| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CWE WELLINGTON NAME OF WORK: PROVN OF OF ELECTRICAL INFRA AND ENHANCEMENT OF HT POWER SUPPLY FOR ELETRIC VEH CHARGING AT DSSC WELINGTON Contract No: CWE/ WEL/ OF 2025-26 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevant columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Item of Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Conversion against each Item Quoted Currency in INR / Other Currency Rate in Figures to be entered by the Bidder including all Taxes etc.Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category Total amount TOTAL AMOUNT With Taxes Total amount in words |
| 2 | Supply, Installation, testing and commissioning of transformer. platform/plinth mounted of capacity 315 KVA step down, 5 star Energy Efficiency, outdoor type, 11.0/0.433 KV, 50 Hz, AC double wound copper type, copper wound, oil immersed type, naturally air cooled with external cooling tubes, transformer delta connection on HT side and star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage (+/-) 7.5% in equal steps of 2.5% as per IS-1180 (Part-1)-2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :-(a) O1 No cable end box on HT side consisting of 03 Nos porcelain bushing with bushing rods, nuts, washers with cable gland of suitable size for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete(b) 01 No cable box on LT side consisting of 03 Nos porcelain bushing with bushing rods, nuts, washers with cable gland of suitable size for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete.(c) Oil conservator tank with filler type drain valve and oil level guage(d) Explosion vent with double diaphragm and sight glass(e) Thermometer pocket.(f) Two earthing terminal on tank body to facilitate fixing of 32 6mm Gl strip etc(g) 01 No thermometer dial type, vapour pressure type having range 0 to 120°C with maximum temperature indicator, re setting device and marked maximum temp reading point. |
| 3 | (h) Rating plate with terminal marking plate(1) Oil level gauge(k) Oil drain filter valve.(1) Oil filling port on top cover with plug.(m) Air release valve/plug(n) 02 Nos plain solid cast steel detachable rollers(0) First fill of transformer oil confirming to relevant 15 & tested upto 60 KV dielectric strength(p) Inspection cover.(a) Lifting lugs & jack lifting pad & support(r) Silica gel breather without / with connecting pipes, first fill of dehydrating agent(s) Cover lifting eyes.(t) Oil temperature indicator of approved range, incl shut off valve between conservator & main tank(u) Additional/Extra bushing for neutral outside of LV side(NOTE: (i) Design/drawing/BOM of the Transformer showing the dimensions is to be obtained from OEM / Auth Supplier and the same has to be got approved from the GE & Engr-in Charge before placing final order to the manufacturer(ii) Quoted rate is deemed to be inclusive of Factory Inspection/Testing of the Transformer before dispatch by an E/M Officer nominated by the Accepting Officer.(iii) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates) |
| 4 | Supply and fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 metres long) complete with CI base including necessary painting complete all as specified and directed. |
| 5 | M & L for Cross arms bracing supports clamps and back plates fabricated from structural steel sections including nut bolt washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and including one primer coat of red oxide zinc chrome primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed. |
| 6 | M & L for pin type porcelain vitreous white/brown insulator including one galvanised mild steel spindle two galvanised iron nut 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed. |
| 7 | S & F Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suiotable for upto 11 kV outdoor/ indoor type incl;uding necessary connections and fittin gs all as per IS-3070 Part-III and IEC 1994 complete all as specified and directed. |
| 8 | S & F Triple pole, mechanically operated (GOD), outdoor type, triple pole, HT 11 kV, 400 Amps, vertical type with 9 insulators mounted with fixed contacts of phosphor bronze and moving contacts of copper, manually operated from ground level with operating mechanism including mild steel galvanised medium grade 25mm bore single length operating rod, pad locking arrangementg including making necessary jumper connections with and including PVC flexible connection pipes duly wrapped colour insulation tapes etc complete all as specified and directed. |
| 9 | S & F swing out expulsion fuse single pole (Drop out fuse) with fuse carrier, fuse element mounted on insulator and fitted on steel frame etc for 11000 Volts of capacity 25 Amps complete all as specified and directed. |
| 10 | M & L for Anti climbing devices; comprising 2.24mm dia galvanised steel 2- strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre including clamped and properly secured or as ordered complete all as specified and directed. |
| 11 | Supply, install, testing & commissioning of Main LT control panel board \\"out-door type\\" of size 1200 mm (height) x 1500 mm (breadth) x 500 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & High grade copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation, necessary earthwork (if any) & incl the following accessories complete all as specified & as directed(a) Tinned Copper Bus-bars 04 Nos of rating 630 A, duly insulated with 1100 V grade standard colour coded PVC sleeves(b) Digital type Multi-Function meter with built in selector Switch with CTs of -/5A(c) R,Y,B LED Indicator lamp - 01 Set.(d) Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size -02 Nos |
| 12 | INCOMING:(a) 4 Pole MCCB 550 Amps, 50 Hz, 415 V with rupturing capacity 36 KA -01 No OUTGOINGS:(a) Supply and fix Four Pole MCCB 125 A, 50 Hz, 415 V with rupturing capacity 25 KA-04 Nos(Notes for Item Nos 1 and 2 :-1) Design / drawing / BOM of the Panel Board showing the dimensions is to be obtained from the Manufacturer / Supplier & same shall be got approved from the Engr-In-Charge & GE before placing final order to the manufacturer. 2) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.) |
| 13 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 11000 volts grade with stranded aluminium conductor of size 95 Sqmm 3 core complete all as specified and directed. (Note: Excvation and earth work shall be measured and paid seperately) |
| 14 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 core complete all as specified and directed. (Note: Excvation and earth work shall be measured and paid seperately) |
| 15 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed. (Note: Excvation and earth work shall be measured and paid seperately) |
| 16 | Excavation in trenches, not exceeding 1.5 M wide and not exceeding 1.5 M depth for foundation, trenches for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out in hard/dense soil complete all as specified and as directed. |
| 17 | Excavating in trenches not exc. 1.5 metre wide and exc. 1.5 metre & not exc. 3 metre depth (beyond the first 1.5 metre) for foundation of poles etc and getting out in hard/dense soil complete all as specified and directed. |
| 18 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm as in hard/dense soil complete all as specified and directed. |
| 19 | Removing excavated soil not exc. 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed. |
| 20 | M & L for Sand cushioning with clean dry sand in trenches for protection of under ground cables (below, above and around the cable laid in trenches) complete all as specified and directed.(Note: Thickness after punning down shall be measured for payment) |
| 21 | Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1 flat, size 300mm x 180mm x 40mm complete all as specified and directed. |
| 22 | Supply and laying well burnt sub class 'B' bricks, old size laid breath wise across the length of cable in trenches for protection of UG cables complete all as specified and directed. |
| 23 | M & L for cutting existing roads/ hard standing/ path etc for laying LT cables through pipes of any size n.exc 60cm depth and 30cm width and making good the damaged surfaces complete as per the existing specifications of roads/ hardstanding/ path etc to match with the existing surfaces complete all as specified and directed. |
| 24 | M & L for 100 mm bore, steel tubes, galvanised, light grade with all fittings, laid in trenches etc as in cable protection complete all as specified and directed. |
| 25 | M & L for 50 mm bore, steel tubes, galvanised, light grade with all fittings, laid in trenches etc as in cable protection complete all as specified and directed. |
| 26 | M & L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32x6mm by means of bolts, nuts, check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 40 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 10 cm C/C both ways and suitable handle of 12 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion complete all as specified and as directed by the Engineer-in-Charge. Total in Figures 0.0 0.0 Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |