| 1 | Supply, installation, testing and commissioning of factory built floor mounted Air-cooled micro processor controlled Packaged AC unit of 17 TR nominal capacity with 6800 CFM (11550 CMH), 35mm WC static pressure conforming to IS: 8148 - 2018. (Reaffirmed year 2022). The air cooled packaged unit shall be supplied in two portion- indoor and outdoor unit. Indoor unit consist of two individual circuit hermetic sealed scroll compressors of each 8.5 TR +8.5 TR circuits operating on refrigerant R-410A, hydrophilic coated DX-type evaporator, evaporator blower with motor, copper piping, thermostatic expansion valve, driers, micro processor control board, temperature sensor, air filter , etc. Outdoor unit consist of condenser unit each 8.5 TR+8.5 TR capacity to suit copper tube with blue finned condenser coil, fan motor with propeller type fan (aluminium), fan bed , fan guard, isolator switch with internal wiring etc,. The condenser coil shall be fabricated of seamless hard drawn internally grooved copper tubes and aluminium fins (anti corrosive blue fins) of 0.1mm thickness, fins space ranging from 3 to 5 fins per cm, the minimum wall thickness shall be 1.0mm.etc., complete as per specification and as directed by Engineer- in- Charge. |
| 2 | Supply, installation, testing and commissioning of factory built floor mounted Air-cooled micro processor controlled Packaged AC unit of 11 TR nominal capacity with 4400 CFM (7470 CMH), 35mm WC static pressure conforming to IS: 8148 - 2018. (Reaffirmed year 2022). The air cooled packaged unit shall be supplied in two portion- indoor and outdoor unit. Indoor unit consist of two individual circuit hermetic sealed scroll compressors of each ( 5.5 TR +5.5 TR circuits ) operating on refrigerant R-410A, hydrophilic coated DX-type evaporator, evaporator blower with motor, copper piping, thermostatic expansion valve, driers, micro processor control board, temperature sensor, air filter , etc. Outdoor unit consist of condenser unit each 5.5 TR + 5.5 TR capacity to suit copper tube with blue finned condenser coil, fan motor with propeller type fan (aluminium), fan bed , fan guard, isolator switch with internal wiring etc,. The condenser coil shall be fabricated of seamless hard drawn internally grooved copper tubes and aluminium fins (anti corrosive blue fins) of 0.1mm thickness, fins space ranging from 3 to 5 fins per cm, the minimum wall thickness shall be 1.0mm.etc., complete as per specification and as directed by Engineer- in- Charge. |
| 3 | Supply and installation of seamless annealed hard drawn copper pipes and fittings like, bends, couplings for R 410A refrigeration system shall be interconnect between indoor and outdoor unit for suction and discharge connections conforming to L type ASTM B-280-03 standards. After completion of the piping installation the system shall be tested with nitrogen at pressure of 31 kg/sq.cm for a period of not less than 8 hours. No measurable drop in pressure should be detected after the pressure reading are adjusted for temperature changes etc., all copper piping complete as per specification and as directed by Engineer- in- Charge. |
| 4 | Set of copper tubes of size OD 1 1/8\\" (28.58 mm) with wall thickness of 1.83 mm& OD 5/8\\"(15.88 mm) with wall thickness of 1.02 mm |
| 5 | Set of copper tubes of size OD 7/8\\"(22.22 mm) with wall thickness of 1.40 mm & OD 5/8\\" (15.88 mm) with wall thickness of 1.02 mm |
| 6 | Supply and fixing of GI tray with cover and Supports for copper piping and cabling: Use factory fabricated 2mm thick GI tray ( perforated ) size of 450 mm x 50mmx 2 mm with GI cover and GI angles (40 x 40 x 3-mm), GI clamps (25 x 3-mm thick flat),GI Threaded rod (8mm) and GI fasteners etc., for clamping the copper pipes and cables . The GI support angles shall be grouted to the wall and roof structure using anchor fasteners. The maximum spacing between the supports shall not exceed 1200-mm. The copper piping and cable shall be completely covered with factory fabricated GI tray, etc., complete as per specification and as directed by Engineer - In- Charge. |
| 7 | Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade following sizes of cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification. |
| 8 | 4C X 16 sqmm 1.1kV grade Copper conductor FRLSH PVC insulation flat wire armour FRLSH PVC outersheath |
| 9 | 3C X 2.5 sqmm 1.1kV grade Copper conductor HRPVC insulation round wire armour FRLSH PVC outersheath |
| 10 | End Termination of the following size Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. |
| 11 | 4C x 16 Sq.mm including cable gland earthing |
| 12 | 3C x 2.5 Sq.mm including cable gland earthing |
| 13 | Supply and laying of 8 SWG copper earth wire double run between Indoor and outdoor units of PAC system as per scope of work and as directed by Engineer - in- Charge. |
| 14 | Supply and fixing of 63A rating , four pole, 415 V MCB 'C' series, Conforms to : IS 13947-3 in the Packaged Air conditioners control panel, complete with connections, testing and commissioning etc., all complete as per specification and as directed by Engineer in charge. |
| 15 | Supplying and fixing of 2 Amps , Two pole, 230 V MCB , \\" C' series, Conforms to : IS 13947-3 in the Packaged Air conditioners out door unit complete with connections, testing and commissioning etc., all complete as per specification and as directed by Engineer in charge. |
| 16 | Supply, installation , balancing and commissioning of following sizes of factory fabricated Galvanized sheet Steel lead free rectangular ducting complete with neoprene rubber gaskets, elbows, hangers, supports, etc,.The entire ducting work shall be fabricated out of lock forming grade galvanised sheet steel with specified Zinc coating of grade 375 conforming to IS 277. The plenum and ducting shall be complete with necessary M.S supports such has anchor fasteners , threaded rod of 10 mm , hangers, clamps, brackets , nuts and washers etc, and these M.S supports shall be duly painted with one coat of red oxide paint and two coat of enamel paint. All the flanges shall be provided with 6 mm thick felt neoprene gasket at joints etc.,complete as per specification and as directed by Engineer in charge. |
| 17 | Class VIII, lead free GSS 20 G ( thk 0.80 mm sheet) for plenum: |
| 18 | Class VIII, lead free GSS 22 G (thk 0.64 mm sheet) for ducting: |
| 19 | Supply and fixing of thermal insulation of 9mm thick duly laminated with 40G thick aluminum foil of mat finish closed cell Nitrile rubber(class \\"O\\") thermal insulation, etc, on fabricated duct after applying suitable adhesive for nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as directed by Engineer in charge. |
| 20 | Supply and fixing of 15 mm thick microban acoustic insulation in Plenum and supply air duct with open cell structure, 0.047 W/mK thermal conduction, fire retarded \\"O\\" class , resistant to chemical & micro organism and sound absorption class - D, etc. complete as per specification and as directed by Engineer in charge. |
| 21 | Supply and installation of adjustable type opposed blade Aluminium volume control damper with necessary flanges and PVC gears. The Dampers shall be made out of 14 G Aluminium channel as per the specification in Section -V. The opposed blades shall have tie rod with ball & socket joints,etc.. all complete as per specification and as directed by Engineer in charge. |
| 22 | Supply and fixing of G.I fire smoke dampers in supply air duct/ main branch and return air passage in the PAC unit . Fire dampers shall be multi blade louvers type. The blades and frame shall be constructed with minimum 1.6 mm thick Aluminium sheet . It shall be supplied with spring loaded UL stamped fusible link to close fire damper in the event of rise in air temperature . Fire dampers shall be CBRI tested & certified for required rating adainst collapse & frame penetration complete with locking device. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal etc., complete as per specification and as directed by Engineer in Charge. |
| 23 | Supply and fixing of double deflection type Supply Air Grille/Diffuser of following specification. Extruded anodized aluminium, powder coated, Off white colour, adjustable and locking type aliminium volume control damper having horizontal and vertical louvers. The louver portion shall be removable type for adjusting the Volume Control Damper etc.,all complete per specification and as directed by Engineer - in- Charge. |
| 24 | Supply and fixing of double deflection type Return Air Grille/Diffuser of following specification. Extruded anodized aluminium, powder coated, Off white colour, adjustable horizontal and vertical louvers and rat entry prevent mesh shall be provided without Volume control dampers etc., all complete as per specification and as directed by Engineer in Charge. |
| 25 | Providing and fixing in position of 9 mm thick PVC Gypsum tiles dimension of 600 X 600 mm. The PVC gypsum tiles with white vinyl finish have a surface light reflection. The tiles with polished aluminium foil backing to tiles increases the thermal insulation and provides protective vapour barrier. The PVC gypsum ceiling tiles should noncombustible and provides thermal insulation . Tiles should be mounted on ceiling suspension with galvanized 'T' grid system. Suspension ceiling 'T' grid (G.I) system includes main tee, long cross tee, short cross tee and wall angles. 'T' grid material should be hot dipped galvanized steel strip of size width 24 mm, thickness 0.3 mm. Surface treatment should be spray painted. (Note: Opening for light fixtures, supply air grilles, return air grilles are in contractors’ scope). |
