| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, with mdular type switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, 2 way piano type switch, phenolic laminated sheet, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class pvc conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class pvc conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire |
| 8 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire |
| 9 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2 x 16 sq.mm. + 1 x 6 sq.mm. Earth wire |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire |
| 11 | Supplying and fixing metal box of 150 mm X 75 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 12 | Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 13 | Supplying and fixing 20 amps, 240 volts, SPN, industrial type socket outlet, with 2 poles and earth metal enclosed plug top along with 20 amps. \\"C\\" curve, SP MCB in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet, and complete with connections, testing and commissioning etc. as required. |
| 14 | Supply and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 15 | Supply and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 16 | Supply and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required : 20 mm. |
| 17 | Supply and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required : 25 mm. |
| 18 | 3Supply and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required : 2 mm. |
| 19 | Supplying and fixing 5 amps. to 32 amps. rating, 240 volts `C' series, miniature circuit breaker (MCB)suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. single pole |
| 20 | Supplying & fixing single pole, blanking plate in the existing MCB DB complete etc. as required. |
| 21 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. 40 Amps |
| 22 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. 63 Amps |
| 23 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. 63 amps. |
| 24 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps. |
| 25 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps. |
| 26 | Supplying and fixing following rating, four pole, (three phase & neutral) 415 volts, residual current circuit breaker (RCCB), having a sensivity current upto 300 miliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required : 63 amps. |
| 27 | Supplying and fixing following way, SP&N, sheet steel, MCB distribution board, 240 V on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator) 6 way, Double door |
| 28 | Supplying and fixing following way, horizontal type TP&N, sheet steel MCB distribution board, 415 V on surface /recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators). 4 way (4 + 12), Double door |
| 29 | Earthing with GI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc, with charcoal/ coke and salt as required. |
| 30 | Supplying and laying 25 mm x 5 mm. G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 31 | Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 32 | Providing and fixing 25mm x 5 mm G.I strip on surface or in recess for connections etc. as required. |
| 33 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 34 | Providing and fixing M.V. danger notice plate of 200mmx150mm made of mild steel, atleast 2mm thick and vitreous enamelled white on both sides and with inscription single red colour on FRLSont side as required. |
| 35 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 36 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 2 run of cable |
| 37 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections butexcluding modular plate etc. as required. 5/6 A switch |
| 38 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections butexcluding modular plate etc. as required. 3 pin 5/6 A socket outlet |
| 39 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75mmX75mm) |
| 40 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 41 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 42 | Supplying and fixing Internet Socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 43 | Installation, testing and commissioning of pre-wired, flourescent fitting / compact fluorescent fitting of all types, complete with all accessories and tubes etc. directly on ceiling / wall, including connection with 1.5 sq. mm. FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 44 | Installation, testing and commissioning of ceiling fan including wiring the down rod of standard length (upto 30 cm.) with 1.5 sq. mm. FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 45 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required Upto 450 mm sweep |
| 46 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 47 | Supply of 36 Watt to 46 Watt indoor Recess mounting LED Square Fitting for Armstrong Ceiling having Powder coated die cast aluminium housing body with extended heat sink and diffuser of Special Polycarbonate meterial and driver set complete in all respect. |
| 48 | Supply of LED Tube Light with Metal heavy duty Box type batten Light fitting 1X22 watt suitable for upto 1X22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect. |
| 49 | Supply of LED Tube Light with Metal heavy duty Box type batten Light fitting 2X22 watt suitable for upto 2X22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect. |
| 50 | Supply of recess/surface mounting round 10 W to 15 W LED Cut out Min 125 mm, Height Min. 40mm, LED Down lighiter having powder coated die cast aluminium housing with heat shink,diffuser/reflector and driver set. suitable for 24Hr Continuous Operation, Complete in all respect. |
| 51 | Supply of 225/230mm sweep ventilating (Light Duty) exhaust fan complete with Metallic Blade (Steel bird guard protector /Copper motor for high air suction performance /Capacitor etc.), Noise level : (45 - 50) dB, Power consumption : 45 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Motor type : Normal Speed. Complete in all respect. 230 mm sweep |
| 52 | Providing & fixng of wall fan Complete in all respect. |
