| 1 | Supply, laying, connecting & testing HT Aluminium cable XLPE insulated screened pre bedded galvanized steel strip armoured electric power cable with stranded aluminium conductor 11 KV grade of size 3 Core 95 Sqmm complete all as specified and directed. |
| 2 | Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, laying of cables/pipes/poles etc., and getting out in hard/densesoil complete all as specified and directed. |
| 3 | Ditto item no 2 above but Exc 1.50 but n.exc 3.0m deep complete all as specified and directed. |
| 4 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding of 25 cm thick in soft/loose soil complete all as specified and directed |
| 5 | Removal of surplus soil as obtained from excavation to a distance not exc. 50 Mtr and depositing where directed at a level not exc. 1.5 Mtr above the starting point complete all as specified and directed. |
| 6 | Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable including spreading levelling watering and consolidation complete all as specified and directed. Note:-Punned thickness only shall be measured and paid separately |
| 7 | Supply and laying class HV, Type 1, flat, size 300mm x 180mm x 40 mm unreinforced precast cable cover as the mechanical protection to cable laid in trenches flat complete all as specified and directed by Engineer-in-charge. |
| 8 | Supply and laying Class LV, Type I, flat, size 250 mm x 150mm x 40mm unreinforced precast cable cover as the mechanical protection to cable laid in trenches flat complete all as specified and directed by Engineer-in-charge. |
| 9 | S&F in HT cable route indicator made of RCC M15 (Nominal Mix) using 12.5mm nominal size crushed stone aggregate of size 200 mm(Length) x 200mm (Width) x 1200mm (Height) duly painted with cement base and written in white colour with lettering MES HT cable/HT Straight joint using two coats of synthetic enamel paint in black colour and including neccesary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20 nominal graded crushed stone aggregate of size 400mm x 400mm x 300mm complete all as specified and directed. |
| 10 | S & F gang operated air break switch with DO fuse assembly, three poles, outdoor type, nominal system voltage 11 KV, rated voltage 12 KV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 KV (rms) (ii) across the isolating distance 32 KV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 KV (Peak) (ii) across the isolating distance 85 KV (Peak), Rated short-time withstand current 25 KA for 3 seconds, rated peak withstand current 63 KA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed. |
| 11 | M&L for earthing continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of 25x4mm galvanised iron strip complete all as specified and directed. |
| 12 | Supply and fix cable jointing kit for 11 KV grade cable for straight through outdoor termination,heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured , Al Conductor cable of size 50 sqmm to 95 sqmm .all as per manufacturer’s recommendations complete all as specified and directed. |
| 13 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured , Al Conductor cable of size 70 to 120 Sqmm .all as per manufacturer’s recommendations complete all as specified and directed. |
| 14 | M&L for earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick, burried directly in ground,earth pit not less than 2.25 meter deep below ground level with top edge of earth plate not less than 1.5 meter below ground level, steel earth plate connected with 32x6 mm GI strip by means of bolts, nuts, check nuts and washer of galvanised iron or steel as shown in electrical plate No. 3 connected to earth test point all as described in MES schedule part II including excavation earth work concreate pit with 50 mm thick RCC cover in RCC 1:2:4 type B-I duly reinforced with MS bars 6 mm dia @ 150 C/C both ways and pit chamber in PCC 1:2:4 type B-I with 2 Nos suitable lifting handles of 12 mm MS bar and GI protection pipe of suitable size,and watering pipe 20 mm dia with water funnel test point and extra length up to 7.5 meter connected to Panel board all as specified and directed. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 15 | M&L for earthing complete with galvanised steel earth plate electrode 600X600X6 mm thick, buried directly in ground,earth pit not less than 2.25 meter deep below ground level with top edge of earth plate not less than 1.5 meter below ground level, steel earth plate connected with 25x4 mm GI strip by means of bolts, nuts, check nuts and washer of galvanised iron or steel as shown in electrical plate No. 3 connected to earth test point all as described in MES schedule part II including excavation earth work concreate pit with 50 mm thick RCC cover in RCC 1:2:4 type B-I duly reinforced with MS bars 6 mm dia @ 150 C/C both ways and pit chamber in PCC 1:2:4 type B-I with 2 Nos suitable lifting handles of 12 mm MS bar and GI protection pipe of suitable size,and watering pipe 20 mm dia with water funnel test point and extra length up to 7.5 meter connected to Panel board all as specified and directed. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 16 | S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour with voltage 33000V/11000V as indicated and fixed with M.S. clamps, bolts and nuts of approved size, for HT size 25x20 cm all as specified and directed. |
