| 1 | M&L for dismantling/taking down carefully by disconnecting of electric connection from pole/ walls of any heights and any situation/location, place street light fittings type of tube rod 36/40 watts, HPSV, HPMV, unserviceable LED street lights any wattage of flood lights, post top lanterns etc complete all as specified and directed by Engineer-in-Charge. |
| 2 | S&F energy saving LED inventer type street light 45 watt and battery back up of minimum 2 hourse environmental friendly, long life , exclusive innovative die-cast aluminium IP 66 security light with high power LEDs as light source, suitable for 40mm GI pipe, 5700K LED of connecting up with twin core twisted flexible copper conductor cable complete all as specified and directed. |
| 3 | All as per Srl item No 02 here-in-before but capacity 60 watt as directed by Engineer-in-Charge. |
| 4 | M&L for point wiring in repair for light controlled by one switch with 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH cable in existing PVC concealed conduit terminated in new anodise pressed steel sunken box having thickness not less than 2mm with 3mm thick ISI marked bakelite laminated sheet fixed with cadmium plated screws and washers for switches and sockets including 1.5 sqmm PVC insulated unsheathed multistranded copper conductor FRLSH as earth continuity conductor connected to common earth dolly including cutting chiseling for concealed boxed including insulation test of point wire and making good disturbed matching with the existing specifications including taking down of old existing point wiring any type complete all as specified and directed. Note :- Colour coding is to be maintained (Ph-Red, N- Black, Half - Yellow, Earth - Green). |
| 5 | S&F in replacement of switch piano flush type one way 5 Amps SP 240 volts complete all as specified and directed. |
| 6 | S&F in replacement of LED bulk head light fitting 1 x9/10 watt cool daylight (CDL) round type premium quality diffuser for even distribution of light complete, connecting electricaly to ceiling rose using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.75 Sqmm all as directed by Engineer-in-Charge. |
| 7 | Repair/ tightening of end terminals of street light fitting, flood light, post top lantern of any size/capacity at any height and repair the street lights, flood lights and post top lantern having minor faults i.e loose connections, carbon deposition, shifting and refixing the same etc and making the light functional all as specified and directed by Engineer-in-Charge. Note:- (a) Complaint shall be done within 24 hrs after intimation by JE E&M/ Engineer-in-Charge failling which penalty of Rs 250/- per day per complaint will be levied on contractor.(b) One supervisor will report to JE E/M, Engineer -in-Charge on daily basis with complaint register. |
| 8 | S&F LED Street light 60 Watt warm white 3000K with silicon gasket for IP 66 (no glue) protection suitable upto 50mm outer dia holder fixed on existing poles. LED street light shall be made up of pressure die cast alluminium LM 6 alloy housing with toughend glass, high power LEDs and secondary lenses with IP 66 protections top opening for separate driver compartment with frame, brand, logo embossed, toughened glass cover. High power ceramic base, CRI > 70,and bolted inside the luminaire panel. Average life class of 50000 hrs metal body fully coated phase to phase protection at 440 V upto 4 hours and > 300 V auto cut and restart feature. Luminaries and driver shall be of same make, lights are connecting up with twin core flexible copper conductor cable complete all as specified and directed. |
| 9 | All as per Srl item No 08 here-in-before but capacity 45watt all as directed by Engineer-in-Charge. |
| 10 | All as per Srl item No 08 here-in-before but capacity 30 watt all as directed by Engineer-in-Charge. |
| 11 | S&F in replacement GI pipe bracket made out of GI pipe light grade 32 mm dia and bend to shape 1.5 mtr long, including MS clamps made out of MS flat iron of size 40X4mm thick with nuts & bolts, washers complete drilling of holes for nuts and bolts etc all as specified and directed by Engineer-in-Charge. |
| 12 | S&F in replacement of unserviceable driver for LED street light of capacity 30 to 70 watt for any make and type all as specified and directed by Engineer-in-Charge. |
| 13 | S&F in repair metal core PCB/MCPCB copper and aluminium core boards of street light any make of capacity 60 watt 3000K complete all as specified and directed. |
