| 1 | Supply and fixing in repair of heat tracing cable ( self regulating) 14 AWG nickel plated copper bus conductor for GI / DI pipe rated ouput wattage at -10 to 5 degree 30 w/m at 220 V complete all as specified and directed. |
| 2 | Supply and fixing in repair of heat tracing cable ( self regulating) 14 AWG nickel plated copper bus conductor for PPR pipe rated ouput wattage at -10 to 5 degree 30 w/m at 220 V complete all as specified and directed. |
| 3 | S&F in replacement of damaged nitrile insulation 19 mm thick over PPR/GI pipe of 20/25 mm bore size complete all as specified and directed. |
| 4 | S&F in replacement of damaged nitrile insulation 19 mm thick over PPR/GI pipe of 32/40 mm bore size complete all as specified and directed. |
| 5 | S&F in replacement of damaged nitrile insulation 19 mm thick over PPR/GI pipe of 50 mm bore size complete all as specified and directed. |
| 6 | S&F in repair 3 layer PPR polypropylene random copolymer pipes SDR 7.4 (PN16) & SDR 11 UV of 25 mm bore stablished and antimicrobial welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings to be laid in trenches/wall/floor complete all as specified and directed.Note all connected fittings like elbow, tee, reducer coupler will be count in RM |
| 7 | All as per item No 6 above but size of pipe 32 mm bore complete all as specified and directed. |
| 8 | All as per item No 6 above but size of pipe 40 mm bore complete all as specified and directed. |
| 9 | All as per item No 6 above but size of pipe 50 mm bore complete all as specified and directed. |
| 10 | S&F in repair 3 layer PPR Gate valve 32 mm bore complete all as specified and directed |
| 11 | S&F in repair 3 layer PPR Gate valve 20 mm bore complete all as specified and directed. |
| 12 | S&F in repair 3 layer PPR Gate valve 25 mm bore omplete all as specified and directed. |
| 13 | S&F in repair 3 layer PPR Gate valve 40 mm bore complete all as specified and directed. |
| 14 | S&F in repair 3 layer PPR Gate valve 50 mm bore complete all as specified and directed. |
| 15 | Making connection of PP-R distribution branch with PP-R main of following sizes by providing and fixing tee including cutting and making fusion joint of size 16 to 40 mm etc. |
| 16 | Making connection of PP-R distribution branch with PP-R main of following sizes by providing and fixing tee including cutting and making fusion joint of size 50 to 75 mm etc. |
| 17 | Excavation in trenches exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard and rock soil complete all as specified and directed. |
| 18 | Returning, filling including spreading leveling watering and well ramming in layers not exceeding 25 mm in any type of soil complete all as specified and directed. |
| 19 | Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point. |
| 20 | S&F in reapair GI tubing galvanized medium grade laid in trenches/walls including all necessary fittings clamps etc complete and connecting to existing system of following dia complete all as specified and directed. |
| 21 | 25 mm bore |
| 22 | 40 mm bore |
| 23 | 50 mm bore |
| 24 | S&F in repair gun metal gate valves with iron wheel head screwed both ends for GI pipe of the following dia: - |
| 25 | 25 mm bore |
| 26 | 40 mm bore |
| 27 | 50 mm bore |
| 28 | S&F in repair sluice valve of size 100 mm bore ISI marked,flanged ends drilled pressure rating PN-1.6 conforming to IS 14846-2000 having stainless steel spindle with cast iron operational wheel at top complete all specified and directed. |
| 29 | S&F in repair sluice valve of size 80 mm bore ISI marked,flanged ends drilled pressure rating PN-1.6 conforming to IS 14846-2000 having stainless steel spindle with cast iron operational wheel at top complete all specified and directed. |
| 30 | S&F in repair 100 mm bore NRV for CI/DI pipe line complete all as specified and directed. |
| 31 | S&F in repair 80 mm bore NRV for CI/DI pipe line complete all as specified and directed. |
| 32 | S&F in repair 50 mm bore Ball Valve for CI/DI pipe line complete all as specified and directed. |
| 33 | Supply and fix in repair pressure booster pump of capacity 1 HP including neccessary connections all as specified and directed. |
| 34 | S&F in repair automatic star delta starter 415 volts 3 phase suitable for 20 HP motor complete all as specified and directed. |
| 35 | M&L for lifting of submersible pump motor set of any description and capacity including dismantling MS column pipe, steel wire rope from the bore well upto a depth of 90 mtr complete all as specified and directed. |
| 36 | Re-installations of pump and motor set in the bore well in the same position alongwith all necessary work like fixing of column pipe, connections of rope with U clamps, connection to the discharge line, dry revolution test etc complete all as specified and directed. |
| 37 | M& L for repair and rewinding submersible motor of capacity of 12.5 HP with existing size wire with copper conductor of standard size including Varnish insulation paper and soldering of connection etc. Assembly of motor with pump set with necessary studs, bolts, washer etc complete with all connection all as specified and as directed by Engr-in-ChargNote:-(1) item rate includes transporation of motor from site to workshop and back.(2) If any other parts found unservicable, the same shall be measured seperately on relevant item under supply only. |
| 38 | Supply only following parts for submersible motor of capacity upto 12.5 HP:- |
| 39 | Upper/lower level spl type GM bush bearing. |
| 40 | Sand Guard of motor |
| 41 | Stainless steel sleeve for pump. |
| 42 | Impeller made of Gun metal for pump |
| 43 | Pump shaft stainless steel upto 5 stage |
| 44 | Seal ring made of Gun metal |
| 45 | Discharge bush made of gun metal |
| 46 | Suction bush made of gun metal |
| 47 | Pump body bush made of gun metal |
| 48 | CI stage bowl |
| 49 | Housing Head Complete Front/Rear |
| 50 | SS Pump motor coupling as per sample |
| 51 | SS stud nut |
| 52 | L Key bolt |
| 53 | M & L for cleaning of under ground RCC tank of capacity 40000 ltr after draining out water with pumpset, scribing and rubbing silt/grass from inside surface of wall/roof by iron brush and cleaning the tank with fresh water and bleaching powder for complete removal of scales,sludge and fungus away from the tank and pump house premises, complete all as desired by Engr-in-Charge |
| 54 | M & L for cleaning of under ground RCC tank of capacity 80000 ltr after draining out water with pumpset, scribing and rubbing silt/grass from inside surface of wall/roof by iron brush and cleaning the tank with fresh water and bleaching powder for complete removal of scales,sludge and fungus away from the tank and pump house premises, complete all as desired by Engr-in-Charge |
| 55 | M & L for cleaning of water storage steel tank of capacity 5000 ltr after draining out water with pumpset, scribing and rubbing silt/grass from inside surface of wall/roof by iron brush and cleaning the tank with fresh water and bleaching powder for complete removal of scales,sludge and fungus away from the tank and pump house premises, complete all as desired by Engr-in-Charge |
| 56 | Deduct Credit for Demolished/Dismantled material Rs (-)69,090.00 (Minus) as listed in Schedule 'A' Part-II (Credit Schedule)Note : Tenderers will not quote against this item being a tentative amount, to be considered to arrive at the 'Contract Sum'. Please Enable Macros to View BoQ information |