| 1 | Sitc for Transformer Bay at Receiving Station Jakheni |
| 2 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Schnieder , ABB . |
| 3 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 4 | 33 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase |
| 5 | 30 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less |
| 6 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Pascal, Stelmec, etc . |
| 7 | 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type |
| 8 | CONTROL CABLES : i) 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a |
| 9 | ii)6 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 10 | iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 11 | Galvanised Pipe/ Steel Structures |
| 12 | Galvanised Nuts & Bolts |
| 13 | ACSR Panther Conductor (Providing & Fixing of of BusBar System with 150 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job |
| 14 | Lugs and Ferrules |
| 15 | SITC of POWER TRANSFORMER (10 MVA) |
| 16 | 33/11kV, 3 phase ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections (10 MVA) as per latest IS StandardsNote:The Power Transformer shall cover the warrenty period of 5 Years |
| 17 | 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 18 | 6 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 19 | 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 20 | SITC of 11 kV INDOOR SWITCHGEAR OF 33/11 kV SUBSTATION |
| 21 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal, Stelmac :- For 10 MVA Power Transformer (1+3) including Smart meters Trivector. |
| 22 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type . |
| 23 | 11 kV 3- Core XLPE 400 mm² armoured, FRLS Cable |
| 24 | 11 kV 3- Core XLPE 185 mm² armoured, FRLS Cable |
| 25 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core(Indoor) |
| 26 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core (outdoor ) |
| 27 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (indoor) |
| 28 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (outdoor) |
| 29 | 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. |
| 30 | 11kV DO set , AB Switch 3-Phase, 3-Pole, 200 Amp |
| 31 | Galvanised iron of sorts |
| 32 | 09 Mtr. Long Pole(ST-410 SP33) |
| 33 | 120 mm² PVC LT Cable 4 Core, armoured, FRLS |
| 34 | Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole |
| 35 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip for ST poles |
| 36 | 100KVA 11Kv/433V Auxillary Transformer( Level 2) |
| 37 | Earthing for 100KVA Auxillary Transformer (complete as per REC standards) |
| 38 | MCCB 200 Amp with box |
| 39 | Civil /Misc Works |
| 40 | Galvanized Chain link Fencing of 33 kV Yard of Substation by way of Mass Concrete in Foundations and chain link fencing of 6 ft height (Size 75 mm x 75 mm made of G.I.Wire 3.15 mm in diamond pattern) using Fencing posts of M.S.angle size 65x65x6mm embedded in 1:2:4 C.C. Block of Size 400 mm x 400 mm x1000m at an average spacing of 2.5 m c/c.The chain Link mesh fencing shall be secured to M.S.Angle post with flat iron strip of size 50x6 mm on both sides.There shall be a provision of 3 rows of 2 strand Barbed wire on top of fencing post. |
| 41 | Providing and laying of Cement Concrete (1:3:6) mix complete in all respects including centring/ shuttering/ earthwork for self supoorting strucureand yard (Retaining Wall) |
| 42 | Cable Trench for laying of Cables From Yard to Control Room with duct covers including separate tray for power and contol cables (1 m x 1 m x 0.6 m) |
| 43 | 33/11 kV Power Transformer Foundation ( 3 m x 3m x 3 m)as per REC standards |
| 44 | 33 kV Equipment Foundation & Gantry foundation as per REC standards |
| 45 | 33 KV Yard Concreting with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick. |
| 46 | 33 kV Yard Lighting ( 4 nos of 100 Wt LEDs, 11 mtr ST poles with Ring on top) complete with earthing , cement bottoming GI brackets, control box , cable etc with centrally controlled Switch. |
| 47 | Providing and Fixing of CCTV cameras 6 nos with specifications IP camera 4 MP IR 30 mtr range with 8 channel DVR POE switch , Hard Disc 4 Tb and LED Monitor 32 inch with all allied accessories. |
| 48 | Earth Mat by using GI Flat with 50mm X 8 mm as grounding Conductor . The mesh size shall be 1m x 1m . The burial depth of GI Flat shall be 600 mm. The work involves the excavation of trenches for burial of grounding flat , laying of GI flat includes welding and backfilling of trenches including earh electrodes. . Complete job |
| 49 | Meggar 5000 mega Ohm- manually operated |
| 50 | Extendable Aluminium Ladder 25 feet |
| 51 | Earthing Rod (set of 3) |
| 52 | Earth Resistance Tester |
| 53 | Lifting Machine (3 tonn) |
| 54 | Lifting Machine (5 tonn) |
| 55 | Earthing Electrode ( 3 m long 40 mm diaGI Pipe) through GI Strip |
| 56 | Survey, Supply, Installation , Testing and Commissioning for Thickening OF 33 kV LINE ( Dog to Wolf) |
| 57 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 58 | GI Channel iron X-arm of 10 ft long |
| 59 | Guard netting Angle 11 ft long |
| 60 | MS Angle braces 12 ft , 5 ft, 2 ft long and angle belts 8 ft long |
| 61 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 62 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 63 | Flat iron clamps and Ties |
| 64 | Galvinized Nuts and Bolts |
| 65 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 66 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 67 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) |
| 68 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 69 | 150 mm2 ACSR Wolf conductor |
| 70 | Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |