| 1 | Grass cutting and surface dressing including removal of unwanted/rubbish plants with roots from open ground /yard and other Nigam premises with stacking of grass/plants at desired place near the ground. |
| 2 | Levelling of ground |
| 3 | Levelling of ground above 30 cm.to 90 CM.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) |
| 4 | Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13). |
| 5 | (A) Height of poles/R.S.Joist/M.S. Rail Size of pit |
| 6 | 9 Mtr/ 1.2mx0.6mx1.50 m deep |
| 7 | (C)Stay set/Depth of pit |
| 8 | 8'x 3/4\\" -0.75x0.5x1.6 m |
| 9 | Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms .Liftup to 1.5 Meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 Meter. |
| 10 | Hard soil mixed with boulders |
| 11 | Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate mix. |
| 12 | Plaster on new surface on walls in cement ,sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick. |
| 13 | Masonry for foundation and plinth |
| 14 | Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges. |
| 15 | Safe carriage of PCC poles including loading / un-loading |
| 16 | a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole |
| 17 | Within 10 Kms. |
| 18 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(4.75*20) |
| 19 | Above 30 Kms. Add for each Kms. or part thereof. |
| 20 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site |
| 21 | Within 10 Kms. |
| 22 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof. (4.61*20) |
| 23 | Above 30 Kms. Add for each Kms. or partthereof. |
| 24 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. |
| 25 | Within 10 Kms. |
| 26 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(5.57*20) |
| 27 | Above 30 Kms. Add for each Kms. or part thereof. (20*3.52) |
| 28 | Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading from store to site (these Charges will be 1.5 times for both sides) |
| 29 | a) 10 & 16 KVA |
| 30 | Above 10 Kms. & upto 30 Kms Add for each Km.or part thereof. |
| 31 | Above 30 Kms. Add for each Kms. or part thereof. |
| 32 | b) 25 & 40 KVA |
| 33 | Within 10 Kms. |
| 34 | Safe Carriage of 33/11 KV Power Transformer |
| 35 | c) 5.0 MVA |
| 36 | Within 10 Kms |
| 37 | Above 10 Kms & upto 30 Kms . Add for each Km or part thereof @(50.81/km *20) |
| 38 | Above 30 Kms & upto 50 Kms . Add for each Km or part thereof @(33.61/km *20) |
| 39 | Above 50 Kms . Add for each Km or part thereof (upto 60 km)@16.27/km |
| 40 | Safe loading of power/ distribution transformer. |
| 41 | (A) 33/11 KV power transformer. |
| 42 | 5 MVA |
| 43 | Safe unloading of steel fabricated/ unfabricated conductor drum & other line material. |
| 44 | Safe unloading of power/distribution transformers |
| 45 | a) 33/11 KV power transformer. |
| 46 | Above 3.15 MVA |
| 47 | Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. |
| 48 | PCC Poles 9 Mtr. Long(400 Kg.)/11Mtr.long |
| 49 | Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire |
| 50 | 8\\"x3/4\\" with 7/8 SWG stay wire |
| 51 | Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. |
| 52 | Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station. |
| 53 | Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1 Nos. disc & 1 set of H/W ) on terminal point including fixing of hardware and strips. |
| 54 | Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 Nos. disc.& 1set of H/W) on terminal point including fixing of hardware and strips. |
| 55 | Fixing of 33kv pin insulator with pins. |
| 56 | Fixing of 11 KV pin insulator with pins. |
| 57 | Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. |
| 58 | (B)G.O. switch . without earthing blade. |
| 59 | 33kv G.O.switch |
| 60 | 11kv G.O.switch |
| 61 | Assembly and installation of Horn Gap fuse set (set of 3nos)on erected structure as per design, complete in all respectwith post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. |
| 62 | 33kv Horn Gap fuse set. |
| 63 | 11kv Horn Gap fuse set. |
| 64 | Installation of lightening arrestors on erected structure /support (1 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates |
| 65 | (A)sub-station type |
| 66 | 33 KV L.A. each |
| 67 | 11 KV L.A. each |
| 68 | Installation testing as per Nigams norm & commissioning of 11/0.4KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates |
| 69 | 25 and 40 KVA |
| 70 | Fixing of PG clamp of Dog /Racoon Conductor |
| 71 | Assembly,installation & commisioning of 11 KV Roaster switchs on erected structures with stting for accurate operation including fixing of allied accessories completed in all respect with post insulators and jumpering on both ends for connection with systm.The nuts & bolts will be supplied by contractor for which payment will be made as per prevailing Dicom store issue rates. |
| 72 | Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. |
| 73 | (A) IN URBAN AREA |
| 74 | ACSR DOG |
| 75 | 3 Nos. of earthing of 11/0.4 KV distribution transformer /sub-station with 3 pieces of M.S.Rod 20mm dia each 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16\\" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm (having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence. |
| 76 | Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder: |
| 77 | Excavation of trench of 0.65 Mtrs.depth and 0.5 Mtr.width |
| 78 | Ordinary rock ( where blasting is not required.) |
| 79 | Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust. |
| 80 | Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust. |
| 81 | Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil: |
| 82 | Where drilling is required |
| 83 | Painting of exposed portion of MS flat/rod with two coats of red-oxide primer and two coats of green enamel paint.including material. |
| 84 | Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates. |
| 85 | (B) IN RURAL AREA |
| 86 | PCC Poles 9 Mtr. Long |
| 87 | Laying / stringing of bus bar with ACSR Dog & jumper connection using tie rod ,33KV /11KV insulator strings,required hardware,P.G.clamps/T clamps etc.as per requirement including Y-connections at bus bar jumpering point as per the direction of engineer in-charge. |
| 88 | ACSR DOG/RABBIT |
| 89 | Laying, testing termination of control cable 1100 volts PVC insulated including supply and installation of ferrules to designate various cores of control cables by terminal Nos. of identification including utilization of cable gland. The control cable should be clearly arranged in trenches avoiding crossings including clamping of control cable at regular interval and providing identify tags. |
| 90 | 2x2.5 Sq.mm. |
| 91 | 4x2.5 Sq.mm. |
| 92 | 12x2.5 Sq.mm. |
| 93 | 4x4 Sq.mm. |
| 94 | Installation of metering points on 11 KV Out going feeder at 33/11 KV S/S. |
| 95 | Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide) |
| 96 | On new surface |
| 97 | Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint) |
| 98 | On new works with two coats. |
| 99 | Fabrication of steel structures of M.S angle, M.S.channel & M.S.Flat including cutting, drilling as per design and drawing. |
| 100 | 33/11 KV Rural Sub-Station Structure (4086.879 Kg) |
| 101 | Drilling of holes in MS Channel / Angle /Flat |
| 102 | 11/16\\" dia holes(17.46 mm dia.) |
| 103 | 33 KV LINE |
| 104 | Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13). |
| 105 | (B) Lattice Tower /Size of pit |
| 106 | 12.8/12.6 Mtr/ 1.5mx1.5m x2.10 m deep |
| 107 | (C)Stay set/Depth of pit |
| 108 | 8'x 3/4\\" -0.75x0.5x1.6 m |
| 109 | Safe carriage of PCC poles including loading / un-loading |
| 110 | a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole |
| 111 | Within 10 Kms. |
| 112 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site |
| 113 | Within 10 Kms. |
| 114 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.@ (4.61/KM *20) |
| 115 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. |
| 116 | Within 10 Kms. |
| 117 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof. @(5.57/KM *20) |
| 118 | Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. |
| 119 | Within 10 Kms. |
| 120 | Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. The cost muffing and grouting will be paid extra. |
| 121 | Lattice Structure |
| 122 | Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire |
| 123 | 8\\"x3/4\\" with 7/8 SWG stay wire |
| 124 | Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. |
| 125 | Supplying and laying of randum rubble stone boulder having weight not less than 20 kgs. |
| 126 | Fixing and assembly of disc.point channel pair with pilot plates top hampers & clamps on erected single pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates, |
| 127 | 33 KV line |
| 128 | 11 KV line |
| 129 | Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 Nos. disc.& 1set of H/W) on terminal point including fixing of hardware and strips. |
| 130 | Fixing of 33kv pin insulator with pins. |
| 131 | Fixing of 11 KV pin insulator with pins. |
| 132 | Fixing of PG clamp of Dog /Racoon Conductor |
| 133 | Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. |
| 134 | (A) IN URBAN AREA |
| 135 | ACSR DOG |
| 136 | Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. |
| 137 | (B) IN RURAL AREA |
| 138 | G.I.Earth wire 6 SWG |
| 139 | Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom) |
| 140 | Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder: |
| 141 | Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil: |
| 142 | Where drilling is required |
| 143 | Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates. |
| 144 | (B) IN RURAL AREA |
| 145 | PCC Poles 9 Mtr. Long |
| 146 | Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide) |
| 147 | On new surface |
| 148 | Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint) |
| 149 | On new works with two coats. |
| 150 | 11 KV INTERCONNECTION |
| 151 | Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line. |
| 152 | Excavation of pit in Hard soil (15% extra shall be payable for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13). |
| 153 | (A) Height of poles/R.S.Joist/M.S. Rail Size of pit |
| 154 | 9 Mtr/ 1.2mx0.6mx1.50 m deep |
| 155 | (C)Stay set/Depth of pit |
| 156 | 6'x 5/8\\" -0.75x0.5x1.35 m |
| 157 | Safe carriage of PCC poles including loading / un-loading |
| 158 | c) 9 Mtr.long 200 Kg. PCC pole |
| 159 | within 10 Kms.- |
| 160 | Above 10 Km. & upto 30 Km. add for each Km. or part thereof |
| 161 | Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site |
| 162 | Within 10 Kms. |
| 163 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof. (4.61*10) |
| 164 | Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. |
| 165 | Within 10 Kms. |
| 166 | Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.(5.57*10) |
| 167 | Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. |
| 168 | (B) IN RURAL AREA |
| 169 | PCC Poles 9 Mtr. Long (400 Kg) |
| 170 | Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. |
| 171 | PCC Poles 9 Mtr. Long(200 Kg.) |
| 172 | Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire |
| 173 | 6\\"x5/8\\" with 7/10 SWG stay wire |
| 174 | Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1 Nos. disc & 1 set of H/W ) on terminal point including fixing of hardware and strips. |
| 175 | Fixing of 33 KV pin insulator with pins. |
| 176 | Fixing of 11 KV pin insulator with pins. |
| 177 | Fixing of PG clamp of Dog /Racoon Conductor |
| 178 | Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. |
| 179 | (A) IN URBAN AREA |
| 180 | ACSR RABBIT |
| 181 | Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. |
| 182 | (B) IN RURAL AREA |
| 183 | G.I.Earth wire 8 SWG |
| 184 | Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil: |
| 185 | Where drilling is required Please Enable Macros to View BoQ information |