| 1 | Dismantling of all damaged switchgears, capacitors, measurement instrument, indicating lights, relay and removing of complete wiring and connection at site and cleaning of P.F.C. Panel by CRC. Fixing of below mention switchgears in both panels as required i.e. contactor, capacitors ,banking of capacitors as required in system and all measurement components, indicating lights, MCCB in their respective space in existing panels duly wired, tapping, thumbling, ferruling and connection with main bus bar both in outgoing incoming part with all required hard wares |
| 2 | Supply of under/over voltage release as per site requirement. Make : L&T/C&S/Schneider/DJB Approved Make |
| 3 | Supply of shunt release as per site requirement. Make : L&T/C&S/Schneider/DJB Approved Make |
| 4 | Supply of Indicating Lamps (Red/Yellow/Blue/Green) as per site requirement. Make : L&T / Havells / Vaishno / BCH / DJB Approved |
| 5 | Supply of Digital Volt meter 3 phase 0-500 V. Make : L&T / AE / Sigma / C&S/ DJB Approved |
| 6 | Supply of AMP Meter Digital 3 phase, 0-800 Amp. Make : L&T / AE / Sigma / C&S / DJB Approved |
| 7 | Fixing the above equipments including fixing of under voltage release, volt meter selector switch, Amp meter selector switch, indicating lamps, digital volt meter, digital ammeter at their proper place in the LT panel with proper connections and fixtures as per site requirement. |
| 8 | Supply of Fixed arching contact for2500 Amp ACB’s as per site requirement. Make : L&T/C&S/Schneider/DJB approved make |
| 9 | Supply of Moving arching contact for 2500 ACB’s as per site requirement. Make : L&T/C&S/Schneider/DJB approved make |
| 10 | Supply of 2500 A Pole assembly as per site requirement. Make : L&T/C&S/Schneider/DJB approved make |
| 11 | Supply of 2500 Jaw contacts as per site requirement. Make : L&T/C&S/Schneider/DJB approved make |
| 12 | Supply of 2500 A Cradle terminal as per site requirement. Make : L&T/C&S/Schneider/DJB approved make |
| 13 | Replacing and fixing the above equipments including fixing of arching and moving contacts, shunt release, 2500 A pole assembly, jaw contacts and cradle terminal in 2500A ACB and 630 A ACB respectively with proper connections and fixtures as per panel requirements. |
| 14 | cleaning oiling tightening of 2500A-3P/MDO including Cleaning of dust, spider web, foreign particles etc., removal of grease from the various parts of ACB, Cleaning of all parts with cleaning agents such as CRC-2-26, Check the setting of arching contacts, releases etc, Check the tightness of all hardware and also presence of hardware, Fixing of spares /accessories which needs replacement. Re-greasing as recommended in ACB service manual. All the required hardware/item will be arranged by the firm itself. |
| 15 | Cleaning, oiling, tightening of 630-4P/MDO including Cleaning of dust, spider web, foreign particles etc., removal of grease from the various parts of ACB, Cleaning of all parts with cleaning agents such as CRC-2-26, Check the setting of arching contacts, releases etc, Check the tightness of all hardware and also presence of hardware, Fixing of spares /accessories which needs replacement. Re-greasing as recommended in ACB service manual. All the required hardware/item will be arranged by the firm itself. |
| 16 | Cleaning & servicing of LT panel, tightening of Bus bar / hardware support and servicing of other accessories as per requirement. |
| 17 | Testing & commissioning of the LT panel and installed equipments, setting of relay ,as per required parameters with relevant IS .testing of the panel prior to switching on as follow i)Continuity and earth testing ii)isolator mechanism and alignments iii) Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. iv) Checking for all tightness of nut and bolts v) Alignments of doors etc. vi) Interlocking tests. vii) All functional tests. |
| 18 | Dismantling of old and faulty panel including removing of all electric connections while taking all safety precautions and cutting of old rusted nuts and MS bar with help of electric cutter/ manual labour including making the surface even with minor civil work for new panel as per site requirement. |
| 19 | S/o Moulded Case Circuit Breaker (MCCB) of rating 400 Amp, Four Pole, 415 V, AC of breaking capacity of 36 kA or more with Spreader Link. Make: Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 20 | S/o Moulded Case Circuit Breaker (MCCB) of rating 63 Amp, Triple Pole, 415 V, AC of breaking capacity of 36 kA or more with Spreader Link. Make: Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 21 | S/o TP Air Break Contactor 40 Amps Coil Voltage 220 V Make Make: - Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 22 | S/o TP Air Break Contactor 32 Amps Coil Voltage 220 V Make Make: - Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 23 | S/o of front mounting NO/NC aux. add on contact block 2NO+2NC. Make: - Havell's/Selec/L&T/Schneider/C&S/HPL/DJB approved make |
| 24 | Star Delta Timer 0-30 Sec,220 V Voltage Make: -Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 25 | Microprocessor based Motor Protection Device having following protection Over Voltage/Under voltage/Single phase /Phase reversal/over current/under current Protection/earth fault as per site requirement range 8-22 A. Make:- Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 26 | TP thermal overload Relay Range 9-15 A Make: - Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 27 | S/o PVC insulated copper flat submersible cable three core 4 sqmm. Make: Havells / Gloster / ICC / ICL/ CCI |
| 28 | S/o PVC insulated flexible copper cable single core 16 sqmm. Make: Havells / Gloster / ICC / ICL/ CCI |
| 29 | S/o aluminium armoured 3.5 core 50 sqmm cable with aluminium conductor. Make: Havells / Gloster / ICC / ICL/ CCI |
| 30 | Supply of AMP Meter Digital 3 phase, 0-800 Amp. Make : L&T / AE / Sigma / C&S / DJB Approved |
| 31 | Supply of Digital Volt meter 3 phase 0-500 V. Make : L&T / AE / Sigma / C&S/ DJB Approved |
| 32 | SP MCB. 6A. MakeHavells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 33 | On/Off Push Button as per site requirement Make: - Warner/ Selec/ DJB approved make |
| 34 | S/o Indicating Lamp, Led type as per site requirement Make: - Havells/Selec/ L&T/ Schneider/ C&S/ HPL |
| 35 | Packing and transportation charges of the filling point panel. This includes shifting of the complete panel from workshop to site and transportation and loading unloading cost done with the help of crane and manual labour. |
| 36 | Installation of the new L.T. Panel at site including providing of the all material required for fixing the panel including grouting and minor civil work as per satisfaction of engineer in charge. |
| 37 | Testing & commissioning of the new starter panels including testing for their operations for the pumps as after making required configurations in the starters. Testing of Starters at No Load and then at on Load. Testing of tripping system of starters as per requirement Please Enable Macros to View BoQ information |