| 14 | S&F in repair of Single phase 8 KW automatic street light control switch using Infrared Sensor based NATURE SWITCH for automatic switching of street lights. Nature switch operation based on natural light lux level. Switching off illuminance level of minimum 30 Lux and switching off illuminance greater than or equal to 10 Lux. The sensor having part night operation facility of min 4 hrs to maximum 12 hrs. The circuit shall have a provision for manual over ride operation. The sensor along with suitable power contactors and incoming outgoing MCBs be enclosed on a pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade with hensel enclosures, conforming to IP 66 complete all as directed by Engineer-in-charge. |
| 15 | All as per Srl item No 14 above but for 5 KW automatic street light. |
| 16 | S&F in replacement of MCB 5 to 32 Amp, SP 'C' series complete all as specified and directed. |
| 17 | S&F in replacement of 3 pole power contactor of rating 25 to 45 Amps as per existing make and rating all as directed by Engineer-in-Charge. |
| 18 | S&F of LED post top lantern with die cast housing cum heat sink with PMMA diffuser in IP-66 fitting of 30watt all as directed by Engineer-in-Charge. |
| 19 | S&F bollard LED light capacity 16watt all as specified and directed. |
| 20 | Supply and laying in replacement weather proof flat twin core cable aluminium conductor 1100 volts grade size 10 Sqmm including taking out old cable complete all as specified and directed. |
| 21 | S&F aluminium lugs eye type suitable for cable size 6 Sqmm to 10 Sqmm including necessary crimping with crimping tool complete all as specified and directed. |
| 22 | All as per Srl item No 21 here-in-before but of size 16 sqmm to 35 sqmm. |
| 23 | S&F in replacement LT straight through cable jointing kit heat shrinkabale complete with jointing materials suitable for LT armoured cable 2/4 core of size 35 Sqmm complete all as specified and directed. |
| 24 | S&F in replacement weather proof flat twin core cable aluminium conductor of size 2.5 sqmm 2 core all as specified and directed by Engineer-in-Charge. |
| 25 | S&F in replacement of junction box size poly corbonate with glass fibre reinforced, environment friendly, recylable, UV resistant, halogen and silicon free anti acid and anti corrosive IP 66/67 in accordance with IE rule internally embedded gasket, junction box including 3 phase 415 volt aluminium bus bar and din rail for fixing the MCB including one No MCB SP 6A 10KA to control the street light with necessary clamps, nuts bolts to fix the junction box with poles complete all as specified and directed. |
| 26 | M&L for preparation of old painted surfaces of electric pole removing complete dust and other deposited materials by cleaning from steel tubular pole of length upto 9 to 12 metres cross arms, bracing, clamps etc and painting with one coat of aluminium paint, replacement of reflective band of 3M brand RED -YELLOW -RED alternate coloured 3 numbers of minimum 5cm in height wrapped all around the pole complete all as specified and directed by Engineer in Charge. |
| 27 | S&F in repair of shackle type insulator porcelain vitrous white, brown or green insulator incl galvanised mild steel straps washers insulators bolts washers of size 75x90 mm all as specified and directed. |
| 28 | Excavation in trenches in soft loose soil including cutting road surfaces n.exc 1.5 mtr wide and n.exc. 1.5 mtr in depth for poles, stay, cable, pipe etc getting out complete all as specified and directed. |
| 29 | Returning, filling in, including spreading, leveling,watering and well ramming in layers each n.exc 25 cm thick in soft loose soil all as specified. |
| 30 | Removal of excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 31 | Supply and laying brick common burnt sub class \\"B\\" old size (compressive strength not less than 75 kg per sqcm) for protection of cable laid in trenches for under ground cable complete all as specified and directed. |
| 32 | M&L for sand cushioning in trenches using fine sand to under ground cable, laid in two layers 15cm before laying the cable & 8cm after laying the cable complete all as specified and directed. |
| 33 | Supply and laying in replacement XLPE insulated armoured (under ground) heavy duty electic cable with stranded aluminim conductor 1100 volts grade of cross sectional area 16 Sqmm 4 core laid in trenches/ ducts/ through pipes/in floor road/along the pole etc all as specified and directed by Engr-in-Charge. |
| 34 | All as per Srl item No 33 here-in-before but of size 25 sqmm 4 core. Please Enable Macros to View BoQ information |