| 1 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type)( (flame retardant type)) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 2 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type)( (flame retardant type)) with suitable size modular box & cover( flame retardant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.(wall fan) |
| 3 | Supplying,fixing of 1x16A Plug with complete fitting as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) |
| 4 | Supplying,fixing of 1x6A+1X1 6A Plug on the separate board with complete fitting by 01 no of 16A+1 no 6A switch & socket(modular type) ( falme retardant type)with suitable size modular box & metallic cover plate (both side)( falme retardant type)including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 5 | Supply and fixing of 32 mm fire retardant ISI Marked UPVC Trunking.Make-Legrand/OBO/Honeywell |
| 6 | SITC of PIR based occupancy sensor for corridor , connected load upto 10Amp, mounting height upto 2.8 mtr and 5m diameter coverage in complete as per the direction of Engineer-in-charge. Make-Schneider/Legrand/Siemens/ABB |
| 7 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)(2X1.5+1X1.5) |
| 8 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI /V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) (2X2.5+1X1.5) |
| 9 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) (2X4+1X1.5) |
| 10 | Sub-Head II (Light fitting Fixture & Fan)Supplying and fixing of Energy efficient surface /recess mounted square /round shape 18 W LED luminaire of dimension of consists of white powder coated , die-cast Alluminium housing with high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 18 watt and lumen output of 1800 lumens, , CRI not less than 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 3 KV , L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years |
| 11 | Supplying, installation, of WALL fan of heavy duty 400 mm sweep 1400 rpm with accessories(Make- Havells/Crompton/Usha/Orient/Bajaj ) of wall fan in the existing wall, including fixing & conntection .as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years. |
| 12 | Supplying, installation, of exhaust fan of heavy duty 300 mm sweep 1400 rpm with louvers (Make- Havells/Crompton/Usha/Orient/Bajaj ) of exhaust fan in the existing wall, including fixing & conntection as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years. |
| 13 | Supply and fixing of 10 Watt LED BH Fitting in complete with all accessories as per the direction of Engineer-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj.) |
| 14 | (Earthing) INSTALLATIONSupplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 15 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 16 | CABLING AND END TERMINATION MAIN AREASupplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 50 sq mm ( FOR power.main ofp high mast ) |
| 17 | 3.5core x 120 sq mm ( FOR DG ) |
| 18 | 4core x 16 sq mm |
| 19 | LAYING OF CABLELaying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 20 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 21 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 22 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 120 SQ. MM From 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 23 | Supplying and making end termination with brass double compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x50 sq mm |
| 24 | 3.5 core x120sq mm |
| 25 | 4core x 16 sq mm |
| 26 | Providing,fixing and laying of following dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 50 mm dia |
| 27 | ( PANELS )CHANGE OVER PANELS/I/T&Commissioning of LT indoor floor mounted cubical type electrical panel made out by 2mm CRCA steel sheet duly derusted & painted by siemens gray powder cote paint fallowed by 9 tank acid treatment is designed as G.A drawing as per direction of Engg.-in-Charge.Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.In commer- 01 no of 200A 4P onload changeover switch ( Dg 01 NO)(Make-ABB/Siemens/Schneider/Legrand)Busbar-1 04 numbers of 300Amps AL. busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing) Instrument- (i) 06 numbers phase indicating lamp with toggle switch & HRC fuse for source 1 and source 2(RYB Indication)(ii)02 numbers phase indicating lamp with toggle switch & HRC fuse for source 1 and source 2 selection |