| 53 | The panel shall be manufactured in conformance to requirements of local Supply, installation, testing and commissioning of electrical panel, modular type, front accessible only, free floor standing confirming to Minimum IP:43 degree of protection. The panel sheet structure shall undergo seven tank pre-treatment process before painting. The sheet steel shall be all of 2.2mm thick CRCA sheet. All the openable compartments of the panel shall be completely shrouded and provided with padlocking arrangement on all compartments including bus bar and cable alley chambers. The panel height shall not exceed 2200mm and the maximum operating height for any switchgear shall not be more than 1700mm. The panel shall be provided with minimum 75mm base channel frame fabricated from ISMC sections. All bus bar links in the panel shall be solid bus bars with coloured PVC shrinkable sleeves, no wires will be acceptable. Continuous earth bus shall run alround the panel with earthing studs provided at minimum 2 places. The control wiring shall be carried out with minimum 1.5/2.5 sqmm copper wires and adequate number of NO/NC, potential free contacts incorporated for remote operation of the starters. Proper sized cable termination gland plates shall be provided on cable alleys and knockouts for same shall be provided during fabrication stage itself. The panel shall be provided with a thermostatically controlled heating arrangement (200 W) to take care of high humidity conditions. A 5A socket service outlet (single phase) shall be provided in one of the compartments as ervice outlet in the panel. Panel shall be so designed at to have minimum 20% spare feeders/space. Panel shall undergo epoxy powder coated paint, colour as per IS:5 requirement. All cable terminations shall be from top. The complete panel shall be fuse less type, for control circuits 2A/6A MCB's to be used. All bus bars shall be of aluminium, electrolytic grade only. Maximum design density shall not exceed 1 Amps/Sqmm. All bus bars shall be insulated with coloured heat shrinkable PVC sleeved. All bus bar supports shall be non hygroscopic DMC/SMC supports. electrical inspector and it shall be contractors responsibility to get initial approval of drawings and also final approval of complete electrical works related to this section.The minimum clearances between bus bars shall be as follows :Phase to phase -Phase to neutral-minimum 15mm, minimum 20mm ,Main L.T. Panel :Incoming : One (1) No300Amp. 4 pole MCCB,Metering :One (1) No. (0-500V) 96 x 96 Sqmm voltmeter with control fuse & selector switch.One (1) No. (0-300A) 96 x 96 Sqmm CT operated Ammeter with selector switch, CTs etc.,One (1) Set of Phase Indication Lamp.Bus Bar :One (1) No. 300 A, TPN aluminimum bus bar of suitable length. Outgoing : Phase indication lamps on each outgoing to be provided. 63 Amps TPN MCB - 3No., 40 Amps TPN MCB -3No. 32 Amps TPN MCB - 2 No. 63 Amps TPN MCB - 1No. Spare 40 Amps TPN MCB - 1No. Spare |
| 54 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.16 sq. mm 4 core(MR) |
| 55 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 35 sq. mm 3-1/2 core(MR) |
| 56 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 16 sq. mm 4 core |
| 57 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 3½ X 35 sq. mm (35mm) |
| 58 | Supply and fixing of C02 type fire extinguisher 6.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.(MR) |
| 59 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.(MR) |
| 60 | Supply & fixing steel tabular pole 9meter long desgonged 410 SP 30 in 1:3:6 cement concrete foundation including excavation back filling etc complete in all respect. |
| 61 | Supply and fixing of LED street light fitting with mandatory driver set having die cast aluminium body and lenses suitable for 60 watt to 72 watt confirming to IP 65/66 protection complete in all respect |
| 62 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. 16 sq. mm 4 core |
| 63 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect.35 sq. mm 3-1/2 core |
| 64 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect .40 A TPN |
| 65 | Supply and burring of Safe Earthing Electrode T-39 (Hot Dip Galvanized), Length up to 3000mm, outer pipe 76mm inner Dia 38mm terminal Dia 12 mm ,outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonary housing. (From electrode terminal to switch board, cost of 25 X 3 GI. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
| 66 | Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect. |
| 67 | Supplying and fixing of 16mtr high mast shaft of apporved make with rising system hot dip glavanized inside & out side dip, heaving pole sheet thickness 3mm. Top dia minium 150mm bottom dia 360mm base plate 32mm thick suitable for wind velocity as pe IS 875 part 3& having no circumferential weld with accesories for high mast suh as head frame suitable for 6 to 12 luminaries & its control gear boxes 1.5HP power tool moter 3point suspension system with steel wire rope 6 mm dia double drum winch including making suitable foundation as per manufacture drawing/ site reiment along ith foundation bolt nuts wahers anchors plates etc complee in all respect. |
| 68 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 170 to 200 Watt. Confirming to IP 66 protection complete in all respect. |
| 69 | upply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect.16 sq. mm 4 core |
| 70 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect.35 sq. mm 3-1/2 core |
| 71 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect .40 A TPN |
| 72 | Supply and burring of Safe Earthing Electrode T-39 (Hot Dip Galvanized), Length up to 3000mm, outer pipe 76mm inner Dia 38mm terminal Dia 12 mm ,outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonary housing. (From electrode terminal to switch board, cost of 25 X 3 GI. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
| 73 | upply and fixing of twin unit aviation obstruction light (GEC-ZH 752) / Bajaj BJAOL-2 with red glass, B.C. holders etc. complete in all respect, at the top of the building complete in all respect |
| 74 | upply and fixing of brass nickel plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer Incharge. 35 sq. mm 3-1/2 core |
| 75 | Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect.(f) 35 sq.mm Please Enable Macros to View BoQ information |