| 1 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR LED Street Light fixture with Minimum lumen output 5600 lm |
| 2 | LED Street Light fixture with Minimum lumen output 8700 lm |
| 3 | Providing & Fixing of Street light bracket made out from followingsize of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P -1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc.as required. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR .40 mm Dia |
| 4 | Supplying and drawing of XLPE insulated LT Aerial bunchedAluminium conductor cable confirming to IS 14255/1995 and IS 398(Pt-4)/ 1994 and as per Discom Specs. on existing cross armsthrough I hook with all necessary T&P required including binding andtwisting etc. complete in all respect as required. All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR .1 X 25 sq. mm. + 1X25 sq. mm. (insulated) |
| 5 | Supplying and drawing FR PVC insulated & unsheathed flexiblecopper conductor as per PWD specification for electrical Works withISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wireshould be made from 99.90 % purity copper, class 5 stranding inacc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for lesschances of oxidization, insulation PVC type A/C/D , flame retardantas per IS 10810-53, better amperage rating as per IS:3961 part 5, inexisting surface or recessed PVC/ MS conduit/casing cappingmaking connections with Copper Lugs of suitable size,Ferrules,testing etc. as required. OEM Must have its own in houseNABL lab setup for all testing facilities for wires. For additionaltechnical parameters of product / work refer Annexure 'A' attachedwith this BSR 2 x 2.5 sq.mm |
| 6 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10kA breaking capacity (B/ C/D tripping characteristic as per type ofload and site requirement) 4 KV impulse withstand voltage, ISImarked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC, minimum phase termination capacity of35sq.mm. , conductor line load reversibility , IP 20 contact protectionand fitted in existing distribution board/sheets, minimum electricaloperation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80A & above rating including making connections, testing etc. asrequired. OEM shall have submit NABL / CPRI / ERDA accrediatedlab type test reports & All as per pre approved by Engineer incharge. For additional technical parameters of product / work referAnnexure 'A' attached with this BSR Single pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating |
| 7 | Four pole MCB (With B/C curve tripping Characteristics) 50/63 A rating |
| 8 | Providing & Fixing of AC operated heavy duty 230 /440 Volt powercontactor as per PWD specification for electrical Works, ISI markedIS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking,auxilary contacts, Din rail mounting type including makingconnections, testing etc. as required. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR . 63 Amp |
| 9 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) /Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity , high tensile nutsand bolts spring washers in existing panel including bending , cuttingin required shape and size and colour coding with heat shrinkablePVC sleeves. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR .One day reserve (Analog type ) |
| 10 | Structural steel work in single section fixed with or withoutconnecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Please Enable Macros to View BoQ information |