| 28 | 13 PASSENGER LIFT --Supply,Installation, Testing & Commissioning of of 13 Passenger- lift gearless with Machine room Capacity(884 Kg), with minimum shaft size of 1600mm(Left to right)x2400mm(Front to back) Elevator G+4 (5 stops) Floors with ACVVVF drive/Control with ARD >=1.25 MPS, SS honeycomb interior ,2hr fire rated door with simplex operation without attendant car position indicators,battery operated alarm bell & emegency light,SS honeycomb finish door finished car interior, recess Granite flooring ,power operated centre opening automatic sliding SS honeycomb finish doors for car entrance & hoist way entrance etc .All SS material shall be of grade SS-304 and minimum thickness of 1.6mm. Machine beams,buffer support channels,facia plate including sills pit ladder metal screen in Elevator pit etc.as per specifiaction including cost of (i)Overload detection,(ii)Voice announcement,(iii) Intercom,(iv)Braille Buttons(v) provision of flat cat 6 cable for CCTV. with all Civil & Electrical works required for installation of Elevator in the existing lift well and machine room,scaffolding ,floor cutting including Fireman's switch complete in all respec as per the instruction of Engg. in charge.The Elevator should be suitable for physically handicapped person. make:OTIS/Mitsubishi/Schindler/Johnson |
| 29 | LIGHTENING PROTECTION SYSTEM--- Lightning Protection :- Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 30 | Supply of Roof conductor holder for parapet- PolyamideConductor holder:With M8 female thread or diameter 7mm, M8Screw to connect the conductor holder.Weather andtemperature resistant from -35 to +90 degree Celsius tested.Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 31 | Supply of Polyamide roof cable holder for flat roof:DIN 48829 Form B1. Closed form with bottom. Filling weight1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 32 | Supply of Connector: For T cross and parallel connectors. Quickinstallation using hexagonal bolt M10X30 high-grade hot dipgalvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB |
| 33 | Supply of Vertical air terminal with accessories:Providing of Air terminalsas per IS-IEC -62305 part-3Nominal size Ø10/16 mm aluminium rod:2 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN48801) Suitable for high wind load.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 34 | Supply for Providing of Stand for Fang Fix system 16 kg with base andclamp ,made up of frost resistant concrete and clamp testedupto 100KA lightning current . Make-OBO/Dehn/ABB |
| 35 | Supply for Providing of Stand for Fang Fix system 16 kg made up of frostresistant concrete. Make-OBO/Dehn/ABB |
| 36 | Supply of Test Joint (Folding Clamp) suitable to connect 8mmround conductor and max by 30x3 mm GI strip as specified indrawing and directed by Engineer.Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 37 | Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr HeightFor Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB |
| 38 | Supply of Galvanised Steel Flat 30X3 mm thickness from earthelectrode directly in ground as required. Flat conductor HotDipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 39 | Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 40 | Supply of flat conductor holder- Fit: FL 30, With mounting hole6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece fromhot-dip galvanised steel, Bottom section from polyamide, black.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 41 | Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB |
| 42 | Supply of UL Listed maintenance free ,Low carbon coppercoated earth rod of 3 metre electrode having diameter of 17.2mm with copper coating thickness of 250micron tested as perIEC 62561-2 Make-OBO/Dehn/ABB |
| 43 | Supply of universal clamp made of SS to connect rod with flatconductor Make-OBO/Dehn/ABB |
| 44 | Supply of Earth conductivity enhancing mineral compound shall be of 25kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB |
| 45 | Supply of The above arrangements shall be provided with Heavy dutyearth champer of 5000kg load bearing capacity to ensure thesafety of earthing system Make-OBO/Dehn/ABB |
| 46 | Installation of The above arrangements including all accessories as per Direction of Engg. In charge. |
| 47 | Street light--- S/F of Street light- 90W,120 lm/w efficacy ,IP PC Lens, IK08 new generation energy saving & environmental friendly long life versatile pressure die-cast alluminium IP66 roadway luminaire with high power LED as light source with acrylic cover(Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) (5Years Warranty) |
| 48 | Supply of 6 mtr long hot dip Galvanized Octagonal pole manufactured from HT steel(single arm) as per BS EN 10025/IS 2062 having minimum yield strength of 350 N/ SQMM having top dia of 70 MM A/F and bottom dia of 130 MM A/F of 3 mm thick or more , base plate as per IS 2062 complete with 4 nos. En 8 grade foundation bolts to withstand basic wind speed of 180 KM/HR wind speed (As per structural calculation of pole manufacturer )or more (Make of poles: Utkarsh/Bajaj/RR Ispat/Vakarangee as per direction of Engg. in Charge. |
| 49 | Installation of pole by making the suitable size foundation by embeding the pole 1 mtr into the ground with necessary civil work and fixing the light on the pole equievalant make ISI marked as approved as per direction of Engg. in Charge. |
