| 1 | SH - I (Maintenance of EI and Fans & Fittings)Day to day maintenance, operation and general up keep of all internal electrical installation such as wiring, switches, MCB's, DB's, fittings and fixtures, main boards, street/ compound lighting & recording and monitoring of the complaints round the clock on all working days including Sundays and Holidays complete in following locations as per terms and conditions and inventory of staff and duty time attached. Total staff required. (a) Skilled (Wireman)-3 Nos. (b) Unskilled (Khallasi)-1 Nos. |
| 2 | SH-II (Operation OF DG SET & SUB STATION AND WATER SUPPLY PUMPSET)Operation & routine maintenance of HT panel substation having 500 KVA, 2 nos.transformers as mentioned in inventory attached including HT panel, LT panel, Capacitor panel and stand by DG set of 125 KVA as mentioned in inventory attached including AMF panel round the clock on all days of the month i/c Sundays & Holidays in following locations.The jobs includes recording of all parameters like HT & LT voltages, current, power factor etc. and routine periodically checking and testing as per terms and conditions and inventory of staff and duty time attached. Total staff required. a) Wireman cum Operator -3 Nos. (Round the clock) b) Khallasi- 1 nos. |
| 3 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 1.5 sq. mm |
| 4 | b) 3 x 4 sq. mm |
| 5 | c) 3 x 6 sq. mm |
| 6 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 amps switch |
| 7 | b) 15/16 A switch |
| 8 | c) 3 pin 5/6 A socket outlet |
| 9 | d) 6 pin 15/16 A socket outlet |
| 10 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.a) 1 or 2 Module (75mmX75mm) |
| 11 | b) 3 Module (100mmX75mm) |
| 12 | c) 6 Module (200mmX75mm) |
| 13 | d) 8 Module (125mmX125mm) |
| 14 | e) 12 Module (200mmX150mm) |
| 15 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. a) 1 or 2 Module |
| 16 | b) 3 Module |
| 17 | c) 6 Module |
| 18 | d) 8 Module |
| 19 | e) 12 Module |
| 20 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 21 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm |
| 22 | b) 25 mm |
| 23 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 24 | b) Double pole |
| 25 | c) Triple pole and neutral |
| 26 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)a) 8 way (4 + 24), Double door |
| 27 | S/I/T/C of 1200 mm sweep BEE 3 and above star rating energy efficient ISI marked ceiling fan capacitor type with double ball bearing suitable for operation of single phase AC supply with power Consumption of Max. 50W capable to deliver 220 CFM (min.), speed of 350 rpm (min.) i/c wiring the down rod of standard length (upto 30 cm) with 1.5 Sqmm FR PVC insulated copper conductor single core cable etc as reqd. |
| 28 | S.I.T.C of 380 mm Sweep 1400 RPM Heavy Duty ISI Marked Exhaust fan i/c supply and fixing of gravity louvers & shutters in the existing opening, including making good the damage, connection, testing, commissioning etc. as reqd. |
| 29 | Supplying, installation, testing and commissioning of oscillating type 400 mm sweep Hi-speed cabin fan/wall bracket fan with mounting based closed mesh guarded blades and speed regulator and two nos. strings for operation of regulator & swing action suitable for use on 230V 50Hz single phase supply complete as required. |
| 30 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)a) 18- 22 Watt |
| 31 | Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/ 4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim .a) 12 -15 watt |
| 32 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft. suitable for surface and recess of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) a) 36 watt |
| 33 | Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). a) 100 watt Please Enable Macros to View BoQ information |