatic flow Meter for line size 200 mm. or as per actual site condition. |
| 429 | Soft starter with RS-485 port-400V Class suitable rating for Motor |
| 430 | Auto Phase reversal unit with inbuilt time delay and enclosure suitable rating for motor |
| 431 | CE & UL certified Radar type water level transmitter for OHT as well as CWR. |
| 432 | CE & UL certified pressure transmitter for each pump |
| 433 | CE & UL certified Surge protector for control panel |
| 434 | CE & UL certified 7\\" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter. |
| 435 | Complete cabling of CWR including all power and control cables of all equipment at CWR and OHT . |
| 436 | Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments) |
| 437 | Installation, commissioning & testing for CWR |
| 438 | Trial run for three month period for one CWR |
| 439 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-1 |
| 440 | Motor operated Actuators with Sluice valve of size 400 mm. or as per actual site condition at distribution line. |
| 441 | CE & UL certified Electomagnetic Flowmeter for OHT line size 400 mm. dia.or as per actual site condition |
| 442 | CE & UL certified Radar type level transmitter for OHT |
| 443 | Installation, commissioning & testing for of above items at one OHT |
| 444 | Trial run for three month period for three nos for one OHT |
| 445 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-2 |
| 446 | Motor operated Actuators with Sluice valve of size 350 mm. or as per actual site condition at distribution line. |
| 447 | CE & UL certified Electomagnetic Flowmeter for OHT line size 350 mm. dia. or as per actual site condition |
| 448 | CE & UL certified Radar type level transmitter for OHT |
| 449 | Installation, commissioning & testing for of above items at one OHT |
| 450 | Trial run for three month period for three nos for one OHT |
| 451 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-3 |
| 452 | Motor operated Actuators with Sluice valve of size 300 mm. or as per actual site condition at distribution line. |
| 453 | CE & UL certified Electomagnetic Flowmeter for OHT line size 300 mm. dia. or as per actual site condition |
| 454 | CE & UL certified Radar type level transmitter for OHT |
| 455 | Installation, commissioning & testing for of above items at one OHT |
| 456 | Trial run for three month period for three nos for one OHT |
| 457 | SCADA WORKS FOR EXISTING OVERHEAD TANK IN ZONE-4 |
| 458 | Motor operated Actuators with Sluice valve of size 150 mm. or as per actual site condition at distribution line. |
| 459 | CE & UL certified Electomagnetic Flowmeter for OHT line size 150 mm. dia.or as per actual site condition |
| 460 | CE & UL certified Radar type level transmitter for OHT |
| 461 | Installation, commissioning & testing for of above items at one OHT |
| 462 | Trial run for three month period for three nos for one OHT |
| 463 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-5 |
| 464 | Motor operated Actuators with Sluice valve of size 400 mm. or as per actual site condition at distribution line. |
| 465 | CE & UL certified Electomagnetic Flowmeter for OHT line size 400 mm. dia. or as per actual site condition |
| 466 | CE & UL certified Radar type level transmitter for OHT |
| 467 | Installation, commissioning & testing for of above items at one OHT |
| 468 | Trial run for three month period for three nos for one OHT |
| 469 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-6 |
| 470 | Motor operated Actuators with Sluice valve of size 250 mm. or as per actual site condition at distribution line. |
| 471 | CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia.or as per actual site condition |
| 472 | CE & UL certified Radar type level transmitter for OHT |
| 473 | Installation, commissioning & testing for of above items at one OHT |
| 474 | Trial run for three month period for three nos for one OHT |
| 475 | SCADA WORKS FOR NEW OVERHEAD TANK IN ZONE-7 |
| 476 | Motor operated Actuators with Sluice valve of size 250 mm.or as per actual site condition at distribution line. |
| 477 | CE & UL certified Electomagnetic Flowmeter for OHT line size 250 mm. dia. or as per actual site condition |
| 478 | CE & UL certified Radar type level transmitter for OHT |
| 479 | Installation, commissioning & testing for of above items at one OHT |
| 480 | Trial run for three month period for three nos for one OHT |
| 481 | Trial Run & Maintenance of 03 Months including liquid chlorine & necessary staff required for operation. (excluding electricity charges) |
| 482 | MASTER CONTROL STATION (M.C.S.) |
| 483 | CE & BIS approved manufacturer's industrial grade LED monitor size 65\\" with latest configuration as per specification mentioned in tender documents. |
| 484 | Desktop/PC with i7 processor as per specification mentioned in tender documents. |
| 485 | CE/UL approved manufacturer's 5 KVA UPS with batteries as per specification mentioned in tender documents. |
| 486 | Full development version of required TAGS SCADA software suitable for digital and analog input/output features with customization of software as per requirement as per spec. mentioned with unlimited digital and analog Input/Output features specified in detailed technical document with customization of software as requirement |
| 487 | CE & UL approved manufacturer's control room PLC with Redundant CPU & power supply at MCS in IP54 enclosure as per specification mentioned in tender documents. |
| 488 | CE/UL certified field gateway agent for transfering data from MCS to Central control room(C.C.R.) Lucknow. |
| 489 | GSM based wireless / broadband/Equipment communication system for PLC capable to transfer and retreive data & gather data from remote sites to control stations, including all accessories complete. All accessories included signal enhancer antenna along with running expenses till DLP. |
| 490 | CE/UL approved manufacturer's Firewall for network protection |
| 491 | Surge protector for ethernet communication protection |
| 492 | CE/UL approved manufacturer's industrial grade ethernet switch |
| 493 | Mobile App facility system architecture complete.( industries internet based & viewed through mobile apps for increased local & remote visibility) |
| 494 | Canon/HP/equivalent latest Laser printer |
| 495 | Security Survelliance IP camera with DVR. |
| 496 | Installation, testing and commissioning with required furniture,Air Conditioner etc. |
| 497 | Test and trial run of whole system. |
| 498 | Trial Run & Maintenance of Three Months including staff (excluding electricity charges) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail