| 1 | H.T. Work |
| 2 | S/Erection of 11 KV section Double pole structure (Riser) made of following types of supports duly grouted in 1:4:8 cement concrete (1 cement, 4 coarse sand and 8 grit of 20mm nominal size) Plinthed, Plastered and painted in the same manner as already specified for respective supports with one nos. channels of size 100x50mm and 75x40mm M.S. channel and 2 Nos. bracing of angle iron size 65x65x6mm 3M length fixed with packing piece and bolt and nuts as required including cost of material, labour and T & P required for proper completion of work as per direction of E/I. |
| 3 | 11 Mts. long 410 SP-55 |
| 4 | Supply of following size 3 Core 11 KV H.T. cable standered compacted circular Al. conductor screen with Extruded Semi conducting compound, XLPE insulated in copper Tape, cores laid up to innersheath of PVC, Galvanised Steel Strip Armoured & overall sheathed cable confirming to IS 7098 (Part-2) 2011 with upto date Ammendments complete in all respect as per Direction of E/I. Make (Polycab/ Gloster/KEI/Finolex /Universal/ Havells) |
| 5 | 300 Sqmm 3 Core |
| 6 | Supply and jointing of 11 KV jointing kit (Heat Sink) per XLPE cable including cost of all material Labour and T & P as per proper completion of work as per direction of E/I. Make (Raychem/3M /Densons) as per DSR 2022 S.No. 10.4.4 & 10.5.4 |
| 7 | 300 Sqmm 3core Indoor type |
| 8 | 300 Sqmm 3core Outdoor type |
| 9 | Supply of HDPE pipe upto PN-6 working pressure Rating material Grade PE-80 Nominal dia (OD) 160 mm 9.50 mm thickness complete in all respect as per relevants I.S. Technicals specification. |
| 10 | Drilling of Road Parallely & Road Crossing at a depth of 2 to 3 Mtr. as required & laying charges of cable & 160mm Dia HDPE Pipe complete with all material, labour, Drilling machine & required T&P etc. required for proper completion of work as per Direction of E/I. |
| 11 | Laying of 11 KV XLPE Cable in loop and On Pole with clamping etc. Complete in all respects with all required material & T&P etc as per direction of E/I as per PWD SOR 2024 S.I. No 20 c.1.19 |
| 12 | S/F of following type of G.I. pipe \\"B\\" class for cable clamped with supports by 3 Nos. clamps made of 20x3mm M.S. flat and suitable size of nut bolt and washer required for proper completion of work as per direction of E/I. Make(TATA/SAIL/JINDAL) |
| 13 | 100 mm dia |
| 14 | Making suitable earthing of ST poles with 2.5Mts. long 20mm dia M.S. rod with 7/16 SWG G.S. wire in 15mm dia 2Mtr. long G.I. pipe duly clamped with 3 nos clampes and binding on poles including cost of labour & T & P etc. required for proper completion of work. |
| 15 | S/F of danger board (H.T.) size 200x250 mm at suitable height of pole as per direction of E/I |
| 16 | S/F of barbed wire (1.5kg) duly clamped with 20x3mm M.S. flats at both ends on steel poles at suitable height as per direction of E/I. |
| 17 | S/F of cable route marker made of 1:2:4 R.C.C. Block size 1000x400x10 mm grouted with 1:3:6 cement stone grit coarse sand 30cm below G.L. with painting numbering & marking etc. complete with all required material T&P etc. complete in all respects as per direction of E/I. |
| 18 | Supply, installation, testing and commissioning of 11kV Outdoor type Fuse type 4 way Ring Mains Unit consisting of 2Nos. 11kV 630A Load Break Switches only for Incoming & 2 Nos. 11kV 630A Load Break Swithes with suitable 11kV HRC Fuses along with suitable Terminal arrangement ( With 1 Set Spare 11 KV HRC Fuses) to connect atleast 300sqmm 3 Core 11kV HT Cable. The RMU shall be Extendible type suitable for Outdoor Installations & Fabricated out of 2mm thick CRCA Sheet Steel duly painted with PowderCoated Paint, The Bus Bar shall be 630A Auminum & shall duly supported by 12kV Grade Epoxy Inulators suitable to bear teh jerks of Shorth Circuit 25kA for 1 Sec. The job shall be completed in all respect including suitabe Foundation for Installation of RMU Complete with all required meterial and T&P etc. as per direction of E/I. |
| 19 | Construction of plinth for 11 KV 4 Way RMU Size (3x1.25x0.5Mt) With All Meterial, labour and T & P Required for proper completion of work as per specification drawing and direction of E/I (as per specification attached) |
| 20 | Construction of fencing plinth of following sizes in Ist class brick work including plaster and providing flat bricks soling and pointing the same with 1:2 cement and fine sand mortar over 75mm thick cement concreting in the ratio 1:6:12 in open space of the cage as per direction of E/I and drawing |
| 21 | 4 x 2.25 M For 4 Way R.M.U |
| 22 | Supply of fixing of 2.5 Mtr. High cage fabricated with 4.0mm thick chain link /wire mesh of equivalent weight fixed on 50x50x6mm angle iron frame having vertical members spaced at 1.0M to 1.25M. and horizontal members spaced at 1.20M the vetical members shall be grouted in ground and horizontal members in the wall to a depth of 300mm with ends folded. The cage shall have 1000x2000mm size single leaf door with locking arrangement having door frame fabricated with 40x40x5mm angle iron and 4 mm expanded G.I. wire mesh of equivalent weight duly fixed with the cage member. The cage shall have nut bolt arrangement for opening the sides by providing tees 45x20cm of angle iron size 50x50x6mm as per direction of E/I. It shall be painted with red oxide primer and synthetic enamelled paint as per direction of E/I. including all materials, labour and T & P for proper completion of work. As per PWD SOR 2018 S.I No 1142 |
| 23 | Transformation Work |
| 24 | Supply and Erection of Double Pole (Bottom Portion Galvanised) 11 Mtr. long 410 SP-55 S.T. pole support duly grouted, plinthed , plastered & painted in the same manner as already specified for respective supports suitable for pole mounted type substation with different types of M.S. channels and angle iron duly fabricated for Disc fittings TPMO, D.O. fuse, outside dropper & bracings including cost of material, labour and T&P required for proper completion of work as per drawing and direction of E/I. |
| 25 | S/F of 11 KV TPMO set complete with all material, labour, T&P etc. required for proper completion of the work. |
| 26 | S/E of 11 KV D.O. fuse set complete with all material, labour, T&P etc. required for proper completion of work. |
| 27 | Supply, Installation, Testing and Commissioning of 11/.433 KV, 63 KVA (EE Level-1) Transformer of following capacity including Loading, unloading, local carriage with all material, labour, T&P required for proper completion of the work. |
| 28 | S/F of H.T/L.T jumpering and connection on double pole/four pole. lightening arrestors & T/F including cost of all material, labour T & P etc. required for proper completion of work. |
| 29 | S/F of lightening arrestor set (3 Nos.) suitable for mounting on steel supports complete with all materials, labour and T & P required of proper completion of work as per direction of E/I. |
| 30 | S/F of following GI pipe 'B' class for cable duly clamped with supports by 3 nos. with clamps of 20x3mm M.S. flat bolts nuts & washers required for proper completion of work. |
| 31 | 100 mm Dia (10.20Kg /Mtr.) |
| 32 | Supply and burring of Safe Earthing Electrode T-39 ( Hot Dip Galvanized) Length up to 3000mm, outer Dia 50mm inner 25mm, terminal Dia 12mm, outer G.I. Pipe of 16 SWG with Hot Dip Galvanization upto 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity & one earthing lead of 25 x 3mm G.I. Strip, up to switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. As per PWD SOR-2018 S.I. No.-725 (B)Make: As approved in U.P. P.W.D., & C.P.R.I. Certified |
| 33 | Supply and Laying of XLPE cable 11 KV grade at a depth of 1.20 Mtrs below GL over a cushion of 75mm thick sand alround protected with bricks on sides and top on surface the cable run shall be fixed on M.S. Clamp etc. of suitable size and arossing the road cable shall run through 150mm dia hume pipe size of G.S. wire 7/10 SWG clipped at several places as directed by E/I for proper completion of work. The armouring of cable shall be properly connected with earth conductor by clamps etc. of following sizes (as per specfication-28) |
| 34 | 3x120 sqmm As per PWD SOR-2018 S.I. No.-506 (f) |
| 35 | S/F and jointing of 120 Sqmm out door Type Jointing kit (Make Raychem/Densons/3M) As per DSR-2022 S.No. 10.5.2 |
| 36 | Supply & Laying of Al. conductor PVC insulated armoured served sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side on top. On surface the cable sun shall be fixed on M.S clamps of suitable size or as directed by the E/I, complete in all respect. The Armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 37 | 70 sqmm 3.5 core (PWD SOR-2018 SI No. 501(m) |
| 38 | Supply and fixing of palm or pin copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects (as per PWD SOR 2018 SI No. 504). |
| 39 | 35 Sqmm |
| 40 | 70 Sqmm |
| 41 | Street Light Work |
| 42 | Supply & fixing of 9 mtr. GI Octagonal Pole of approved make (top dia 70 mm, Bottom dia 155 mm and base plate 16 mm thick) having 3 mm thickness with single arm bracket length of 1 mtr length in 1:2:4 RCC Foundation bolt including the cost of foundation, excavation & back filling and Required T&P complete in all respect. UP PWD SOR 2024 SI No-21.2.4 Make Bajaj/Vallmont/RRISPAT CONSOUL (Without GST Rate 30046.00x0.8475=25464.00) |
| 43 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body with toughend glass/ UV stablised PC cover and lenses suitble and 1 no 6 Amp SPMCB Complete driver set suitable for 110 to 130 watt Confirming to IP 66 and IK07 and above Protection having company LOGO engraved complete in all respect including labour.PWD SOR 2024 SI No-23.17 CAT-AAA Make Havells/Polycab/Philips/Jaquar |
| 44 | Supply and fixing of 12.5 mtr. High Mast shaft of approved make with rising system hot dip glavanized inside & out side dip, heaving pole sheet thickness 3 mm. Top dia minimum 150 mm, botom dia minium 310 mm, base plate 25 mm thick, suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 luminales & its control gear boxes 0.75 HP Power tool motor, 3 point suspension system with steel wire rope 6mm dia, double drum winch, including making suitable foundation as per manufacture drawing/site recuirment along with foundation bolts nuts, washers, anchor plates etc complete in all respect. PWD SOR 2024 SI No-21.3 |
| 45 | Supply and fixing of factory wired integral LED flood light luminaries with die cost aluminium housing with toughend glass/UV stabilized PC cover and lenses built with mandatory driver set suitable for 170 to 200 Watt. Confirming to IP 66, IK 07 and above protection complete in all respect including Labour. 20400-24000 system lumens, High power LED with lense, >120 Lm/W, P.F.>0.95 THD <10% at full load, CDI >70, potted driver Set in Metal housing (Not Circuitory) Phase to phase Protection at 440V & >300V auto cut and re-start feature, 4 KV internal Surge Protection, with 5 year warrantee. CAT-AAA. UP PWD SOR 2024 SI No-23.26 (Without GST Rate 17337.00x0.8475=14693.00) |
| 46 | S/F of following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contractors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect UPPWDSOR 2018 SI No-807 |
| 47 | 40 A TPN |
| 48 | Making suitable earthing of PCC/ST poles with 2.5Mts. long 20mm dia M.S. rod with 7/16 SWG G.S. wire in 15mm dia 2Mtr. long G.I. pipe duly clamped with 3 nos clampes and binding on poles including cost of labour & T & P etc. required for proper completion of work. |
| 49 | Supply and burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000mm, outer pipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing. (From electrode terminal to switch board, cost of 25 x 3 G.I. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.UPPWD SOR-2018 item no. 726 (D) |
| 50 | Supply & Laying of 25mm x 3mm G.I. Strip from Earth Electrode directly in the ground as required complete in all respect as per PWD SOR 2018 S.No. 716 |
| 51 | Supply and Laying of following Size of Aluminium Conductor PVC Insulated armoured served sheathed cable 1100 Volt grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engieer in Charge complete in all respect including excavation and refilling and crossing the road, cable should run through 140mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I. wire, clipped at several places as per direction of E/I for proper completion of work. The armouring of the cable shall be properly connected with the earth conductor by clamps etc as per PWD SOR 2024 S.No. 20a.1.8 & 20a.1.11 Make Polycab/Gloster/Finolex /Universal /KEI /Havells (Without GST Rate 618.00x0.8475=524.00 and 724.00x0.8475=614.00) |
| 52 | 10 Sqmm 4 Core |
| 53 | 35 Sqmm 3.5 Core Please Enable Macros to View BoQ information |