| 1 | Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in PVC casing & capping with 5/6 Amps one way switch, piano type and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. |
| 2 | Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in PVC casing & capping, with 2-way, 5/6 amps piano type switch and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. |
| 3 | Wiring for circuit / sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in PVC casing & capping along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required. |
| 4 | 2x1.5 Sq. mm. |
| 5 | 2x4.0 Sq. mm. |
| 6 | 2x10 Sq. mm. |
| 7 | Supplying and fixing Metal box of following sizes (nominal size) on surface or in recess suiable for phenolic laminated sheet cover in the front including painting etc. as required. |
| 8 | 100mm x 100mm x 60mm deep |
| 9 | 180mm x 100mm x 60mm deep |
| 10 | Supplying and fixing metal box of 180mmx100mmx60mm deep (nominal size) on surface/recess with suitable size phenolic laminated sheet cover in the front including providing and fixing 6 pin 15/16 amps socket outlet and 15/16 amps, piano type switch, connections, painting etc. as required. |
| 11 | Supplying and fixing following rating piano-type switch/socket on the existing switch box/cover including connection etc. as required. |
| 12 | S.P. 5/6 Amps one way switch, piano type. |
| 13 | S.P. 5 pin 5/6 Amps socket outlet, porcelain base/ piano type. |
| 14 | Supplying and fixing Ding-Dong / Electronic musical bell, suitable for D.C./A.C. single phase, 230 volts complete as required: |
| 15 | Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: Exhaust Fan, Heavy Duty 300 mm sweep Size. |
| 16 | Providing and fixing of surface mounted luminaries aluminium batten tubes, white power coated CRCA Housing diffusser to avoid glaire and it should be compatible with specifications i.e. power factor ≥ 0.9, harmonic distortion ≤ 10% and efficacy ≥ 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz, including one no. tube rod 20 Watt complete with all accessories, connections, testing and commissioning etc. as required. LED Aluminium batten Tube 20Watt |
| 17 | Supplying and fixing bakelite batten/angle holder including connections etc. as required |
| 18 | Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required. Double door-12 way. |
| 19 | Supplying and erection of 16 Amp to 32 Amp rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of Single pole in the existing MCB DB complete with connections etc. as required:- Cat-A. |
| 20 | Supplying and Fixing following rating, double pole 240 volts isolator in the existing MCB DB with connections testing and commissioning as required. 63 Amps Cat. 'A' |
| 21 | Earthing with G.I. earth plate 600 mmx600 mmx 6 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (But without charcoal/ coke and salt ) as required. |
| 22 | Extra for using salt and coke for G.I. or copper plate earth electrode complete as required. |
| 23 | Supplying and laying 6 SWG G.I. wire at 0.50 mtr. below ground level for earth electrode conductor, including soldering etc. as required. Please Enable Macros to View BoQ information |