| 1 | Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr deep in soft/loose soil and getting out for taking down/laying of cables of any description and in any position, complete all as specified and directed. |
| 2 | Returning, filling in, excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 Mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point.complete all as specified and directed |
| 4 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed. |
| 5 | Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm 4 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 6 | Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm 4 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 7 | Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 8 | Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 9 | Supply and laying in replacement XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 10 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50mm outer diameter and 38 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole & other connected accessories complete all as specified and directed. |
| 11 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 110mm outer diameter and 94 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole & other connected accessories complete all as specified and directed. |
| 12 | Removing of old paint by removers scrubing from LT poles of any size, cross arms clamps etc for painting and M &L for painting with one coat of superior quality aluminum paint on exposed surface of poles and street light bracket mounted on the poles,junction box etc and making yellow strip upto1.5 Mtr height from ground level and writing pole Nos etc. written on it with black synthetic enamel paint compete all as specified and directed. |
| 13 | M & L for Calliberation of APFC Relay fixed in existing panel complete all as specified and directed. |
| 14 | M&L in replacement Copper strip 32 x 6mm for connection of cable to the studs of transformer HV/LV, complete all as specified and directed |
| 15 | Supply and fix in replacement including testing and commissioning of 50 A / 415 volts, 3 phase AHF Panel (Active Harmonic Filter and Automatic Load Balancer) as per IEEE 519-2014, Power factor compensation 100% (Lead / Lag), Load Balancing : Negative Sequence Compensation (Zero Sequence compensation in 4 P / 4 W range), Reaction time: <0.3 ms, Interface (Communication) GSM, MODBUS RTU, USB, Ethernet, Profibus Compatible, IP-65, air cooling, overheating protection including necesary excavation and foundation work, complete all as specified and directed. |
| 16 | Supply and fix in repair Concrete RCC Route Marker of size (Length 0.60 mtr, Width (Bottom) - 300 mm), width top 20 cm, Thicknes 10 cm) with M-20 concrete with 8 mm MS reinforcement is used. LT Cable engraving will be made on the marker. Top 300 mm should be in yellow and bottom should be in black paint. The engraving will be visible on one side only complete all as specified and directed. |
| 17 | M&L for writing/PVC Venyle stickers pole Nos on street light poles with background yellow and Nos in black on yellow oval shaped compete all as specified and directed. |
| 18 | Supply in replacement post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 19 | Supply and fix in replacement of Tiranga Led Rope Light Indian Tricolor Strip Light (Orange + White + Green) Colour in Single Strip | Independence Day/Republic Day Rope Light for complete 9 meter pole (SP-31), Plug and Play Waterproof IP65 Strip Light Post Light Outdoor Lamp (Multicolor), Complete with driver and all fixing arrangements, complete all as specified and directed |
| 20 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 4 sqmm 2 core , served with inner sheathing of PVC tape and overall PVC sheathed in service connections, complete all as specified and as directed |
| 21 | Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, 10 sqmm 2 core , served with inner sheathing of PVC tape and overall PVC sheathed in service connections, complete all as specified and as directed |
| 22 | M&L for drilling suitable dia horizontal bore holes for insertion/ laying of upto 110mm bore HDPE pipe of any description below/under existing road surfaces etc with using mechanical and / or manual devices as required at site including making good the disturbed surfaces to match with the existing strata after laying pipes complete all as specified and directed. Note :Equipment, tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor without any extra cost to the Govt. Please Enable Macros to View BoQ information |
| 23 | M&L for drilling suitable dia horizontal bore holes for insertion/ laying of upto 110mm bore HDPE pipe of any description below/under existing road surfaces etc with using mechanical and / or manual devices as required at site including making good the disturbed surfaces to match with the existing strata after laying pipes complete all as specified and directed. Note :Equipment, tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor without any extra cost to the Govt. Please Enable Macros to View BoQ information |