| 1 | SITC of Diesel GEN-SET 10 KVA CPCB IV 3 phase as per the specification belowDiesel Engine:- Water cooler of suitable HP at 1500 rpm . The Engine should be electric start with suitable 12V DC Battery.Alternator:- The Alternator rated at 10 KVA, 415Volts at 1500 rpm, 3 Phase, 50 Hz AC with 0.8 logging power factor having IP 23 enclosure protection, brushless excitaton, single bearing with class H type insulationBase Frame Foundation: Both Engine and alternator shall be mounted on Suitable base frame made of MS sheet metal with foundation and vibration isolator arrangement /AVM/panel as per recommendation of manufacturer.Exhaust System:- The exhaust line should be insulated with glass wool and clad as required.Enclosure: Acoustic enclosure shall have sound proof with quality fire resistant grade foam of suitable density. The enclosure should be powder coated color shade. The noise level rating should be with limit of 75 dBA as per ISO 8528 part 10.Control panel: It shall have DG Controller, relays, Control MCB’s/ Fuse, Current transformers as required. |
| 2 | SITC of Diesel GEN-SET 10 KVA CPCB IV 1 phase as per the specification belowDiesel Engine:- Water cooler of suitable HP at 1500 rpm . The Engine should be electric start with suitable 12V DC Battery.Alternator:- The Alternator rated at 10 KVA, 230Volts at 1500 rpm, 1 Phase, 50 Hz AC with 0.8 lagging power factor having IP 23 enclosure protection, brushless excitaton, single bearing with class H type insulationBase Frame Foundation: Both Engine and alternator shall be mounted on Suitable base frame made of MS sheet metal with foundation and vibration isolator arrangement /AVM/panel as per recommendation of manufacturer.Exhaust System:- The exhaust line should be insulated with glass wool and clad as required.Enclosure: Acoustic enclosure shall have sound proof with quality fire resistant grade foam of suitable density. The enclosure should be powder coated color shade. The noise level rating should be with limit of 75 dBA as per ISO 8528 part 10.Control panel: It shall have DG Controller, relays, Control MCB’s/ Fuse, Current transformers as required. |
| 3 | SUPPLY OF 63AMPS ATS PANEL as required |
| 4 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with CI/RCC cover having locking/Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil. c)Watering GI pipe 20mm Class B with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs(min) with soft black agriculture soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe.g)watering arrangement(plumbing will be paid seperately).;(b) In rocky strata |
| 5 | Extra for using salt and charcoal for GI or copper plate earth electrode as required( 96 Kgs of Charcoal and 5 Kgs of Salt) |
| 6 | Supplying and laying 25 mm x 5 mm GI strip at 0.5 m below ground as strip earth electrode including soldering etc. as required |
| 7 | Supply of 4 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) IS:7098(Part I) with latest amendments of following size.;4 Core 16 sq.mm |
| 8 | Supply of 2 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) IS:7098(Part I) with latest amendments of following size.;2 Core 16 sq.mm |
| 9 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of grade exceeding 1.1 KV but not exceeding 11 KV grade of size not exceeding 120 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Inchargesand cushioning with screened sand bed of 20mm thick protective covering with bricks placed lenghtwise on top of cable all over the run and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.;(b) Rocky strata |
| 10 | Supplying and making cable end terminations with brass compression gland and copper lugs for folowing sizes of 4 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(5) 4 x 16 Sq. mm. |
| 11 | Supply and making cable end terminations with compression gland and copper lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade complete as required.;(5) 2 x 16 Sq. mm. |
| 12 | Providing suitable cables for control cabling & connections as required |
| 13 | Providing civil foundation of suitable size for installing the Diesel generator as required as per engineer incharge |
| 14 | Transportation of Diesel-Gen from factory to site including unloading of DG-SET as required |
| 15 | Electrical Permission as required Please Enable Macros to View BoQ information |