| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CE (DGNP) MUMBAI Name of Work: CREATION OF HYDRAULIC AND PNEUMATIC REPAIR BAY (HPRB) & UPGRADATION AT ND MBI. Contract No: CA No: DDG & CE(MB)/TEMP-04 of 2025-26 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e. DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit, if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES |
| 2 | LIST OF WORKS (Schedule A Part I to Part XVII) |
| 3 | Total amount of Sch 'A' Part-I (Building Works) brought forwarded from sl page No 34. |
| 4 | Total amount of Sch 'A' Part-II ( Excavation & Earth work & Site clearance) brought forwarded from sl page No 35 . |
| 5 | Total amount of Sch 'A' Part-III (Pile Foundation) brought forwarded from sl page No 36 . |
| 6 | Total amount of Sch 'A' Part-IV (Internal Water supply) brought forwarded from sl page No 38. |
| 7 | Total amount of Sch 'A' Part-V (Internal Electrification) brought forwarded from sl page No 42 . |
| 8 | Total amount of Sch 'A' Part-VI (External water supply) brought forwarded from sl page No 43. |
| 9 | Total amount of Sch 'A' Part-VII (External electrification) brought forwarded from sl page No 45 . |
| 10 | Total amount of Sch 'A' Part-VIII (Sewage Disposal) brought forwarded from sl page No 47. |
| 11 | Total amount of Sch 'A' part- IX (Area Drainage) brought forwarded from sl page No 48. |
| 12 | Total amount of Sch 'A' part- X (Fire fighting, Fire Alarm & Fire Detection) brought forwarded from sl page No 56 . |
| 13 | Total amount of Sch 'A' part- XI (Lift) brought forwarded from sl page No 57. |
| 14 | Total amount of Sch 'A' part- XII (Cooling appliances) brought forwarded from sl page No 58. |
| 15 | Total amount of Sch 'A' part- XIII (Lightning Protection) brought forwarded from sl page No 59. |
| 16 | Total amount of Sch 'A' part- XIV (Road & Path) brought forwarded from sl page No 62. |
| 17 | Total amount of Sch 'A' part- XV (Granite Flooring) brought forwarded from sl page No 63. |
| 18 | Total amount of Sch 'A' part- XVI (Miscellaneous (E/M) diversion of services) brought forwarded from sl page No 64. |
| 19 | Total amount of Sch 'A' part- XVII (Demolition & Dismantling) brought forwarded from sl page No 66 . |
| 20 | Subtotal |
| 21 | Sch 'A' Part- XVIII (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \\"Rs. 0.00\\" under Col.5 signifies this fact only. |
| 22 | INTERNAL WATER SUPPLY |
| 23 | Supply and Fixing Health Faucet 15mm dia with CP flush pipe, CP nozzel hook complete including CP flange complete all as specified. |
| 24 | Supply and Fixing C.P. Brass bib cock including wall fange, connections, screws, nut, bolts, cutting wall/floor and making good the same whatever required Complete all as specifed and as directed. |
| 25 | ELECTRIFICATION |
| 26 | Supply and fixing 20A single phase, industrial socket with MCB complete with connection testing and commissioning. |
| 27 | Supply and fixing 20A, three phase, industrial socket with MCB complete with connection testing and commissioning. |
| 28 | Supply and fixing of Surface industrial Batten Tube light - 20W LED. complete with all accessories internally prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size & highly efficient design with efficacy up to 120 lm/W.(Make: BCLSB 20W WH LED in Bajaj or latest equivalent in Crompton, Philips, Havells) |
| 29 | Supply and fixing of Highbay luminaire - 120W LED. complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size & highly efficient design with efficacy up to 120 lm/W.(Make: LHB II-120-CDL/60 in Crompton ot latest equivalent in Bajaj, Philips, Havells) |
| 30 | Supply and fixing WALL FAN ( 450MM sweep) complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size heavy duty, metal body oscillation type, single phase 1440 RPM built in regulator. |
| 31 | Supply and fixing 63A, Double pole, 240V, 10KA 'C' curve miniature circuit breaker MCB complete with connection testing and commissioning. |
| 32 | MCCB 4 Pole, 415 V, thermal adjustable type, 125 Amps with breaking capacity 36 KA |
| 33 | Flame proof switch socket & plug combined in LM6 cable termination box in LM6 25A, 415V, 4P+ earth |
| 34 | LED luminaire 300mmX 300 mm, 12 watt 220V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor wire of suitable size design with efficacy 120 Im/W (Make: LHEBAEP7IZ1W012 in Havells or latest equivalent in Crompton, Bajaj, Philips) |
| 35 | LED luminaire surface industrial batten 40 Watt with high efficiency, complete with driver, holders and LED lamp suitable for roof ceiling including Connecting up with driver three core flexible copper conductor wire of suitable size design with efficacy 120 Im/W. (Make: LHEXAPP7IN1W040 in Havells or latest equivalent in Crompton, Bajaj, Philips) |
| 36 | LED new luminaire industrial 40 Watt weather proof with high efficiency. complete with driver, holders and LED lamp suitable for roof ceiling including Connecting up with driver three core flexible copper conductor wire of suitable size design with efficacy 120 Im/W.(Make: LCTLSNE-36-FO-CDL in Cropmton or latest equivalent in Bajaj, Philips, Havells) |
| 37 | Flame proof wall fan 450 mm sweep, Heavy duty complete with all accessories including connecting up with three core flexible copper conductor wire of Suitable size. |
| 38 | AC single phase, exhaust fan (300mm Sweep). steel body with blades, heavy duty, frame, louvers including cutting hole in wall of proper size & making good as directed complete in all respect. |
| 39 | 06 way SPN MCB DB 240 V, with 200 Amps rated bus Bars double door on Surface / recess complete. |
| 40 | PILE FOUNDATION |
| 41 | TMT CRS bars 10mm dia and over cut to length bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips |
| 42 | Boring 600mm dia pile to any depth in any type of soil/starta/soft weather rock by any type of approved methode all as specified and directed including mobilisation and demotition of pile equipment and making good approaches to the site. |
| 43 | Boring for bored cast-in-situ pile 600mm dia through hard rock starta by any suitable method duly supported by drilling fluids or casing pipes including removal of excavated materials outside MD land |
| 44 | Non destructive integrity test on 600mm dia piles all as per IS-14893-2001 or ASTM std and all as specified and directed including bringing on site all equipment required and removal from site after testing is done |
| 45 | Initial load testing (vertical load testing) on 600mm dia as per IS2911 (Part-IV) - 1985 and all equipment required and removal from site after testing is done |
| 46 | Lateral load testing on 600mm dia as per IS2911 (Part-IV) - 1985 and all as specified and directed including bringing on site all equipment required and removal from site after testing is done. |
| 47 | Pull out testing on 600mm dia as per IS2911 (Part-IV)-1985 (Part-I Sec 2) and all as specified and directed including bringing on site all equipmeny required and removal from site after testing is done. |
| 48 | Routine load testing (static load testing) on 600mm dia as per IS2911(Part-IV) - 1985 (Part-I sec 2) and all as specified and directed including bringing on site all equipment required and removal from site after testing is done. |
| 49 | Providing 6mm thick MS plate fabrication Fe-410-0(Gde E-250) quality A with necessary shore cutter edge of (6+6) mm thick MS plate two layers with stiffeners and drains the same to a depth of rock touch level for piles and applying one coat of red oxide metal peimer all as specified & directed by GE Note- The rate shall be deemed to include cost for cutting and removal of MS liner at cut off level of pile, MS liner shall be measured and paid from sutt off level to hard rock level or till the liner is actually provided which ever is less. |
| 50 | EOT CRANE |
| 51 | Design,fabricate,supply,installation,test and commissioning of 20Ton Main Hook capacity and 5Ton auxillary hook capacity dougle girder EOT (Electrical operated over head Travelling) crane with a span of 15 mtrs and long travel 45 mtrs including VVVF AC drivers for LT,CT,Hoist speed,pendents push button,copper DSL,power cable for panel to DSLand suitable MCCBSand panel complete all as specified and as described below:-Type of capacity:Double girder type pendent operated 20Ton (safe working load) with 5 ton auxiliary hook double lifting hook.Span :15Mtr,Lifting ht:-11MtrsLong Travel: 37MtrsNote:-Quated rate includes the following:-(i) After completing crane tank work third party insepction (TPI) shall be carried out.(ii) Independent testing of rail, fish plate, rivets bolts, base plate & all the accessories of crane rail including rail stopper shall be carried out. |
| 52 | LIGHTNING PROTECTION |
| 53 | Supply and fix Horizontal roof conductor and down conductor of size 25 x 3.15 mm Aluminum strip fixed to walls/ columns/ projections roof by means of hylam sheet/porcelain insulator/PCC blocks spaced at 1 Mtr interval ans making grooves in hylem sheet to hold seat aluminum strip complete all as specified and directed. |
| 54 | Earthing complete with galunized steel (earth electrode 60cm x 60cm x 60mm thick, buried direcly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less’ than 1.5 meters below normal ground level, connected to galvanized earth lead strip 32 x 6mm thick by means of bolts, nuts check- nuts and washers of galvanizes iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completionNote : The GI strip shall be fixed to GL plate by bolts, nuts washers and electrical arc welding upto a length of 100mm on either side of strip and Gl strip exceeding 7.5 Mtrs will be measured and paid separately |
| 55 | AIR CONDITIONING |
| 56 | Supplying, Installation, testing and commissioning of following nominal capacity Air Cooled 100% Inverter based Variable refrigerant flow / volume Scroll/ Rotary modular type air-conditioning system. The units shall be suitable for operation on 415 V, 50 Hz AC Supply. The units shall have cooling and heating type, low noise condenser fans, auto address setting, auto check function for connection error and complete with indoor and outdoor units with individual controller and with fittings etc. as per quantity given below including full charging of R-410A refrigerant gas i/c powder coating of all metalic encloser. The fan static pressure of the outdoor unit shall be more then 75 Pa to avoid hot air recirculation. Supply Installation, testing & commissioning of Outdoor UnitThe IEER shall be 6.5 minimum. Further for enhanced savings COP at 50% load at 35 Deg C ambient in cooling mode at 27 Deg C/ 19 Deg C DBT/ WBT of each refrigerant circuit system mentioned below shall be 6.50 min. The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 10 deg C with respect to load for better comfort and energy efficiency. The condensing coils shall be coated with special anti corrosion coating at site for additional protection. |
| 57 | 16 HP Heat Pump Type (Cooling) Nominal Capacity in Single / Two or more modules including interconnection kit & MS Stands |
| 58 | Supply Installation, testing & commissioning of Indoor units address setting and capacity as mentioned below. multispeed motor, coil section with DX coil, outer cabinet, drain pan, drain water lift-up mechanism insulation, pipe connections, fresh air intake etc. of various capacities as per specifications and drawings. All indoor Units should have force shut option port or adaptor to connect with fire alarm adaptor, so that the unit automatically stops in case or fire, if requiredCassette Type Unit ( Multi Flow Type) |
| 59 | 1.28 TR / 600 CFM approximate. |
| 60 | 2.0 TR / 830 CFM approximate. |
| 61 | Cassette Type Unit ( Multi Flow Type) 1.6 TR / 530 CFM approximate |
| 62 | Supply Instalaltion, testing & commissioning of Y-joint set. |
| 63 | Supply Instalaltion, testing & commissioning of self diagnostic type remote controllers . |
| 64 | Cordless/ Corded Type |
| 65 | Supply Instalaltion, testing & commissioning of Intelligent central controller system suitable for 31 indoor units to operate, monitor, on/off, temperature setting etc. |
| 66 | Supply Installation, testing & commissioning of Header Set having liquid / gas connection 6branches type suitable for 4 IDUs. The IDU side shall be with flares. |
| 67 | Refrigerant PipingSupply& Fixing of Interconnecting copper refrigerant pipe work of following sizes with insulation ( class O) 25 mm / 19 mm thick duly insulated with Close Cell XLPE with Star baond cloth between indoor and outdoor units as per specifications. All piping inside the rooms shall be properly supported on MS angles and all external piping shall run in MS angle |
| 68 | 6.4 mm O.D. Pipe Size with insulation of 19 mm thick |
| 69 | 9.5 mm O.D. Pipe Size with insulation of 19 mm thick |
| 70 | 12.7 mm O.D. Pipe Size with insulation of 19 mm thick |
| 71 | 15.9 mm O.D. Pipe Size with insulation of 19 mm thick |
| 72 | 19.1 mm O.D. Pipe Size with insulation of 25 mm thick |
| 73 | 22.2 mm O.D. Pipe Size with insulation of 25 mm thick |
| 74 | 28.6 mm O.D. Pipe Size with insulation of 25 mm thick |
| 75 | 34.9 mm O.D. Pipe Size with insulation of 25 mm thick |
| 76 | 41.3 mm O.D. Pipe Size with insulation of 25 mm thick |
| 77 | Supply and fixing of UPVC drain water piping complete with fittings, support as per specification and insulated with 19 mm thick insulated with Class O XLPE insulation. |
| 78 | 25 mm dia |
| 79 | 32 mm dia |
| 80 | 50 mm dia |
| 81 | MOTOR CONTROL CENTRE |
| 82 | For Total 82 HP Unit |
| 83 | Supply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board of 31 MVA fault capacity at 415 V complete with 4 strip, 400 A capacity Aluminium Bus - Bar Electrolytic grade, cable alley, switchgears of following capacity & as per specifications. |
| 84 | INCOMER |
| 85 | 01 No. - 200 A FP MCCB Microprocesser Baased Electrical Drawout protection relays type with overload,short ckt.,earth fault protection release & under voltage protection, selector switch, 96mm ammeter & 96mm Voltmeter with selector switches, phase indication light with protection fuse,on / off / trip indicating light with Protection Fuse. MCCB shall be of 50 KA (Icu = Ics). |
| 86 | i) For Outdoor VRV Unit |
| 87 | 4 No. - 40 A TPN MCCB |
| 88 | 1 No. - 63 A TPN MCCB |
| 89 | Controls & interlocking accessories as required. LOT |
| 90 | POWER & CONTROL CABLINGSupply, laying, testing and commissioning of power and control cabling, as per Standard specification including end termination as required.Power / Control Cabling ( PVC insulated and PVC sheathed, armoured, Copper Conductor of 1.1 KV grade on existing cable trays). |
| 91 | 4C x 6 Sq mm |
| 92 | 4C x 10 Sq mm |
| 93 | 2C x 1.5 Sq mm |
| 94 | 3C x 2.5 Sq mm |
| 95 | Providing & fixing of weather-Proof Isolators consisting of 40A, 300 mA ELCB for each Outdoor unit for Each refrigerant ckt. |
| 96 | Providing & fixing of weather-Proof Isolators consisting of 63A, 300 mA ELCB for each Outdoor unit for Each refrigerant ckt. |
| 97 | MISCELLANEOUS (E/M) DIVERSON OF SERVICES |
| 98 | Disconnecting/cutting and removing the following HT cables of sizes upto 3 core X 400 sqmm from power supply and keeping in safe custody and handed over to user all as directed. |
| 99 | Disconnecting/cutting and removing the following LT cables of sizes 3.5 core X 400 sqmm/ 300 sqmm/ 240 sqmm/ 185 sqmm from power supply and keeping in safe custody and handed over to user all as directed. |
| 100 | Supply and lay pipe DI, flanged of class K-9, 150 mm dia including fittings 6 mm thick rubber gaskate and GI nut and bolts. |
| 101 | Supply and fix sluice valve flange of clss 1.6 PN with latest IS, 150 mm dia including nut and bolts. |
| 102 | Taking down steel / GI tubbing and connection, including cleaning and handing over to user including making good the distrubed area and matched with surrounding area all as directed |
| 103 | Supply and fix straight through cable jointing kit for 6.6/11 KV grade cable for termination heat shrink type joint complete with jointing material and accessories for 3 core XLPE armoured AL conductor cable of size 400 sqmm |
| 104 | EXTERNAL WATER SUPPLY |
| 105 | Supply and install Mono block Centrifugal pump set Confirming to IS- 12469 : 1988 With Cl Casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 volts, 3 phase, AC 50 Hz power supply having at 70 Mtr head, (5 HP/7.5WHP Approximate) discharge, |
| 106 | Slipply and install, testing of factory fabricated cubical type compartment, hinged door with locking arrangement at front arld fixed doors at back indoor type, floor mounted LT motor cohtrol panel 3 phase, 4 wire 415V, AC 50Hz with 2mm thick CRCA sheet steel, totally enclosed dust and Vermin proof with aldminum bus bar of rating 1.5 times the rated capacity of incomer, insulated with colour sleeves in cluding suitable rated analogue volt meter, ammeter with cast resin CTs, selector switch arid one set of RYB LED indication lamps for incoming and and ON/OFF indication and Start/stop push button, starters, powder cởated Siemens grey colour shade including complete mounting channel at bottom and comprising the the followig switchgear. a) MCCB 4P 32A 35 KA-1No b) MCCB 4P 16A 35 KA-3Nos C) MCB DP 16A 6 KA-1 No dy DOL starter suitable for 15 HP 3 Phase 415V AC 50Hz squirrel cage motor - 2Nös (Note- All MCCBs shall be of thermal adjustable type) |
| 107 | Supply and fix XLPE armored LT UG cable 4 Core 16Sqmm with multistrand aluminum conductor. Including cable glands and lugs complete. |
| 108 | EXTERNAL ELECTRIFICATION |
| 109 | M&L of HT 11KV Dual voltage , 3 phase 50 Hz, indoor type, totally enclosed metal clad switchgear complete with Vacuum Circuit Breaker having rupturing capacity 350 MVA,overload and earth fault protection, ammeter, voltmeter and of rating upto 630 Amp. |
| 110 | One (1) Nos. 6.6KV/11KV 630 Amps. 350MVA, 26kA for 1sec. Electrically/ manually operated draw out type vacuum circuit breaker complete with trip free spring charged closing mechanism, necessary auxiliary relays, control switches, emergency hand trip devices and mechanical ON / OFF indicator etc. |
| 111 | One (1) Multifunction Meter showing all Electrical Paramater ie Volt, Ampere, kw, kVA, P.F., kWH etc. |
| 112 | One (1) digital type ammeter with 11kV Cast resin CTs for metering (50/25 /5-5A, CL- 1, 15VA) with ASS and 2 Amp SP MCB. |
| 113 | One (1) voltmeter (0-15KV) with VSS. |
| 114 | One (1) Set of phase indication lamps with 2Amp SP MCB for protection (Red, Yellow and Blue). |
| 115 | One (1) set of Red/ Green indicating lamp for close and open position. |
| 116 | One (1) No. amber indicating lamp for auto trip. |
| 117 | One (1) No. clear indicating lamp for trip circuit healthy. |
| 118 | One (1) blue indicating lamp for spring charged. |
| 119 | One (1) strip heater to prevent absorption of moisture. |
| 120 | One (1) set of 3 O/C + 1E/F (with High Set) Neumerical Relay with 3 Nos. 6.6KV/ 11kV Resin Cast CTs 50/25/5-5A, CL 10P10, 15VA. |
| 121 | Master Trip Relay. |
| 122 | Trip circuit supervision relay |
| 123 | One (1) No. Potential Transformer 6.6KV/11KV/√3/110/√3 100VA burden |
| 124 | One (1) set of 3Element 24V DC Aux. Relay with H/R flag for tripping of Transfomer Fault ie. OTI, WTI & Buchholz Tripping. |
| 125 | One (1) set of 3Element 24V DC Aux. Relay with H/R flag for Alarm of Transfomer Fault ie. OTI, WTI & Buchholz Alarm. |
| 126 | One (1) set of 8 Stage 24V DC Annunciator with builtin test/Accept/ Reset Push Button along with 24V DC Hooter. |
| 127 | Master Trip Relay. |
| 128 | 12 Window Annunciator |
| 129 | Auxiliary switch/relay, master trip, anti pumping relay Trip circuit supervision relay and other control relays etc. as per requirements. |
| 130 | Power Pack : |
| 131 | One (1) Set 230V A.C, / 24V DC, Battery Backup, Power Pack to operate atleast 5Nos. Operation without AC Supply. |
| 132 | Supplying ,Assembling , erecting, testing and commissioning of 630 KVA 6.6KV-11KV/0.433KV Dual voltage 3phase 50Hz, indoor type copper wound, ONAN type step down transformer complete with all modern fittings as given in the specifications including , lifting lugs, Roller type bi-directional wheels, suitable boxes on both the ends for cable entry & bus duct,winding temprature indication & alarm, earthing terminals, diagram and rating plat etc. as required. |
| 133 | The transformers shall be ONAN Type & capable of continuous operation of rated output under the operating conditions of voltage and frequency variations as per statutory limits governed by relevant Indian Standard and Indian Electricity Rules, 1956 / IEC with latest amendments in force. |
| 134 | Requirement: 6.6KV-11KV/433V Dual voltage ONAN type with ON LOAD Tap Changer(OLTC), Tapping range +5% to -7.5% in steps of 2.5% (HV side), neutral air cooled, double copper wound, core type suitable for packaged substation housed in a enclosure. |
| 135 | Voltage Ratio: No load voltage 11000/433volts within tolerance as stipulated in latest IS standard. |
| 136 | Insulating material shall be of proven design. The insulating materials shall be class “F” |
| 137 | Rating: The transformer shall have a continuous rating as specified at any of the specified tapping position and with the maximum temperature rise specified. |
| 138 | Temperature Rise: The maximum temperature rise at the specified maximum continuous output shall not exceed 40°C by thermometer of winding above ambient temperature of 50°C. |
| 139 | Type of Load: The transformer shall be suitable for carrying unbalanced load up to 90% load within temperature rise indicated in the Indian Standard specification. |
| 140 | Overloads: The transformers shall be suitable for carrying overload within temperature rise indicated in IS. |
| 141 | Connections: H.V. Delta and L.V Star connected with neutral brought out on the secondary side for connection to earth; Vector group DYn11 of IS:2026 |
| 142 | Each 6.6KV-11KV/433V Dual voltage Step down transformers shall be provided with the following fittings and accessories: Rating diagram and terminal marking plate for transformer |
| 143 | Lifting lugs for transformer |
| 144 | Bi-directional Rollers |
| 145 | Rating diagram and terminal marking plate for transformer |
| 146 | Earth terminals (2 Nos) for body earthing for transformers |
| 147 | Inspection door for access to terminal connections for transformers |
| 148 | Suitable cable termination arrangement for M.V. side with 3.5Cx 240/300sq. mm 11 K.V. XLPE Aluminum Conductor cable. and cable box terminations on H.V. Side, suitable for 3Cx 240/300sq. mm 11 K.V. XLPE Aluminum Conductor cable. |
| 149 | Necessary hardware, clamps, lugs etc. for terminations of H.V. Cables on HV side and cable termination on M.V. Side. |
| 150 | Winding temperature indicator with contacts for remote alarm and tripping. |
| 151 | Including first fill of transformer oil |
| 152 | SAFETY EQUIPMENTS |
| 153 | Supply & fixing of Carbon dioxide (CO2) type fire extinguisher with suitable base pipe & horn (conforming to IS 2876 with cylinders fully charged of capacity 9.0 Kgm). |
| 154 | Supply & fixing of Carbon dioxide (CO2) type fire extinguisher with suitable base pipe & horn (conforming to IS 2876 with cylinders fully charged of capacity 4.5 Kgm). |
| 155 | Supply & fixing of G.I buckets of followings capacity paint and written with white paint Fire and mounted on M.S. angle iron bracket of sizes 50 mm x 50 mm x 6 mm thick and 500 mm long including grouting in wall etc. as required including filling with dry sand 9 ltr capacity. |
| 156 | Supply of First aid box as approved by St. John Ambulance Brigade/Indian Red Cross Conforming to IS:2217 - 1963. |
| 157 | Supply & fixing of Shock treatment chart at least in three languages duly mounted on a wooden frame with glass as required. |
| 158 | Supply of Elastomeric mat 2 mm thick to withstand 1.1KV dielectric strength as per IS 15652/2006. |
| 159 | Main LT PANELSupplying of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and Indoor type floor mounted, free standing extendible type Main LT Panel compartmentalized design and fabricated out of 2 mm CRCA sheet steel complete with Aluminium Bus bars, Electrical interlocks as per the various status of all the equipments indicated on the drawings. Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Cables incomings / Outgoings from Top / Bottom as per drawings and as approved by Engineer incharge, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing attached. (Note- All MCCBs shall be thermal adjustable type) |
| 160 | Incomer 1 No. 1250 A, 415V, 50kA (Ics=Icu=Icw =50 KA for 1 second), 4 Pole, Electrical draw out type, Micro-processor based release (for over current, Earth fault and short circuit protections) A.C.B. with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. each feeder shall have following: |
| 161 | Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency / Harmonics etc. with 3 Nos. current transformers of 1250/5 ratio, 15 VA Class 1.0 metering. |
| 162 | 6 nos NO/NC contacts for remote opening & closing. |
| 163 | Red/Green/Amber ON/OFF/TRIP indicating lamps with 2A SP MCB backup protection. |
| 164 | 1 set of three phase indicating lamps along with 2A SP MCB backup protection. |
| 165 | Spring charge& DC supply healthy indicating lamp with 2A SP MCB backup protection. |
| 166 | Separate set of Class 5P10, 15VA CT of suitable capacity for protection/Capacitor Panel |
| 167 | 24 V DC Shunt trip coil. |
| 168 | Motor wound spring closing mechanism. |
| 169 | Control MCB, control terminals& wiring as required. |
| 170 | Restricted Earth fault relay with 3 Nos. current transformers of 1250/5 ratio, 15 VA Class 5P 10 |
| 171 | Undervoltage, Overvoltage & phase reversal relay for persisted voltage of 105-180% & 20-95% of rated voltage. |
| 172 | All outgoing feeders shall be provided with one set of three phase R,Y,B indicating lamps along with 2A SP MCB backup portection and 1 Set of ON/OFF/Trip indicating lamps . |
| 173 | Bus Bars: |
| 174 | BUS BAR 1500 Amp TPN Copper bus bar with heat shrinkable coloured insulated PVC sleeves having a current density of not less than 1.0 Amp sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid strip. |
| 175 | Outgoings : |
| 176 | All outgoing shall have Ics = 50 KA (As per SLD) |
| 177 | 2 Nos. TPN feeder having 400A TPN MCCB, ON /OFF indication with control MCB. |
| 178 | 2 Nos. TPN feeder having 160A TPN MCCB, ON /OFF indication with control MCB. |
| 179 | 3 Nos. TPN feeder having 125A TPN MCCB, ON /OFF indication with control MCB. |
| 180 | 2 Nos. TPN feeder having 100A TPN MCCB, ON /OFF indication with control MCB. |
| 181 | 4 Nos. TPN feeder having 63A TPN MCCB, ON /OFF indication with control MCB. |
| 182 | 1 Nos. TPN feeder having 400A TPN MCCB.(SPARE) |
| 183 | 1 Nos. TPN feeder having 160A TPN MCCB.(SPARE) |
| 184 | 1 Nos. TPN feeder having 125A TPN MCCB.(SPARE) |
| 185 | 1 Nos. TPN feeder having 63A TPN MCCB.(SPARE) |
| 186 | Other items such as |
| 187 | 1 Lot of control wiring |
| 188 | 1 Set of designation plates |
| 189 | MAIN LT PANEL Described as above. |
| 190 | APFC PANEL Supply, testing & commissioning of 175 KVAR at 415V capacitor panel INDOOR TYPE having 1 no. 400Amps TP Isolator as incomer. Incomer shall have 3 nos indicating lights with control MCB for incoming power, ON/OFF trip indication, 1 no. Multifunction meter showing V/A/PF parameters with matching cast resin CT's, 3 phase 12 steps automatic power factor correction relay. |
| 191 | BUS BAR: |
| 192 | BUS BAR 500 Amp TPN Copper bus bar with heat shrinkable coloured insulated PVC sleeves having a current density of not less than 1.0 Amp sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid strip. |
