| 1 | Supply, laying and testing, in replacement LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 10 sq. mm 2 core, confirming to IS -7098 Part-I complete all as specified |
| 2 | Supply, laying and testing, in replacement LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 volts, grade cross sectional area 10 sq. mm 4 core, confirming to IS -7098 Part-I complete all as specified |
| 3 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/loose soil for laying of cable, pole foundation, stay, laying of pipe etc complete all as specified and directed. |
| 4 | All as per item No. 3 here-in-before but depth exceeding 1.5 mtr and not exceeding 3 mtr. |
| 5 | Removing excavated soil to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 6 | Returning filling including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and directed. |
| 7 | M&L for sand cushioning to under ground cables with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable punned down to 18 cm complete all as specified and directed. Note :- Punned thickness 18 cm shall be measured for payment. |
| 8 | M&L for Brick covering with width equal to length of brick as mechanical protection to cable with well burnt sub class 'B' bricks laid as directed. |
| 9 | M&L for Prestressed concrete pole, 9.0 metres long 102mm x 152mm at top and 102 mm x 289 mm at bottom, class 10 in replacement including dismantling of old UNSV pole , numbering new pole and applying two coats of synethic enamel paint upto 1.5 mtr from top of coping for black and white strip alternately each 30 cm wide.(Note: Earth work including excavation ,Returning filing,PCC work,removing excated material will be measured and paid separetly under respective items of schedule) |
| 10 | M&L for providing Plain cement concrete 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) as in coping, cable duct, cover slab and benching including all necessary form work complete all as specified and directed. |
| 11 | M&L for providing PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation, filling and mass concrete all as specified and as directed. |
| 12 | S&F in repair pole mounted junction box made out of 18 gauge MS sheet front opening shutter with locking aggangement including fixing accessories such as clamp, nuts and bolts etc including two coats of aluminium paint over a coat of red oxide primer of size min 20x15x10 Cm comprising of 04 strips 63 Amps aluminium bus bar with MCB SP 06 Amps complete all as specified and directed by Engr-in-Charge |
| 13 | S&F in repair street light fixture ≥90 watt LED with pressure die cast aluminium housing with toughened glass having IP-66 degree of protection, individual LED's must have secondary lense for better throw across and along the road, with system luminarie efficacy ≥100 lumen/watt, colour rending index(CRI) of ≥ 70, co-related colour temperature (CCT) of 5700K. Luminaire should have surge protection upto 05 KV and having additional surge protection upto 10 KV for driver, PF ≥ 0.9 and THD ≤10% , operating voltage range from 140 to 270 volt, The potted driver used shall be a constant curent driver with efficiency of ≥ 85%.The manufacturers LOGO shall be engraved into housing of luminaire. including bracket for fixing of street light fittings bend to shape, made out of 25 mm dia GI pipe medium grade upto 1.5 mtr long fixed with and including two sets of MS clamp made out of Flat iron of size 50x6 mm, fabricated to shape and fixed with nuts, bolts & washers & two coats of aluminum paint over a coat of red oxide primer complete all as specified and directed by Engr-in-charge. |
| 14 | S&F in repair single run of PVC insulated and PVC Sheathed cable HR with copper conductor of size 3 core x 1.5 sqmm & necessary conduit pipe of size 20mm for protection from wind/sunlight proper clamping etc from JB to bracket of streetlight copper conductor cable of size 1.5 sqmm threecore all as required and specified by Engr-in-Charge |
| 15 | S&F in replacement automatic street light timer switch single phase, suitable to take load of minimum 5 kw 3 Phase, 230 V based on weather proof photoelectric timer adjustable upto min 10 lux , alongwith suitable power contactor & MCB TPN 40 Amp on both input and output duly prewired with suitable size of copper wiring with proper lugs and terminal blocks with facility of manual ON/OFF switch complete enclosed in polycarbonate IP 66 enclosure shock, rust, weather & termite proof uv-resistant, FR grade fixed on pole with MS strip of size 20 X 2 mm complete all as specified & directed by Engineer -in -charge |
| 16 | Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 63,705.00 and any other reduction if any from quoted amount. Please Enable Macros to View BoQ information |