| 17 | Supplying, fixing, installing, commissioning and testing transformer step down, 11/0.433KV, copper wound, outdoor type, 3 phase, of capacity 160 KVA, level 3, 4 wire, 50 cycles per second, oil immersed, naturally cooled connected with delta on HT side and star on LT side, LT side to vary secondary voltage + 7.5% in three steps of 2.5% each with standard fittings/fixtures. Bushing at HT/LT side with neutral brought out complete with first fill of transformer oil to appropriate level, temp gauge, breather tank cooling coil, HT/LT side cable to be fitted with suitable size of thimble/lugs complete all as specified and as directed by Engineer-in-Charge.(Including Outdoor Type Pole Mounted) |
| 18 | M&L for steel tubular swaged pole 410 SP-55(11.0 meter long) including CI base plate, final taper plug, bolts , nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30cm upto 1.5m from ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion including making good to match existing area complete all as specified and as directed. |
| 19 | Supply and fixing cross arms, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed inclusive of one primer coat, one under coat and one finishing coat of paint. |
| 20 | S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT size 25x20 cm all as specified and directed by Engr-in-Charge. |
| 21 | Supply and fixing pin type porcelain vitreous white or brown or green insulators of size 150 mm height and 150 mm dia for 11 KV grade and on galvanised mild steel spindle, two GI washers and one No GI nut complete conforming to the latest IS all as specified. |
| 22 | Supply and fixing disc type porcelain vitreous white or brown or green insulators of size 145 mm height and 255 mm dia for 11 KV grade and on galvanised mild steel spindle, two GI washers and one No GI nut complete conforming to the latest IS all as specified. |
| 23 | M&L Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed by Engr-in-Charge. |
| 24 | S&F lightening arrestor expulsion type complete with fittings, transmission class discharge capacity 65 KA suitable for 11000 Volts all as approved by GE . |
| 25 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) in foundation of PCC poles/struts as specified including necessary form work, complete all as specified & directed. |
| 26 | M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundation of stay assembly etc including necessary form work, complete all as specified & directed. |
| 27 | M&L for plain cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) for coping around poles, including necessary form work finishing even and smooth without using extra cement, complete all as specified & directed. |
| 28 | Supply laying &testing Cable XLPE insulated Screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy Duty) With stranded aluminium conductor, 1100 volts grade of size 95 Sqmm 3.5 core. |
| 29 | Supply laying &testing Cable XLPE insulated Screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy Duty) With stranded aluminium conductor, 1100 volts grade of size 35 Sqmm 3.5 core. |
| 30 | Supply & Fixing steel tubing GI light grade 100 mm dia for cable protection passing under Road/Floor or for fixing on walls complete all as specified and directed. |
| 31 | M & L for carrying out boring under the black top road for crossing of LT cable/protection pipe by any means boring machine or otherwise without damaging black top surface of road for fixing of GI pipe 100/80mm bore under the road complete all as specified and directed. |
| 32 | M&L for supply, install, connecting and commissioning of CPRI approved main LT distribution panel board ( main) , outdoor type, both side openable including locking arrangement with sliding door bolt , cubical type, 3 phase, 4 wire, 415 V, factory made free standing, floor mounting, dust and vermin proof, cubical type, fabricated from 3.15 mm thick MS sheet with anticorrosive coating and finally epoxy polyester powder coating of flint grey shade fully compartmentalised design with 4 Nos insulated bus bar each made of high conductivity aluminium suitable for 400 Amps, prewired with suitable size of copper cable/insulated copper strip including PCC work and Iron work for fixing arrangement at site suitable earth strips conforming to IS, cable glands, lugs etc. suitable for and comprising of the following.(a) Copper bus bar capacity 400 Amp-04 Nos(b) MCCB Incoming four pole with thermal magnetic release adjustable type with breaking capacity 36 KA, 320 Amp - 01 No(b) MCCB Outgoing four pole with thermal magnetic release adjustable type with breaking capacity 25 KA, 100 Amp - 04 No(c) Digital Voltmeter-96 x 96 mm flush secure Panel mounting type 0-500V with selector switch - 01 No(d) Digital Amp meter 96 mm X 96 mm flush secure Panel mounting type 0-100 Amps with selector switch with CT - 01 No(e) RYB neon indicating lamp set of three- 01Notes:(i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 50mmx50mmx6mm and 60 cm in height for fixing the panel(ii) Make of MCCB:-Legrand, Schneider, Siemens, L&T or equivalent(iii) Danger notice plate (02 Nos) in Hindi and English of size 20cmx 15cm shall be fixed on the panel. Please Enable Macros to View BoQ information |