| 50 | Supplying, Erection, Fixing, connection & testing of LED BOUNDRY WALL Light of elegant look (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) 35 W LED street light having die cast aluminium housing with toughened glass having lumen efficacy of 110 lm/w or more (As per LM 79 report of third party NABL lab) ,IP 65 protection or more , LED street light model having warrantied for a period of 5 years . The luminaire should be supplied along with bracket maintenance free for inspection as required as per direction of Engg.-in-Charge. |
| 51 | Supplying, Erection, Fixing, connection & testing of 100W FLOOD Light(120LM/W) of Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) maintenance free having 5 years warranty wit including MCB,stainless steel braket along with driver & including with foundation as per the Drawing for inspection as required & as per direction of Engg.-in-Charge. |
| 52 | S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 53 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 54 | CABLING--Supplying and laying of one number PVC insulated armoured and PVC sheathed XLPE AL. conductor power cable of 1.1 KV grade POLYCAB/KEI/HAVELLS/Gloster/Finolex/RR Kabel of following size cables as per direction of Engg.-in-Charge.Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. 4core x 16 sq mm |
| 55 | 4core x 6 sq mm |
| 56 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 57 | Supplying and making end termination with brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 4core x 16 sq mm |
| 58 | 4core x 6 sq mm |
| 59 | Supplying,laying of 3cx2.5 sq.mm copper flexible cable with insulated cover of reputed make,ISI marked with all other concerned materials as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.Make- POLYCAB/KEI/HAVELLS/Gloster/Finolex/RR Kabel |
| 60 | Providing,fixing and laying of fallowing dia PN10 HDPE pipe (medium class) in ground complete with fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 32mm |
| 61 | S/I/T&Commissioning of LT OUT DOOR FLOOR mounted cubical type IP66 based panel made out by 2mm CRCA steel sheet duly derusted & pented by simens gray powder cote paint is designed as G.A drawing. (FOR USE) with 63A TPN MCB 01 NO,1 no. Astronomical digital timer, AUTO MANUAL(with start and stop push button) SELECTOR 63 A 3P contactor, OLR,RYB,ON,OFF trip indication, Type-II SPD 40ka ,,04 nos 10A 4P MCB,C,10KA as outgoing MCB legrand dx3/ schneider acti9 A9N/ Siemens betaguard/ ABB ( SB 200) as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period 1 years of acceptance of materials |
| 62 | Highmast lightingSupply,installation,testing and commissioning of 12M high mast shaft in two sections suitable for 200 km/hr wind speed along with head frame, luminaires carriage suitable for 6 luminaires in symmetrical arrangement and other accessories manufactured in factory. ( Bottom 360mm / Top -150mm, 3mm thickness, 445PCD, diameter of base plate 520mm including supplying of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightning finial. (Wiring material from JB to individual luminaire & MCB in base compartment are not included and are a part of installation)along with foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template along with Construction of shallow foundation with M20 grade concrete for the highmast considering the safe soil bearing capacity at site as 10 T/sqmtr at 2 metre depth with all materials and labour.Erection of the high mast with the help of suitable tools and plants, wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq. mm, lugs, MCB and all labour . Provision of GI pipe earthing for High mast with 2.5 M long 40 mm dia GI Pipe including connection to High mast earth terminal with 25 x 3 mm GI flats with all materials and labour. (2nos per mast required) Approved colour after treatment along with provision of masonary pedestal duly finished with plaster and painting with GI pipe for cable entering as required.. (2nos per mast required) (Make:-Bajaj/ Utkarsh/ Vakrangee/RR ISPAT/Valmont |
| 63 | SITC of 400W Outdoor Flood LED lights with silicon potted driver, IP66, , bottom opening maintanance , LPW not less than 130.Input Voltage: 85-265V AC ,Body : Die cast Aluminium, IP66 as per the Drawing for inspection as required & as per direction of Engg.-in-Charge. Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj as rerquired. |
| 64 | SITC of LED type single dome aviation obstruction light. (Make:-Bajaj/ Utkarsh/ Vakrangee/RR ISPAT/Valmont |
| 65 | S/I/T&Commissioning of LT OUT DOOR FLOOR mounted cubical type IP66 based panel made out by 2mm CRCA steel sheet duly derusted & pented by simens gray powder cote paint is designed as G.A drawing. (FOR USE) with 63A TPN MCCB 01 NO,1 no. Astronomical digital timer, AUTO MANUAL(with start and stop push button) SELECTOR 63 A 3P contactor, OLR,RYB,ON,OFF trip indication, Type-II SPD 40ka ,,08 nos 10A 2P MCB,C,10KA ,02 nos 10A 4P MCB,C,10KAas outgoing MCB legrand dx3/ schneider acti9 A9N/ Siemens betaguard/ ABB ( SB 200) as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period 1 years of acceptance of materials |
| 66 | MAIN PANEL FOR HIGH MASTS/I/T&Commissioning of LT OUTDOOR floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. (FOR ALL HIGHMAST)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.3P+N Type 2 SPD 40 kA with 63A 4P MCB,10kA, Cseries shall be installed in the incomer. 20X10MM Separate Aluminium Earth bus bar should be installed..In commer-1-01 number of 100A 4P Icu=100%Ics,25Ka MCCB with TMR based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB Formula Busbar-1&2 04 numbers of 200Amps Aluminium busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing) Out going- 05 numbers of 63Amps 4P MCCB.Icu=100%Ics,16Ka TMR based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB Formula Out going- 2 numbers of 32A 4P MCB10KA,C series ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200) Out going- 4 numbers of 63A 4P MCB10KA,C series ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200) Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse. (ii) 01 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication |
| 67 | HVAC WORK(SPLIT TYPE)-AIR CONDITIONER SPLITSITC of 2.0 TR high wall 5 star inverter type split A.C machine (BTU/Hr-21000-24000) with copper condensor & evaporator having ambient temperature 52 degree celcius with comprehensive 1 year warranty,5 years warranty on PCB, 5 years warranty on compressor (Make:O-General/Diakin/Mitsubishi/Hitachi) |
| 68 | REFRIGRANT PIPING-- Supply,installation of hard/soft copper refregrant piping of size 5/8 inch and 1/4 inch for suction and liquid line with 3 corex4 sqmm FRLS Copper control cable alongwith 25 mm Factory laminated GC Cloth weather proof closed cell nitrile insulation ,complete with fitting of bends and other nesessary material to complete the job. 1 TR to 3 TR high wall split A.C |
| 69 | FRAME WORK-- Supply,installation & fabrication of MS base frame for both indoor and outdoor unit and other nesessary material to complete the job.1 TR to 3 TR high wall split A.C |
| 70 | DRAIN PIPING- Supply,installation & fabrication of Insulated drain water piping from indoor to nearestdrain point separate to all and other nesessary material to complete the job. 25mm nom. Dia pipe |
| 71 | Supply and fixing of 5kVA Voltage stabilizer (Make-V-Guard/Microtek |
| 72 | FIRE EXTINGUISHERS-- Providing and Fixing ISI marked ABC stored pressure type Fire extinguisher of 6 Kgs. Capacity confirming to IS: 15683 with discharge hose, nozzle, Mono Amonium Phosphate base & ABC powder pressurised with nitrogen gas carrying handle and wall mounting bracket etc as required.Make-Safex/Fireshield/Ceasefire/Flameklog |
| 73 | Providing and Fixing of 4.5 Kgs. Capacity CO2 gas type ISI marked fire extinguisher (IS: 15683) fitted with high pressure 1 mtr. Long discharge hose & horn complete with refill gas, carrying handle and wall mounting bracket etc as required.Make-Safex/Fireshield/Ceasefire/Flameklog |
| 74 | Providing and Fixing of of 2 kG capacity Eco Friendly, Stored pressure type filled with HFC 134 A ( clean agent fire extinguishant having Zero Ozone depletion potential ) Clean Agent Fire Extinguishers with safety seal, pressure guage, controllable discharge mechanism, helium leak detection tested and conforming to IS 15683 complete with initial charge as required.Make-Safex/Fireshield/Ceasefire/Flameklog |
| 75 | Providing and Fixing of Mechanical Foam type fire extinguisher 9Lts. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket etc. complete, confirming to IS: 15683.Make-Safex/Fireshield/Ceasefire/Flameklog |
| 76 | Supplying and installing at approved location approved make fire buckets at 24 gauge galvanized stseel sheet, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letter \\"FIRE\\" in black and gold. Cost shall be inclusive of Providing MS stand duly painted over a coat of primer (one stand shall be suitable for hanging 5 buckets. |
| 77 | SIGNAGES: SITC of Flexyle Photoluminescent based Glow-in-the-dark sheeting with luminious properties enclosed in a weather-proof UV stabilized film with UV screen printing by imported inks pasted over 3 mm Thick Cast Acrylic Sheet with the Protection of 3 mm Thick Cast Acrylic from Front side with stud type mirror screw for floor indication, fire exit, hydrant, hose reel, fire extinguisher, MCP, fire alarm panel, in case of fire, lift, alarm valve signages, FIRE EVACUATION PLAN |
| 78 | Illumination Glow light for Exit Indication with Battery Back-up. Please Enable Macros to View BoQ information |