| 1 | M&L for inspecting and servicing of electric Overhead Traveling (EOT) Crane of capacity 5 Ton installed at tech area (AF) station Chandigarh including assemblies inspection to maintenance of following:-(a) longitude travel motion and cross travel motion:(i) Checking of gear box oil level and filling with required oil.(ii) Brake adjustment.(iii) Checking of long travel & cross travel wheel for any noise/ malfunctioning.(iv) Checking grease of gear coupling, nut tightening and replacement of grease nipple.(v) Checking of oil in hydraulic thruster brake, and filling with required qty of oil.(vi) Checking of electric motor connections, insulation resistance value etc.(vii) Checking the cut off at extreme ends with the limit switch.(viii) Checking and greasing of shaft pedestal. |
| 2 | (b) Hoist motion: (i) Checking gear box oil level and filling with required oil.(ii) Brake adjustment.(iii) Checking of main bearings of the rope drum including greasing the same.(iv) Checking grease of geared couplings and nut tightening. (v) Checking of oil in hydraulic thruster brake and filling with required qty of oil.(vi) Checking of electric motor connections, insulation resistance value.(vii) Checking wire rope for any damage & greasing the rope.(viii) Adjustment of the rotary limit switch.(ix) Checking of bearing of the hook and greasing the same.(c) Electric panel:(i) Checking of contactors for overheating or flashing.(ii) General checking of contacts and connections thimbles etc.complete all as specified and directed. |
| 3 | S&F in replacement Gear Pinion & Super Gear of EOT crane complete all as specified and directed. |
| 4 | S&F in replacement Gear Key of EOT crane complete all as specified and directed. |
| 5 | S&F in replacement Coupling Kit of EOT crane complete all as specified and directed. |
| 6 | S&F in replacement 6sqmm 4core PVC insulated and FRLS PVC round sheathed Copper conductor (Flexible) industrial cable 1100 volts conforming to IS 694 of the crane motor complete all as specified and directed. |
| 7 | S&F in replacement of Carbon Bush Set 160 Amp complete all as specified and directed. |
| 8 | S&F in replacement of Brake Set of EOT crane 5 ton capacity of make as per site complete all as specified and directed. |
| 9 | S&F in replacement VFD Device suitable for 5 Ton EOT Crane of make: ABB |
| 10 | S&F in replacement Limit Switch suitable for 5 Ton EOT Crane. |
| 11 | M&L for overhauling and re-alignment of unserviceable manually operated Hanger Doors of any size/ height including replacement of defective bearing and grinding of wheels for smooth movement of doors, replacement of clamps, bolts etc. including cleaning, oiling and greasing of moveable parts and welding work complete all as specified and as directed. |
| 12 | Taking out unserviceable manually operated Hanger Door Wheel with pin and supply, fixing and testing hanger door wheel with pin in existing size suitable for hanger door and model complete all as specified and as directed. |
| 13 | M&L for overhauling and re-alignment of unserviceable Door Rolling Shutters of area n.exc. 12 Sqm including replacement of defective bearing and grinding of wheels for smooth movement of doors, replacement of clamps, bolts etc. including cleaning, oiling and greasing of moveable parts and welding work complete all as specified and as directed. |
| 14 | Supply, installation, testing and commissioning DOL Starter in sheet steel enclosure single phase starter type MK-I, single phase DOL, 6-10 A, 360 volts including taking down existing starter of any type & capacity complete all as specified and directed. MAKE: L&T/ BCH/ SIEMENS/ C&S. |
| 15 | Supply, installation, testing and commissioning Reverse Starter 3 phase, 415 volts, 20/ 15HP/ KW, relay rating 23-32 Amp, SS enclosure grouting in wall including making all incoming & outgoing connection and testing in full load including taking down existing reverse starter of any type & capacity from hanger door complete all as specified and directed. MAKE: C&S/ BCH/ SIEMENS/ L&T/ HAVELLS. |
| 16 | M&L for attending Hanger Motorized Doors Complaints of any nature pertaining to electrical & mechanical problem of hanger motorized door like long travel, all motion motors, control panel, pendent control box, MCB's contactors, steel wire rope, control cable, push greasing of rope, loose nut bolts etc. and rectification of the fault and replacing the unserviceable items as per site requirement including making connection and testing after completion of Job complete all as specified and directed. |
| 17 | Taking out unserviceable Steel Wire Rope of any size from hangar door and supply, fixing, testing & commissioning steel wire rope multi stranded 6/ 19 center fiber core, 6 to 8mm dia complete all as specified and directed. Make:- Usha Martin/ MAHADEV or equivalent as approved by GE. |
| 18 | Taking out unserviceable Steel Wire Rope of any size from hangar door and supply fixing testing & commissioning steel wire rope multi stranded 6/ 19 center fiber core, 10 to 12mm dia complete all as specified and directed. Make:- Usha Martin/ MAHADEV or equivalent as approved by GE. |
| 19 | Taking out old unserviceable Ball Bearing of any size and supply and fixing of ball bearing (Hanger Door) 6308 ZZ/ as per existing complete all as specified and directed. |
| 20 | Taking out old burnt out unserviceable Motor 3 HP capacity and transporting to workshop to facilitate the repair work and carrying out repair work as under:-(i) Strip opening of the burnt stator of 3 HP induction motor and taking out the burnt copper wire from stator.(ii) Cleaning of the stator slots and removing the unwanted deposit in the stator.(iii) M&L for rewinding of the motor with standard gauge super enameled copper wire and varnishing the same after rewinding including insulating materials etc.(iv) Assembling of the motor and transporting to the camp site for fixing in the door mechanism.(v) Testing for same for its operation to the entire satisfaction of Engineer-in-Charge. |
| 21 | All as per item No. 19.00 above but for 5 HP capacity. |
| 22 | All as per item No. 19.00 above but for 7.5 HP capacity. |
| 23 | M&L for comprehensive systematic maintenance and annual inspection service of Fire Alarm System to provide routine maintenance, examination, service according to recommended schedule of maintenance/ service by the manufacturer in working hrs (i.e. Monday to Friday from 0900 to 1700 Hrs) except scheduled holidays to furnish the necessary parts and cleaning material including the replacement of any defected parts of misc nature and ensure overall serviceability of the fire alarm system including repair/ maintenance of the following parts of the system in addition to attend for annual government inspection complete all as specified and directed. |
| 24 | M&L opening and servicing of Panel 8 Zone including repair/ replacement and updation of electronic components including replacement of battery set wiring, nuts bolts, switch, sockets etc. wherever required complete all as specified and directed by Engineer-in-Charge. |
| 25 | M&L for complete servicing with necessary repair/ replacement of MCP and Hooter complete all as specified and directed. |
| 26 | S&F in replacement microprocessor based 1 loop capacity networkable analogue addressable type Fire Alarm Control Panel with 80 character LCD display, loop shall have a capacity of 318 analog addressable devices in one loop. Four access levels, capabale of taking Flash scan devices (like detectors, LCP's, hooters, control modules, monitor modules, fault isolation, response indicators, audio visual signals central processing units, complete with LCD display, zone indicating LED's having multiple access levels), flash EPROM sufficient numbers of programmable relay controls for controlling AHu's, pressurization fans, ventilation fans, monitoring of fire hydrants pump, 240 volts AC power supply, automatic battery charger, sealed maintaince free lead acid battery - 02 Nos of cap 12 volts 180 AH sufficient for 24 hours normal workiing and then be capable of operating the system for 2 hours during an emergency conditions as required. (UL 9th Edition approved) Make : Notifer by Honeywell, Ravel, JCI/GST. |
| 27 | S&F in replacement microprocessor based 2 loop capacity networkable analogue addressable type Fire Alarm Control Panel with 80 character LCD display, loop shall have a capacity of 318 analog addressable devices in one loop. Four access levels, capabale of taking Flash scan devices (like detectors, LCP's, hooters, control modules, monitor modules, fault isolation, response indicators, audio visual signals central processing units, complete with LCD display, zone indicating LED's having multiple access levels), flash EPROM sufficient numbers of programmable relay controls for controlling AHu's, pressurization fans, ventilation fans, monitoring of fire hydrants pump, 240 volts AC power supply, automatic battery charger, sealed maintaince free lead acid battery - 02 Nos of cap 12 volts 180 AH sufficient for 24 hours normal workiing and then be capable of operating the system for 2 hours during an emergency conditions as required. (UL 9th Edition approved) Make : Notifer by Honeywell, Ravel, JCI/GST. |
| 28 | S&F in replacement of automatic floating sensitivity type analog addressable acclimate photo thermal Smoke and Heat Detector with mounting base LED , address switch from 01-159, to programme the detectors, complete as required (in changing environment area) Make : Model No FAPT-851(A) of Notifier by Honeywell or equivalent model of Ravel/GST/JCI |
| 29 | S&F in replacement Sounder cum Strobe at respective places. Make : Notifier by Honeywell, Ravel, JCI, GST |
| 30 | S & F in replacement of 2 core 1.5 sqmm FRLS copper cable 1100 Volts grade in concealed with copper jointing materials and all accessories required drawn and through and including 20mm dia stove enamelled MS conduit (ISI marked) complete all as specified |
| 31 | S&F in replacement of single ended reflector type addressable Beam Smoke Detector with monitor module 4 manual and 2 acclimate sensitivity setting address switch to programme the detectors including necessary power, communication wiring, mounting accessories for integrating with main fire alaram control panel complete as required. Make : Notifier by honeywell/ Ravel/JCI |
| 32 | S&F in replacement addressable type Fault Isolator Module for isolating shorted, dewired and loose circuits between two successive fault isolators with automatic resetting arrangement base Model : Notifier by Honeywell or equivalent model of Ravel, JCI/GST |
| 33 | S&F in replacement addressable Control Input Module for hooters/ sounders / strobes etc Make : Notifier by Honeywell or equivalent model of Ravel/ JCI/GST |
| 34 | S&F in replacement addressable Control Output Module for hooters/ sounders / strobes etc Make : Notifier by Honeywell or equivalent model of Ravel/ JCI/GST |
| 35 | S&F in replacement Response Indicator having twin LEDs for mounting of false ceiling/ wall at the entries of the cabin for indicating the operational of detectors in the above false ceiling/wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling below the false flooring detectors etc as required Make : Notifier by honeywell/ Ravel/ JCI |
| 36 | M&L for visiting and labour charges once in three months including inspecting all the smoke detectors, MCP, hooters including general maintenance like fitting/ tightening of connections and clearing all issues if any for un-interrupted working of the fire alarm system complete all as specified and directed by Engineer-in-Charge.Note: The contractor shall replace of spares/ components free of cost related to the normal wear and tear and other minor electrical/ electronic or mechanical parts as required at the time of inspection for smooth functioning of system all as specified and directed by Engineer-in- Charge. |
| 37 | Supply, install, connecting & commissioning in replacement Battery 12 volts DC 180 AH 25 plates, including disconnecting & taking out old, complete all as specified and directed. Make: Amaron/ TATA Green/ Standard. Please Enable Macros to View BoQ information |
| 38 | Supply, install, connecting & commissioning in replacement Battery 12 volts DC 180 AH 25 plates, including disconnecting & taking out old, complete all as specified and directed. Make: Amaron/ TATA Green/ Standard. Please Enable Macros to View BoQ information |