| 26 | Supplying, fabricationg and fixing of medium weight channels for mounting of packaged AC outdoor unit. The \\"C\\" channel ISMC 100 as per ISI 808:1989 ( D100 mm X B 50 mm X T 5.0 mm). IS channels of TATA or SAIL or approved equivalent make including cutting, painting exposed faces with two coats of anti - corrosive paint of approved colour over a coat of red oxide primer, embedding with brick wall pedestaletc.,complete all as per specification. |
| 27 | Supply and fixing of 25 mm dia PVC drain pipe conforming to IS :15778 including fixing with required specials, fittings including fixing of G.I \\"C\\" clamp with interval of 1.0 m with sloping, bends , couplings and T - connection etc, all complete as per specification and as directed by Engineer in charge. |
| 28 | Providing and laying brick masonry in cement mortar 1:6 with well burnt chamber bricks/FLAG bricks of approved quality for PAC outdoor units including curing, raking out joints etc., all completes as per specification and as directed by Engineer - in Charge. |
| 29 | Plastering with cement mortar 1:5, 12 mm thick for brick work on its external faces at all sides of brick wall pedestal including curing and forming grooves wherever necessary all complete as per specification and as directed by Engineer in Charge. |
| 30 | Providing and casting insitu RCC M30 grade using machine crushed hard broken granite stone of maximum size 20mm, curing and finishing smooth all exposed faces including mechanical mixing, transporting, vibrating, consolidation, all insitu items like pedestal slabs for supply and exhaust blowers etc.as per drawings and specifications. |
| 31 | Safely dismandling of old Packaged AC equipments, air cooled condensers and associated ducting, dampers, existing false ceiling and supports, etc., from Male ward of DAE Hospital to IGCAR/DPS scrap yard by contractor in coordination with Department , all complete as per the scope and as directed by Engineer in charge. (NOTE : Contractor has to arrange transport facility and send G.I duct from GSO Hospital to DPS stores,IGCAR by peel of all Glass wool insualtion as a bare ducts). |
| 32 | Condensing unit : Supply and fixing of 5.5 TR outdoor condensing unit with hermetically sealed Non inverter ( fixed speed) scroll compressor of 5.5 TR capacity operation on R-22 refrigerant system (to suit existing blue star air cooled DX AHU for operation Theatre AHU as emergency standby ). Packaged AC Air- cooled condensing unit shall be compact coil made using advanced cross hatched copper tubes with anti corrosive coated aluminium blue fins. The entire unit shall be suitable for outdoor installation near seacoast. Complete as per specification and as directed by Engineer- in- Charge. Government of IndiaDepartment of Atomic EnergyGeneral Services OrganizationCentralised Tender Cell TENDER DOCUMENT FOR Refurbishment of packaged air conditioning system installed in Male ward at DAE Hospital, Kalpakkam. Tender No: GSO/CTC/MSD/306/2026. Part – II : Financial Bid (Section - VIII) INDEX S/No. Title No of Pages |
| 33 | GENERAL INFORMATION FOR GUIDANCE OF TENDERERS |
| 34 | The schedule of quantities is to be read for the purpose of pricing in conjunction with the special conditions, general rules for the guidance of contractors, conditions of contract, specifications, drawings, schedule of supply of materials and the appendices. |
| 35 | The prices inserted in the schedule of quantities shall be inclusive of value of the work described including all cost and expenses, which may be required in and for the construction of the work described together with the general risks, liabilities and obligations not forth or implied in the documents on which the tender is to be based. |
| 36 | The quantities stated are to be considered approximate only and the unit prices entered in the schedule of quantities and prices shall apply only to the actual quantities measured in the completed work in accordance with the specifications. |
| 37 | All the materials other than those shown in schedule of supply of materials in section VII are to be arranged by the contractor and his rates should account for the same. |
| 38 | Rates quoted for all items in this tender shall include cost of all materials. Department will not supply any materials other than materials stipulated in Section - VII of the tender and as such the rates quoted must be all inclusive. |
| 39 | If contractors need any clarification they are required to contact the ‘Engineer-In-Charge, CTC, ESG, GSO, Kalpakkam – 603 102, Chengalpattu district, Tamilnadu (Ph – 044-27480500 Extn. 85803, 85352) during office hours. Please Enable Macros to View BoQ information |