| 1 | Supply & Erection of 33 KV section Double Pole Structure (Riser) 11 Mtr. Long SP-55 Type S.T. Pole (Bottom Portion Galvanised) made of following types of supports duly grouted 1:4:8 (1cement,4 coarse sand and 8 brick ballast 40mm size) Plinthed plastered and painted in the same manner as already specified for respective supports with 02 Nos. MS channels of size 125x65mm, 01 No. 100x50m Size and 65x65x6 mm angle iron bracing fixed with MS clamp of size 75 x10 mm & 03 Nos. Pin Insulator etc. complete with all material labour and T&P etc. required for proper completion of work as per direction of E/I. Make:- (Only manufacturers whose GTP will be Approved in MVVNL) |
| 2 | Supply of following size H.T. cable standered compacted circular Al. conductor screen with extruded semi conducting compound, XLPE insulated in copper Tape, cores laid up to innersheath of PVC, Galvanised Steel Strip Armoured & overall sheathed cable confirming to IS 7098 (Part-2) 2011 with upto date Ammendments complete in all respect as per Direction of E/I. Make (Polycab/ Gloster/KEI/ Universal / Finolex/ Havells) |
| 3 | 300 Sqmm 3 core |
| 4 | S/F and jointing of Indoor/outdoor 33 KV jointing kit (Heat Sink) per XLPE cable including cost of all material Labour and T & P as per proper completion of work as per direction of E/I. Make (Raychem/3M) |
| 5 | 240-300 Sqmm 3core Indoor type as per DSR 2022 SI No. 10.7.3 |
| 6 | 240-300 Sqmm 3core Outdoor type as per DSR 2022 SI No. 10.8.3 |
| 7 | S/F of G.I. Pipe of following sizes for cable duly clamped with supports by 2 No. with clamps of 50 x 6 mm M.S. flats bolts, Nuts and washer required for proper completion of work. Make (TATA/SAIL/JINDAL) |
| 8 | 150 mm dia (18.20 Kg/M) |
| 9 | Supply of HDPE pipe upto PN-6 working pressure Rating material Grade PE-80 Nominal dia (OD) 160 mm 9.50 mm thickness complete in all respect as per relevants I.S. Technicals specification. |
| 10 | Drilling of Road Parallely & Road Crossing at a depth of 2 to 3 Mtr. as required & laying charges of cable & 160mm Dia HDPE Pipe complete with all material, labour, Drilling machine & required T&P etc. required for proper completion of work as per Direction of E/I. |
| 11 | Laying of 33 KV XLPE Cable in loop and On Pole with clamping etc. Complete in all respects with all required material & T&P etc as per direction of E/I as per PWD SOR 2024 S.I. No 20 c.1.19 |
| 12 | Supply & Making of suitable earth of O/H line pole with 2.5 Mtr. Long 20 mm dia M.S. rod complete with 7/16 SWG G.S. wire in 2.00 Mtr. Long 15 mm dia G.I. Pipe (0.96 Kg/Mtr.) duly clamped on pole with 3 No.s 20 x 3 mm M.S. Flate clamp with bolts nuts and washers complete with all material labour and T&P etc. required for proper completion of work. |
| 13 | S/F of danger board of size 200 x 250 x 1.6 mm of M.S. sheet fixed with clamp of 20 x 3 mm M.S. flate including bolts, nuts and washerduly painted completed with all material, labour and T&P etc. for proper completion of work. |
| 14 | S/F of barbed wire (1.5kg) duly clamped with 2 No. clamps made of 20x3mm MM. at both ends on poles flate including bolts, required for nuts and T&P etc. required for proper completion of work. |
| 15 | S/F of cable route marker made of 1:2:4 R.C.C. Block size 1000x400x100 mm grouted with 1:3:6 cement stone grit coarse sand 30cm below G.L. with painting numbering & marking etc. complete with all required material T&P etc. complete in all respects as per direction of E/I. (As per drawing atteched) |
| 16 | Supply, Installation, Testing & Commissioning of 33kv, 630A, 25kA/1Sec, 4-Way, non extensinle outdoor IP55, SF6 Gas insulated Ring Main Unit consist of four (3) motor operated Vacuum Circuit Breaker (VCB), and (1) one motor operated load break Switch, with Suitable site replaceable bushing and full front door cover, as per attached BOM (Ann II) (Configuration: CVVV) Make ABB/Schneider/Siemens |
| 17 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D) Make as approved in UPPWD & CPRI Certified |
| 18 | Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect.UPPWD SOR-2018 item no. 717 |
| 19 | Construction of plinth for 33 KV CVVV RMU Size (3x1.25x0.5Mt) With All Meterial, labour and T & P Required for proper completion of work as per specification drawing and direction of E/I (as per specification attached) |
| 20 | Construction of fencing plinth for RMU of following sizes in Ist class brick work including plaster and providing flat bricks soling and pointing the same with 1:2 cement and fine sand mortar over 75mm thick cement concreting in the ratio 1:6:12 in open space of the cage as per direction of E/I and drawing |
| 21 | 4 x 2.25 M For 33 KV CVVV RMU |
| 22 | Supply of fixing of 2.5 Mtr. High cage fabricated with 4.0mm thick chain link /wire mesh of equivalent weight fixed on 50x50x6mm angle iron frame having vertical members spaced at 1.0M to 1.25M. and horizontal members spaced at 1.20M the vetical members shall be grouted in ground and horizontal members in the wall to a depth of 300mm with ends folded. The cage shall have 1000x2000mm size single leaf door with locking arrangement having door frame fabricated with 40x40x5mm angle iron and 4 mm expanded G.I. wire mesh of equivalent weight duly fixed with the cage member. The cage shall have nut bolt arrangement for opening the sides by providing tees 45x20cm of angle iron size 50x50x6mm as per direction of E/I. It shall be painted with red oxide primer and synthetic enamelled paint as per direction of E/I. including all materials, labour and T & P for proper completion of work. As per PWD SOR 2018 S.I No 1142 Please Enable Macros to View BoQ information |