| 1 | Augmentaion of 100 KVA Sub-station to 200 KVA |
| 2 | Supply, Installation, Testing and commissioning of 200 kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff. |
| 3 | Safe Backcarriage of old 100kva sub-station from lone mohalla khudwani to divisional stores. |
| 4 | Supply,fixing, testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per IS Standards |
| 5 | Supply,fixing, testing & commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type as per IS Standards |
| 6 | Providing and fixing of anticlimbing device complete with GI Barbed wire and clamps |
| 7 | Supply, laying of 300 mmsq Single Core XLPE, FRLS unaroumed Cable |
| 8 | Providing of Industrial Safety Belt Harness Full Body Fall Protection |
| 9 | Supplying and fixing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 10 | Providing of Electric Shock Proof Gloves Class 0-1000V |
| 11 | Providing and fixing of suitable LT Fuse Set as per the approved drawings of KPDCL. |
| 12 | Providing and fixing of suitable sign board (600x450 mm) fabricated out of sheet steel with suitable angle stand indicating name of work , Estimated cost ,DOS and DOC written with white paint on dark blue background |
| 13 | Providing and fixing of danger plate with clamps. Please Enable Macros to View BoQ information |