| 1 | AIR WASHER :- Supply, Installation, testing and Commissioning of floor mounted double skin type air washer units with minimum 90 % saturation efficiency made of 46 mm thick panels consisting of pre-plasticized SS casing of thickness 0.8 mm outside layer and 0.8 mm thick plane SS sheet at inside layer with polyurethane foam (PUF) insulation with density of 40 kg/cum. factory injected between them by injection moulding machine, complete with 46mm thick HDPE prefilter, 200mm deep cellulose pad , water distribution header, indigenous pump, internal piping GI 'B' class, valves & fittings, MS water tank with FRP lining, DIDW centrifugal forward curved fan and fan motor ( EFF-1) with IP-55 protection suitable for 415 +10% volts, 3 phase, 50 Hz A.C supply , V-belt & drive set vibration isolators quick fill, make up, drain, overflow connection and TP isolator with MS enclosure box complete in all respects etc. The unit shall be of following capacities with 65 mm WG static pressure |
| 2 | 42500 CFM 65 MMSP (Main Kitchen) |
| 3 | 20000 CFM 65 MMSP (1st Floor) |
| 4 | 40000 CFM 65 MMSP (Boondi Kitchen) |
| 5 | 50000 CFM 65 MMSP (Boondi Kitchen) |
| 6 | Exhaust Air Scrubber :- Supply, Installation,Testing & Commissioning of Floor Mounted Dry Air Scrubber each comprising of extract air intake section, electrostatic precipitation technology, dry type air cleaner to remove odour, smoke & fumes from exhaust air. Electrostatic section shall be made of 22 gauge Stainless Steel sheet, high bake epoxy powder coated, washable type aluminium mesh filters, stainless steel spiked ionizers to create high voltage DC field, aluminum collector plates which should be alternatively charged positive and negative with large collecting area with 14\\" deep cell, to work as magnet for charged smoke & oil particles. Average efficiency of 90-95% in single pass as per DOP test method. Electrostatic Precipitator should be able to charge particles from 0.01 micron to 10 microns through solid state power supply. Collector cell should be of permanent type and incorporate slide out facility for easy removal for cleaning. The system should be fitted with interlock switch for safety . The system should allow connection to a fan section to achieve 500 FPM velocity across the air cleaner. |
| 7 | 50000 CFM 80 MMSP (Main Kitchen) |
| 8 | 23900 CFM 80 MMSP (1st Floor) |
| 9 | 34000 CFM 80 MMSP |
| 10 | 42500 CFM 80 MMSP |
| 11 | Chiller Supply, installation, Testing & Commissioning of nominal cooling capacity - 18.8 TR Air Coolled Scroll Chiller Package complete with 2 Nos. of hermetic scroll type compressor - each with microprocessor based control panel, motor, starter panel, machine mounted air cooled condensers, insulated chiller, water flow switch, vibration isolators. Refrigerant gas used shall be R410a of following specifications : Cooling Capacity : 18.8 TR Water Flow : 49.7 US GPMPower Unit : 20.3 KwCompressor Type : Hermetic Scroll X 2Refrigerant Type : R410a |
| 12 | Ducting Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 13 | Main Kitchen |
| 14 | 0.63 mm (24 guage) |
| 15 | 0.80 mm (22 guage) |
| 16 | 1st Floor |
| 17 | 0.63 mm (24 guage) |
| 18 | 0.80 mm (22 guage) |
| 19 | Boondi kitechn |
| 20 | 0.63 mm (24 guage) |
| 21 | 0.80 mm (22 guage) |
| 22 | Duct Insulation :- Supplying , installation, testing & commissioning of external thermal insulation on ducts with Duly laminated aluminum foil of mat finish Closed Cell Nitrile Rubber (class “O”) insulation after applying of suitable adhesive for nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specification9 mm thick Closed Cell Nitrile rubber insulation with Factory Laminated Aluminium Foil for Supply Air Duct |
| 23 | Main kitechen + 1st floor |
| 24 | Boondi kitechn |
| 25 | Air Grills :- Supply, fixing and commissioning of powder coated extruded aluminium 300X300 size fresh air grills with damper complete with nuts, bolts, screws etc. |
| 26 | Main Kitchen |
| 27 | 1st Floor |
| 28 | Boondi kitechn |
| 29 | Supply & fixing of Powder Coated Aluminium Grills/Diffusers with Volume Control Dampers |
| 30 | Kitchen Hood :- Supply, Installation, Testing & Comissioning of SS Exhaust Hood with Baffle type Filter one side SS Grade 304 & 18 Guage (1.2 mm) of SS Filter size 500X500 with or without 2 LED Light of following sizes, the rate should be inclusive of transportation, labour, loading & unloading and extra expenses if any |
| 31 | 1500X1500X750 |
| 32 | 1800X1500X750 |
| 33 | 3000X1500X750 |
| 34 | Electical Panel : Supply, Installation, Testing Comissioning of Powder Coated Electrical Control Panel for Air Washer of the following specifications with test certificate: Voltage Range : 380-480VPhase- 3 PhaseFrequency : 50-60 HzPower Rating : 5KW to 15KWMain Circuit Breaker : MCCBMotor Protection : Speed Control, Soft Start, Overload Protection, Overvoltage, Phase Failure RelayContractor : High-Quality 3 Phase ContractorControl System : PLC for Automation and Sequencing with user-friendly control and monitoringController : EC Fan Motor Controller for Variable Speed Control and related accessoriesSafety Control : Waterproof, Shockproof |
| 35 | Electrical Control :- Supply, Installation, Testing Comissioning of Powder Coated Electrical Control Panel for Air Scrubber of the following specifications with test certificate: Voltage Range : 415VPhase- 3 PhaseMain Circuit Breaker : MCCB 32A Breaking Capacity 25kAOverload Relay : Adjustable for 16-20AMotor Protection : Speed Control, Soft Start, Overload Protection, Overvoltage, Phase Failure RelayContractor : AC3 Duty Rated 32ABusbars : Copper or GI with capacity of 25AComponents : Push Button for Start/Stop, Indicator Lamps (On/Off, Fault), Emergency stop Switch, Timers for star-delta or soft start operationSafety Control : Waterproof, Shockproof |
| 36 | Supply, Installation, Testing and Commissioning and laying of following 415 volts grade PVC insulated sheathed copper conductor unarmoured control cables in existing conduit,OR clamped on wall with suitable saddles, cable tray fixing bolts, including testing and commissioning as per site requirement. |
| 37 | 3 Core 2.5mm Flexible Copper Control cable for Air Washer Electrical Panel |
| 38 | 3 Core 1.5mm Flexible Copper Control cable for Air Scrubber Electrical Panel |
| 39 | Buyback existing Air ventilation & Exhaust system with electric pannel and ducting etc. Please Enable Macros to View BoQ information |