| 1 | Schedule 'A' Section - I |
| 2 | Excavation in trenches in hard dense soil n.exc 1.5 mtr wide & n.exc 1.5mtr in depth and n. exc. 10sqm on plan for laying pipe in trenches and getting out complete all as specified and directed. |
| 3 | Returning filling in trenches, spreading, levelling, watering and well ramming in layers n.exc 25cm in hard dense soil complete all as specified and directed. |
| 4 | Removing of surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above starting point complete all as specified and directed. |
| 5 | Taking down unserviceable old sluice valve from existing position and supply and fixing in replacement CI Sluice valve of 150mm dia bore, seated gate valve with pocket less body, SS Stem (AISI 410), EPDM coated DI wedge 100% vaccum tight design with toroidal sealing rings & over 250 micron epoxy coating in PN 1.6 designed to BS:5163/IS:14846 Non-Rising stem type with gear wheel operation with including necessary arc/gas welding with flange as per existing pipe line , tail pics of MS Pipe as per site requirement not less than 350mm length, dia of tail peace as per existing pipe ,stainless steel spindle of suitable length including suitable size nuts, bolts, washer and rubber gasket all as required and directed at site. |
| 6 | All as per Srl No 04 but for sluice valve size 100mm dia bore complete all as specified and directed. |
| 7 | All as per Srl No 04 but for sluice valve size 80mm dia bore complete all as specified and directed. |
| 8 | All as per Srl No 04 but for sluice valve size 50mm dia bore complete all as specified and directed. |
| 9 | Supply And Fixing in replacement of Air release valve DI Single Chamber, Tripple Action with Ss floating And working parts & Fb Expoxy coating in PN1.6 of size 150mm conforming to IS 14845 incl 8 Nos 19.05mm dia ,100mm long Nut ,bolts, 2 nos washer incl 3 mm thick gasket of required size and shape complete for jointing with the existing pipes, duly welded with pipes/fittings bends properly to both the plain ends complete all as specified and directed. |
| 10 | Supply, installation, testing and commissioning of chlorine dosing pump model RA-11 electromagnetic type with accessories like anti siphon valve/ discharge tubing capable to driver 10LPH @ 6 kgs/cm squ back pressure and FRP solution preparation tank capacity : 100 Ltr with lid, port hole, onlet / outlet / drain connection, level guage etc and fitted with 960 RPM motor & PVC agitator complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply, installation, testing and commissioning of 5 HP submersible pump set (vertical type) suitable for installation in well, complete with submersible motor, pump, suction strainer, non-return valve (NRV), rising main, submersible copper cable of required size, control panel with starter and protection devices, earthing, and all necessary accessories, complete all as specified and directed by Engr- in-Charge. |
| 12 | Supply and fixing of 5 HP submersible pump starter control panel complete in all respects, suitable for safe, efficient, and reliable operation of submersible pump motor, including sturdy weather-resistant enclosure, all required relays, start and stop push buttons, indicator lamps, internal wiring and voltmeter and ampere meter complete all as specified and directed by Engr- in-Charge. |
| 13 | Re- development of bore well by means of air compressor of capacity ( not less than 600 cu.feet/minute) followed by high capacity pump to its optimum yield till clear water of potable quality free from sand and silt is obtained including draw down performance and yield test of tube well complete all as specified and directed by Engineer - in charge.(Note :- compressor shall be not less than 75 BHP or above capacity pumping set equipment for testing yield shall be used). Note: (i) Unit rate quoted under this items shall deemed to be inclusive cost of Necessary tools and equipments with fuel as required to the site of work and removing the same after completion of work. |
| 14 | Supply & fixing in replacement Mild steel screw bolts (machine made) with hexagonal heads at one end and screwed the other, or screwed both ends, each washers and one hexagonal or sequare nut, exc. 5 cm but n exc 10 cm te all as specified and directed bt Engr-in-charge |
| 15 | Material & labour for removing existing sludge from reservoir & depositing the sludge upto 100 m distance & cleaning , scrapping down deposit from floor & wall , washing the walls/floor with bleaching powder in the reservoir of following capacity, complete all as specified & directed. |
| 16 | 14 Lakhs gallon water South spring supply installation |
| 17 | 10 Lakhs gallon water RCC supply installation |
| 18 | 30 Lakhs gallon water RCC supply installation |
| 19 | 24 Lakhs gallon water RCC supply installation |
| 20 | .315 Lakh gallon water South spring Installation |
| 21 | Supply & fixing in repair/replacement Steel reinforced compressed asbestos fibre gasket of 5.0 mm thickness for 150mm nominal size pipes comprising of suitable holes for attachments, complete all as specified and directed by Engr-in-charge. |
| 22 | Dismantling and Construction of new brick masonary pit of size 150x120x90 Cm internal size with MS Sheet 3MM Thick and angle iron frame of size 40x40x6mm duly painted with 2 cots of synthetic enamel paint over a coat of red oxide primer including locking arrangement with lock with 3 keys, lifting handle and includng excavation / earth work, PCC in foundation, brick work , plaster including demolaton of existing pit complete all as specified and directed by Engr- in-Charge. |
| 23 | Material & labour for PCC (1:3:6) type C2 using 40mm graded stone aggregate for anchorage blocks for pipe line/making good the cut portion of roads/paths/hard standings etc including necessary from work where required , to support the pipe line complete all as specified and as directed by Engineer-in-charge. |
| 24 | Material & labour for Two coats of synthetic enameled paint (tint of paint as directed) over one coat of red oxide primer on surfaces including preparation of old surfaces of any description including fittings, Gate valve and NRV etc complete pump sets upto tanks and complete pipe lines inside distribution tank area to delivery gate valve in pit chamber for Pump, delivery head, NRV, Sluice Vlave for one Set of Pump complete as directed at different locations of water supply installation at kasauli complete all as specified and directed by Engineer-in-charge. |
| 25 | All as per item No 15.00 above but from Tank to pump suction line -- ditto --, |
| 26 | All as per item No 15.00 above but from pump to delivery line upto inside installtion area -- ditto --, |
| 27 | Dismantling and taking out old u/s worn out MS/CI/GI pipe line flanged type 150 mm bore including fittings complete with nuts, bolts, washers and gaskets etc and removing from the site complete all as specified and as directed by Engineer-in-charge. Note:- New pipes shall be laid first at spring area and old ones to be taken out later. |
| 28 | Supplying, laying and testing hot finished seamless carbon steel pipe not less than YST-240, grade B as per ASTM A 106, Sch 40, nominal size NPS-150 mm, outer dia 164.22 mm, with nominal wall thickness 7.11 mm and weight 28.26 Kg/ mtr, including short pieces as required at site, laid in trenches/over RCC pillars/across or under bridges/along hill side (up or down)/culverts/inside valve pits complete all as specified and directed by Engr-in-charge. NOTE:- (i) Excavation Earth work, PCC, seamless pipe fittings, MS flanges & flanged joints shall measured and paid for separatly under relevant items. (ii) Work will be carried out in piecemeal loacations experienced based on break downs and weaker sections of existing rising main as per site requirement and as directed by Engineer-in-charge. (iii) Any other expenses including permision from state authorities are included under this item. |
| 29 | Material & labour for MS Flange of inner dia 150 mm (outer dia 164.22mm) and 280 mm outer dia of thickness 25.3 mm having 8 drilled holes complete for jointing with the existing pipes, duly welded with pipes/fittings bends properly to both the plain ends complete all as specified. and directed. |
| 30 | Supply and fixing of joint for 150 mm nominal bore pipes, comprising one 5.0 mm thick steel-reinforced compressed asbestos fibre gasket, including 8 Nos. M38 nuts and bolts (each bolt not less than 25 mm in diameter and 125 mm in length), and 2 Nos. 5 mm thick washers per joint, suitable for pipes/fittings/bends, complete all as specified and directed by the Engineer-in-Charge. |
| 31 | Supply And Fixing in replacement and testing of high pressure, heavy duty cast steel sluice valve, nominal size 150mm, conforming to API 600, classs 600, Suitable to hydrostatic test pressure for body 156 KG /sq cm & for seat 115kg/cm, both ends flanged in existing line, after removal of old unservicable gate valve without damaging to exting pipe line complete all as specified and diected by Engr-in-charge. NOTE:- Suitable size MS Flange for exiting pipe line, joints and joining materials shall be including under this item. |
| 32 | Supply And Fixing in replacement and testing of high pressure, heavy duty type cast steel Non Return,valve/ check valve, nominal size 150mm, PN 10 conforming to BS 1868, classs 600, Suitable to hydrostatic test pressure for body 156 KG /sq cm & for seat 57 kg/sq cm, both ends flanged in existing line, after removal of old unservicable gate valve without damaging to exting pipe line complete all as specified and diected by Engr-in-charge. NOTE:- Suitable size MS Flange for exiting pipe line, joints and joining materials shall be including under this item. |
| 33 | Supply And Fixing in replacement and testing of high pressure, heavy duty cast steel sluice valve, nominal size 150mm, conforming to API 300, classs 300, Suitable to hydrostatic test pressure for body 78 KG /sq cm & for seat 115kg/cm, both ends flanged in existing line, after removal of old unservicable gate valve without damaging to exting pipe line complete all as specified and diected by Engr-in-charge. NOTE:- Suitable size MS Flange for exiting pipe line, joints and joining materials shall be including under this item. |
| 34 | Supply and fixing of chequered steel plate cover over cable trench, conforming to Fe 410-W (Gde E-250) Quality-A steel. The plate is provided with an anti-slip chequered pattern to ensure safe movement. It securely covers electrical conduits and utility cables, protecting them from damage, dust, and unauthorized access complete all as specified and directed by Engr-in-charge. |
| 35 | Amount of credit of Rs. 210780.00 for retrived old material as mentioned in Schedule 'A' section-II of tender document in pdf form, will be deducted offline while acceptence of tender. Please Enable Macros to View BoQ information |