| 193 | OUTGOINGS: |
| 194 | 5 no. x 25 KVAR capacitor banks each having 25 KVAR (should offer net capacitance of 25 KVAR at 415V) section will have 80A TP MCCB with 1 no of 60amps TP capacitor duty contactor, 1 no. 25KVAR 7% harmonic block reactor with 200% linearity class H, Net 33.5 KVAR Heavy duty MPP type capacitor rated at 525V, 1 set lights ON/OFF, 1 set of ON/OFF push buttons, 1 no. CT operated ammeter 0-60amps. |
| 195 | 4 no. x 12.5 KVAR capacitor banks each having 12.5 KVAR (should offer net capacitance of 12.5 KVAR at 415V) section will have 40A TP MCCB with 1 no of 40amps TP capacitor duty contactor, 1 no. 12.5KVAR 7% harmonic block reactor with 200% linearity class H, Net 33.5 KVAR Heavy duty MPP type capacitor rated at 525V, 1 set lights ON/OFF, 1 set of ON/OFF push buttons, 1 no. CT operated ammeter 0-40amps. |
| 196 | Each capacitor bank shall be able to operate in either manual or auto mode individually through APCR relay and separately in auto mode. Actual capacitance value will be high at 525V and each capacitors should be derated to offer value given above at 415V. |
| 197 | 1 set of complete wiring |
| 198 | MACHINE PANEL-1 |
| 199 | Supplying, installation, testing & commissioning of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and Indoor type wall mounted power distribution boards/ Panels compartmentalized design and fabricated out of 2 mm CRCA sheet steel complete with Copper Bus bars, Electrical interlocks as per the various status of all the equipments indicated on the drawings. Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Cables incomings / Outgoings from Top / Bottom as per drawings and as approved by consultant / Engineer incharge, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing attached. |
| 200 | 1 No. TPN Incomer feeder having 100A 4P MCCB (35kA) & ON/OFF indications, 3 nos. phase indicating lamps to show the incoming power with control MCB,1 no. multifunction meter (showing all parameters) with selector switch with matching cast resin CTs. |
| 201 | Bus Bar |
| 202 | BUS BAR 125 Amp TPN Copper bus bar with heat shrinkable coloured insulated PVC sleeves having a current density of not less than 1.0 Amp sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid strip. |
| 203 | Outgoings:- All outgoing shall have Ics = 25 KA or 10KA (As per SLD) |
| 204 | 2 Nos. TPN feeder having 40A 4P MCB, ON indication with control MCB. |
| 205 | 7 Nos. TPN feeder having 32A 4P MCB, ON indication with control MCB. |
| 206 | 3 Nos. TPN feeder having 63A 4P MCB (SPARE). |
| 207 | 1 Nos. TPN feeder having 32A 4P MCB (SPARE). |
| 208 | Other items such as |
| 209 | 1 Lot of control wiring |
| 210 | 1 Set of designation plates |
| 211 | LIFT PANEL-1 |
| 212 | Supplying, installation, testing & commissioning of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and Indoor type wall mounted power distribution boards/ Panels compartmentalized design and fabricated out of 2 mm CRCA sheet steel complete with Copper Bus bars, Electrical interlocks as per the various status of all the equipments indicated on the drawings. Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Cables incomings / Outgoings from Top / Bottom as per drawings and as approved by consultant / Engineer incharge, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing attached. |
| 213 | 1 No. TPN Incomer feeder having 63A 4P MCCB (35kA) & ON/OFF indications, 3 nos. phase indicating lamps to show the incoming power with control MCB,1 no. multifunction meter (showing all parameters) with selector switch with matching cast resin CTs. |
| 214 | Bus Bar |
| 215 | BUS BAR 100 Amp TPN Copper bus bar with heat shrinkable coloured insulated PVC sleeves having a current density of not less than 1.0 Amp sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid strip. |
| 216 | Outgoings:- All outgoing shall have Ics = 25 KA or 16KA (As per SLD) |
| 217 | 1 Nos. TPN feeder having 63A 4P MCCB, ON indication with control MCB. |
| 218 | 1 Nos. SPN feeder having 32A DP MCB, ON indication with control MCB. |
| 219 | 1 Nos. TPN feeder having 63A 4P MCCB (SPARE). |
| 220 | 1 Nos. SPN feeder having 32A DP MCB (SPARE). |
| 221 | Other items such as |
| 222 | 1 Lot of control wiring |
| 223 | 1 Set of designation plates |
| 224 | MCC PANEL-1 |
| 225 | Supplying, installation, testing & commissioning of 415V, 3 Phase, 50 Hz., 4 wire system, sheet steel clad, dust and vermin proof cubical and Indoor type wall mounted power distribution boards/ Panels compartmentalized design and fabricated out of 2 mm CRCA sheet steel complete with Copper Bus bars, Electrical interlocks as per the various status of all the equipments indicated on the drawings. Providing & Fixing of base plate / channel, P/F the following Switchgears, complete with earth Bus bar throughout the length of the panel, terminal arrangement for Cables incomings / Outgoings from Top / Bottom as per drawings and as approved by consultant / Engineer incharge, The incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement, detachable gland plates, adequate size cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate etc. complete as required as per specifications and drawing attached. |
| 226 | 1 No. TPN Incomer feeder having 63A 4P MCCB (35kA) with ON/OFF indications, 3 nos. phase indicating lamps to show the incoming power with control MCB, 1 no. multifunction meter (showing all parameters) with selector switch with matching cast resin CTs. |
