| 1 | Design, Engineering and Supply of material |
| 2 | Design, Engineering, Supply of Galvanised Tower structure including stubs as per the specifications mentioned in SBD (C+9) |
| 3 | Phase Plates 3 No Per Tower for D/C |
| 4 | Number Plates 1 No Per Tower |
| 5 | Circuit Plates 1 No. Per Tower for D/C |
| 6 | Nuts & Bolts |
| 7 | 200 mm² ACSR PANTHER Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering |
| 8 | Mid Span Joints |
| 9 | Vibration Dampers |
| 10 | Repair Sleeves For Conductor |
| 11 | Arching horn |
| 12 | Anti Climbing Device |
| 13 | Disc insulator 120 KN for 132 KV Transmission Line |
| 14 | Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 15 | Tag welding of towers |
| 16 | Earth wire of size 7/3.15 mm |
| 17 | Mis Span Joint for earth wire |
| 18 | Vibration damper for earth wire |
| 19 | Tension clamps for earth wire |
| 20 | Erection, testing and commissioning |
| 21 | Galvanised Tower structure including stubs as per the specifications mentioned in SBD (D+6 type) |
| 22 | Phase Plates 3 No Per Tower for D/C |
| 23 | Number Plates 1 No Per Tower |
| 24 | Circuit Plates 1 No. Per Tower for D/C |
| 25 | Nuts & Bolts |
| 26 | 200 mm² ACSR Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering |
| 27 | Mid Span Joints |
| 28 | Vibration Dampers |
| 29 | Repair Sleeves For Conductor |
| 30 | Arching horn |
| 31 | Anti Climbing Device |
| 32 | Disc insulator 120 KN for 132 KV Transmission Line |
| 33 | Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 34 | Tag welding of towers |
| 35 | Earth wire of size 7/3.15 mm |
| 36 | Mis Span Joint for earth wire |
| 37 | Vibration damper for earth wire |
| 38 | Tension clamps for earth wire |
| 39 | Dismantling of the existing tower along with conductor material and accessories |
| 40 | Civil Works including material |
| 41 | Design, Engineering of Foundation of C+9 type tower as per Site requirement and specifications laid in SBD |
| 42 | Earthing of Tower as per soil resistivity and site conditions( Normal type /Counter Poise) Please Enable Macros to View BoQ information |