| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / heavy class PVC conduit having wall thickness minimum 2 mm, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required..Make:- Legrand (Myrius)/ Schneider(Livia)/Anchor Roma (Plus) |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required Make:- finolex/Anchar/ Finolex |
| 4 | 2x2.5 Sq. mm. |
| 5 | 2x4.0 Sq. mm. |
| 6 | 2x6.0 Sq. mm. |
| 7 | 2x10.0 Sq. mm. |
| 8 | Wiring for circuit / sub-main with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.4 Sq.mm. (4X4+2X4)HRFRLS/PVC insulated single core copper conductor cable for earthing as required.Make:-finolex/Anchar/Finolex |
| 9 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit having wall thickness 2.0mm as required |
| 11 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 12 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVCconduit as required. Make: polycab/ KEI/ Anchor. |
| 13 | 3x2.5 Sq. mm. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 15 | 3 pin 5/6 Amps module - Modular GI box with Modular base & cover plate |
| 16 | Makes:- Anchor (Roma plus) /Panasonic. |
| 17 | Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 18 | 6 Pin 15/16 Amps. module - Modular GI box with Modular base & cover plate |
| 19 | Makes:- Anchor (Roma plus) /Panasonic. |
| 20 | Supplying and fixing Computer board comprising 3 nos 5 amp modular switches & Sockets , G.I box 2 module for jack box and G.I Box 12 module for 5 amp switchs and 5 amp sockets comprising frame and cover plate for each 2 module metal box and 12 module metal box , one no computer jack (RJ-45) with shutter including connections etc as required. |
| 21 | Modular G.I box for 12 mudule |
| 22 | Makes:- Anchor (Roma plus) |
| 23 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 24 | PVC conduit 25mm. |
| 25 | Makes:- BEC Plast/Anchor. |
| 26 | Supplying and drawing LAN cable CAT 6, solid copper conductor protected with PVC sheath in the existing surface / recessed, steel / PVC conduit as required |
| 27 | 1 Pair. |
| 28 | Makes:- Molex/Belden/Syslimax/Corning/DLINK |
| 29 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 amps modular socket outlets and 2 nos 5/6 amps modular switches, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 30 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 31 | Supplying and fixing Ding Dong bell suitable for single phase, 230 volts, complete as required. |
| 32 | Makes:- Anchor. |
| 33 | Providing and errection of LED 45 watt Street light luminaries, powder coated pressure die-cast aluminium SMDLED Street light with heat resistant toughened glass including connections, testing and commisioning etc. as required.Make:Jquar/Panasonic/ Wipro |
| 34 | Street Light LED-45 watt. |
| 35 | Supplying & fixing following type of Surface mounted luminaires Aluminium Batten Tubes, white power coated CRCA housing diffusser to avoid glaire,it should be compatible with specification i.e. Power Factor > 0.9, Harmonic Distortion < 20% and efficacy > 100 Lumens per watt, CRI rating> 70 suitable for input voltage: AC 220-240 V, 50 Hz, complete with all accessories, connections, testing and commissioning etc. as required. |
| 36 | LED Aluminium Batten Light 22 W (Make Bajaj) |
| 37 | Providing and Fixing of IP20 LED fixture of 12 watt +/- 1 W LED Surface Mounted Downlighter Square Shape with minimum system lumen efficacy of 100 lm/W with Polycarbonate housing,pressure die cast heat sink and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 . The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K with CRI of minimum 80.The Input voltage range shall be 150V to 270V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 38 | LED Surface mounting Square downlighter 12 watt Makes:- Panasonic |
| 39 | Supplying and fixing Surface mounting following size LED solution suitable for surface application with the use of the latest technology 24 watt (2400 lumens 6500 K and it should be compatible with specifications i.e. power factor > 0.9, harmonic distortion<10% and efficacy > 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. including 5 year warrenty as required . Make:- Bajaj/Panasonic/Wipro. |
| 40 | LED Panel Light 24 Watt EOS Surface. (1'x1). |
| 41 | Providing and Fixing of 1200 mm X 300 mm LED fixture 36 W +/- 1W Surface mounted fixture with HET Plastic diffuser with CRCA Powder Coated housing having minimum system lumen efficacy 100lm/W with P.F.>0.95 with THD<10%. The LED with Useful life of 50000 Hrs at L70. The LEDs used in the luminaire shall have CCT of 5700 K with CRI of minimum 80. The Input voltage range shall be 150V to 270V , 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 42 | LED Panel 1'x4' 36 watt Makes:-Wipro |
| 43 | Providing and fixing of IP65 Bulkhead led fixture 10 W +/- 1 W Wall Mounted with minimum system lumen efficacy of 100 lm/W with Pressure Die Cast Aluminum housing, Polycarbonate Opal Diffuser and P.F.>0.95 with THD<10% ,CRI 80.The LED shall be tested with LM80-08 standard with Useful life of 50000 Hrs at L70 .The LEDs used in the luminaire shall have CCT of ANSI Bin 5700 K only with CRI of minimum 80.The Input voltage range shall be 140V to 280V, 50/60 HZ complete with all accessories, including connections, testing and commissioning etc.as required complete in all respects. |
| 44 | LED Bulk Head Light 10W Makes:- Wipro |
| 45 | Supplying and fixing bakelite batten/angle holder including connections etc. as required:- |
| 46 | Supplying and fixing LED retrofit lamp suitable for B-22 holder base fittings with polycarbonate diffuser and aluminium heat sink as required complete in all respects. |
| 47 | 9 Watt LED, B-22 |
| 48 | Supplying & fixing following type of Surface mounted luminaires, white power coated CRCA housing diffusser to avoid glaire,it should be compatible with specification i.e. Power Factor > 0.9, Harmonic Distortion < 20% and efficacy > 100 Lumens per watt, CRI rating> 70 suitable for input voltage: AC 220-240 V, 50 Hz, complete with all accessories, connections, testing and commissioning etc. as required. |
| 49 | LED Batten Light 10 W (Mirror Light). |
| 50 | Supplying and fixing of fancy wall bracket suitable for input voltage:AC 220-240V,50/60Hz, complete with all accessories ,lamp holder, LED lamp including making connectons,testing etc. as required: of Approved Make:- Jaquar/Philips/Bajaj |
| 51 | Fancy Wall light fixture Metal body,suitable for 7 W retrofit LED lamp |
| 52 | Providing, Installation, testing and commissioning of wall fan of following size by means of suitable rag-bolt/ nuts, connections, testing and commissioning etc. as required complete in all respects to the best satisfaction of Engineer-in-charge .Make:- Usha/Bajaj/Crompton |
| 53 | Wall Fan 400 mm sweep |
| 54 | Providing, Installation, testing and commissioning of ceiling fan ( 1 star rating), including wiring 1the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required: |
| 55 | Ceiling Fan 1200 mm sweep |
| 56 | Providing and installation exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: |
| 57 | Exhaust Fan, Light duty, (Domestic) |
| 58 | Make:- Usha. |
| 59 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 60 | 20 A SPN, industrial type socket |
| 61 | Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:- |
| 62 | 25 Liter capacity water heater (Cat-A) |
| 63 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 64 | 16 way, Double door Make:- Anchor Uno. |
| 65 | Supplying and fixing 6 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make:- Anchor Uno. |
| 66 | Single pole |
| 67 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 68 | 40 AmpsMake:- Anchor Uno. |
| 69 | 63 AmpsMake:- Anchor Uno. |
| 70 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 71 | 40 Amps Makes:-Anchor Uno/Legrand/Schneider |
| 72 | 63 Amps Makes:-Anchor Uno/Legrand/Schneider |
| 73 | Supply,Favirication,installation,testing,commissioning and electrically connected Factory (CPRI approved) made,LT panel Board of approved size as 600x600x225mm (LxHxD) as recommended by IS & CPRI norms,indoor type,Floor Mounted 1100 Volt,made out off CRCA sheet 1.6mm thick with IP-54 protection ,for 415 volts, (Certified not older than 2 Years) for volts 3 phase,4 wire AC supply,complete all as specified including provision of following accessary/components housed in it -: (1) 200 Amps rated copper bus bar with colour code TPN mounted on epoxy insulator : 01 set (set for 04 bus bar. (ii) LED indication lamp (set of 04 bus bar) (iii) Internal wiring with 1100 volt grade unsheahed PVC insuladed copper conductor of suitable size, cable as per colour coding or suitable size of bus bar for all connections with suitable lugs as required as per specified.(v) Earthing teminals and cable glands.(vi) Danger notice plate for LT with conventional skull and riveted/pasted to the panel door.Confirming to IS:-64139 and tested/approved from CPRI Lab Make:- Hark Power Control/ Power system control |
| 74 | The Panel shall include the following Switchgear & accessories; as per the Make of L & T,Schneider, C&S etc. |
| 75 | Incoming-: |
| 76 | (1) MCCB 200- Amps,4P 36KA Adjustable Thermal and fixed Magnetic MCCB (Spreader Links Inc.) |
| 77 | Supply,Favirication,installation,testing,commissioning and electrically connected Factory (CPRI approved) made,LT panel Board of approved size as 600x600x225mm (LxHxD) as recommended by IS & CPRI norms,indoor type,Floor Mounted 1100 Volt,made out off CRCA sheet 1.6mm thick with IP-54 protection ,for 415 volts, (Certified not older than 2 Years) for volts 3 phase,4 wire AC supply,complete all as specified including provision of following accessary/components housed in it -: (1) 100 Amps rated copper bus bar with colour code TPN mounted on epoxy insulator : 01 set (set for 04 bus bar. (ii) LED indication lamp (set of 04 bus bar) (iii) Internal wiring with 1100 volt grade unsheahed PVC insuladed copper conductor of suitable size, cable as per colour coding or suitable size of bus bar for all connections with suitable lugs as required as per specified.(v) Earthing teminals and cable glands.(vi) Danger notice plate for LT with conventional skull and riveted/pasted to the panel door. |
| 78 | The Panel shall include the following Switchgear & accessories; as per the Make of L & T,Schneider, C&S etc. |
| 79 | Incoming-: |
| 80 | (1) MCCB 63- Amps,3P +N.L 10KA Adjustable Thermal and fixed Magnetic MCCB (Spreader Links Inc.) |
| 81 | Earthing with G.I. earth plate 600 mmx600 mmx 6 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt ) as required. |
| 82 | Supplying and laying 6 SWG G.I. wire at 0.50 mtr. below ground level for earth electrode conductor, including soldering etc. as required. |
| 83 | Less the credit for dismentaled material:-Rs.(-3554)/- Please Enable Macros to View BoQ information |