| 227 | Bus Bar |
| 228 | BUS BAR 100 Amp TPN Copper bus bar with heat shrinkable coloured insulated PVC sleeves having a current density of not less than 1.0 Amp sq.mm. and the neutral bus of 50% capacity interconnections between bus bars and breakers shall be through solid strip. |
| 229 | Outgoings:- All outgoing shall have Ics = 16 KA (As per SLD) |
| 230 | 2 Nos. 40A TPN feeder having 40A TP MPCB with ON/OFF indication & START/STOP push buttons with Ammeter & Ammeter selection switch with cast matching resin with 12A 4P contactor. |
| 231 | 2Nos. 40A TPN feeder having 40A TP MPCB with ON (SPARE). |
| 232 | Other items such as |
| 233 | 1 Lot of control wiring |
| 234 | 1 Set of designation plates |
| 235 | AREA DRAINAGE |
| 236 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : |
| 237 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 238 | Constructing brick masonry road gully chamber 45x45x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand ) with precast R.C.C. vertical grating complete as per standard design : |
| 239 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 240 | Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cementconcrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. completeFor pipes 100 to 250 mm diameter |
| 241 | Providing and executing 60 Cum percolation modular harvesting pit of polymer based modules (Honeycomb design on each plates) made up of 100% recycled polypropylene, capable of taking light vehicular movement up-to at-least 20 tonnes/sqm and load bearing strength of 20-25 tons. The pit shall be wrapped with geotextile fabric material to prevent soil insertion and effective insertion of surrounding water. The Geotextile material shall be UV resistant, conforming to ASTM 154/EN 12224, non-woven geotextiles having thickness of 400 GSM, made out of long fibres to hold the modules including cutting, sizing, heat welding and needle punched for high porosity and proper percolation complete as per entire satisfaction of Engineers- ncharge. Depth shall ( 30 meter) be as per actual site condition and invert level. The item is inclusive of FRP based filter with diameter of 650 mm and height 1000 mm having inlet and outlet of required size with SS 304 mesh. Flow rate of filter should be at-least 40-45 KL/hr. FRP based RWH filters should be GRIHA and SVAGRIHA certified with valid certification on date. The product should be registered under GRIHA Criterions 21 &18 & SVAGRIHA Criterions 9.PVC pipe 200mm Make-Bantair |
| 242 | FIRE FIGHTING |
| 243 | Fabricating, supplying, testing and commissioning of electrical control panel of cubicle construction, floor mounted type, fabricated out of 2mm thick crca sheet, compartmentallised and hinged lockable doors, dust and vermin proof, powder coated approved shade after 7 tank treatment process, cable alley interconnection, having switchgears and accessories mounting and internal wiring, earth terminals, numbering etc., complete in all respects, suitable for operation on 415V, 3 phase 50 Hz., AC supplywith enclosure protection class IP-42as required. |
| 244 | INCOMER |
| 245 | 630A, 50kA 4 Pole MCCB, Ics=100% Icu rating |
| 246 | Digital Voltmeter 0-500V with selector switch |
| 247 | Ammeter (0-800 A) with selector swtich & CTs etc. |
| 248 | LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps |
| 249 | Set of Copper Bus Bar 800Amps |
| 250 | OUTGOING. |
| 251 | Main fire pump |
| 252 | 250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
| 253 | Jockey pump |
| 254 | 125 A, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
| 255 | Booster pump |
| 256 | 125 A, 50KA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector swiitch for loical/remote, auto/manual/OFF operation-2 sets |
| 257 | Diesel Engine Control |
| 258 | Control for Diesel Engine comprising:- |
| 259 | Auto / Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons, start / stop in manual mode. |
| 260 | Indication lamp for High / Low Lub. Oil pressure, High Water Temp. and Engine ON indication. |
| 261 | Battery charger suitable for 12V / 24 V DC with boost and tickle selector switch, 0-30 V DC volt meter, 0-20A DC Ammeter. |
| 262 | All standard relays and acessories for automatic operation of diesel engine. |
| 263 | SYSTEM CONTROLLER |
| 264 | Designing, Supply, Installation, Testing and Commissioning of system controller to control operation of Main Electric Fire Pump, Diesel Pump in sequence as per specification consisting of relays, timets, sensors, annunciation window for fault indication, complete as per specification.Note - All cabling, earthing, GI strip and cable tray including all electrical related accessories included in electrical tender.MCCBs shall be provided with series contactors for control through BMS/Automation |
| 265 | Supplying and Earthing with GI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc, with charcoal/ coke and salt as required, Earth work and excavation in any type of earth. |
| 266 | Supplying and laying 25 mm x 5 mm. G.I. strip in 40 mm dia. G.I. Pipe from earth electrode, including connection with GI nut, bolt, spring, washer excavation and re-filling etc as required. |
| 267 | Providing & fixing 25mm x 5mm G.I. strip on surface or in recess for connections etc. as required. |
| 268 | Supplying, fabricating and installing following size of perforated painted with powder coating M.S. cable trays,with perforation not more than 17.5%, in covenient section, joined with connectors, suspended from the ceiling with MS suspenders including bolts & nuts, painting suspenders etc. as required. |
| 269 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 270 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 271 | Laying and fixing of One number PVC Insulated and PVC Sheathed/XLPE power cable of 1.1 kV grade of size not exceeding 35 sqmm on surface as required. |
| 272 | Supplying of all materials and making terminations of 1.1 KV grade aluminium multicore cables of the following sizes. The work includes cable glanding using brass plated double compression glands, sizing the core leads, removing insulation, fixing suitable crimping type copper lugs/ thimbles by using hydraulic crimping tools with correct size of the dies, shaping the leads and neatly connecting the same to the equipment terminals. |
| 273 | 3.5 Core 120 sq. mm. Armoured Aluminium cable. |
| 274 | 3.5 Core 35 sq. mm. Armoured Aluminium cable. |
| 275 | 3.5 Core 16 sq. mm. Armoured Aluminium cable. |
| 276 | Control Cabling (PVC insulated and PVC sheathed, armoured, Copper Conductor of 1.1 KV grade on existing cable trays)5C x 1.5 Sq. mm |
| 277 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete asrequired. |
| 278 | Providing and fixing C.I. double acting air valves of approved quality with bolts, nuts, rubber insertions etc. complete ( The tail pieces, tapers etc. if reqd. will be paid separately) 50 mm dia. |
| 279 | Providing, installation, testing and commissioning of non-return valve (wafer type spring loaded dual platePN -1.6 rating) of following sizes confirming to IS:5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 280 | 250 mm dia |
| 281 | Supplying, fixing, testing and commissioning of butterfly valve (hand lever/gear operated) of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 282 | 250mm dia |
| 283 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to soundcontinuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : |
| 284 | 150mm dia |
| 285 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 286 | Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S. cylindrical body, internal discharge tube, discharge nozzle, suspension bracket, conforming to IS 15683, finished externally with red enamel paint and fixed to wall with brackets complete with internal charges. |
| 287 | Capacity 4.5 kg |
| 288 | Capacity 6 Kg. |
| 289 | Providing and fixing mechanical foam type Trolley Mounted Fire Extinguisher of bearing to IS:10568/IS13385/IS13386 with dis |
| 290 | Capacity 45 Lit. |
| 291 | Providing and fixing Carbon Dioxide Type Trolley Mounted Fire Extinguisher of as per IS: 2878 with discharge time of 10 to 20 sec/15 to 36sec/20 to 60sec respectively. |
| 292 | 22.5 Kg. CO2 Fire Extinguisher |
| 293 | Providing and fixing angle iron (40 mm x 40 mm x 5 mm) MS door frame 900x2100 door capable of accommodating fire hose reel, landing valve, hose pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. |
| 294 | Providing and fixing of TAC approved 1.6mm thick M.S. fire hose cabinet (750x600x250mm) made out of 16 gauge M.S. sheet capable of accommodating landing valve, hose pipes, fittings & accessories. The box shall have a front glass door with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) - for external and roof hydrant. |
| 295 | Providing and fixing of Fire Axe |
| 296 | Supply, installation testing & commissioning 100mm dia brass Foot Valve lift type as per specifications to the satisfaction of Project-in-charge |
| 297 | Supply & laying of cabling for fire detection and alarm system with 2 core annealed tinned copper conductor PVC sheathed, flexible, 2x1.5 sqmm armoured cable complete in all respect as specified or indicated including testing on completion. |
| 298 | Supply, installation,testing & commissioning of repeater panel with 320 character/touch screen LCD display with inbuilt, reset, acknowledge and silence switches complete as required. |
| 299 | Supply installation, Testing and commissioning of single unit flame type detectors(Triple Ir infrated Flame detectors) complete all as specified and ditected by Engineer -in - charge. |
| 300 | DEMOLITION & DISMANTLING |
| 301 | Demolition/ Taking down DB's MCB (SP/DP & TPN) etc by disconnecting electric connections and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 302 | Demolition/ Taking down old PVC tank of capacity upto 7500 ltrs and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 303 | Demolition/ Taking down Gate valve/ stop clock 40 mm to 100 mm by disconnecting water supply and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 304 | Demolition/ Taking down carefully old cable upto 50 sqmm to 300 sqmm 3.5 core etc by disconnection from panel board/TPN/DB etc and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 305 | Demolition/ Taking down carefully LT panel board by disconnecting cable including remove panel board, MCCB, Bus bar and other connected items etc and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 306 | Demolition/ Taking down fire hydrant landing valve type A (single headed outlet) of 63 mm dia and put in store for keeping in safe custody for taking credit all as directed by Engr-in-charge. |
| 307 | Dismantling and taking down carefully and handed over to user within Naval Dockyard Mumbai including transportation, labour etc hand operated crane of 2 ton capacity single girder with all accessories. |
| 308 | Subtotal Total in Figures 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail