| 1 | Estimate for renovation of Electrical Wiring at Library portion of Education Department, BT College Campus under University of Kalyani. |
| 2 | Supplying and fixing 415V, 160 A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T) (Ref:PWD Page No-D-3,Item No:4(a))(For Main Panel) |
| 3 | Supplying and fixing 415V 160 A TPN On load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etcn.(L&T)(Ref:PWD Page No-D-2 Item No-3(a)) |
| 4 | Supplying and fixing 415V, 100 A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T) (Ref:PWD Page No-D-3,Item No:4(a))(One for GF Panel O/G other for FF Panel I/C) |
| 5 | Supply & fixing 415V 200 A capacity MS (16 SWG) Busbar Chamber having dimension of (500x150mm) to be fixed on iron frame on wall consisting of 4 nos copper bars of size (4x40x5mm). The same BBC should have a separate cubicle at one end consisting 3 nos 200 A capacity porcelain cut out fuse unit & one nutral bar to receive the service cable including connecting the cut out fuse units with the BBC by S/F PVC insulated copper wire duly socketed at both ends incl. earthing attachment & painting .[Ref:PWD Page No-D-13,Item 19(b)](For Main Panel) |
| 6 | Supply & fixing 415V 125 A capacity MS (16 SWG) Busbar Chamber having dimension of (500x150 mm) to be fixed on iron frame on wall consisting of 4 nos copper bars of size (4 x 15x3 mm). The same BBC should have a separate cubicle at one end consisting 3 nos 125 A capacity porcelain cut out fuse unit & one nutral bar to receive the service cable including connecting the cut out fuse units with the BBC by S/F PVC insulated copper wire duly socketed at both ends incl. earthing attachment & painting .(PWD Page No-D-13,Item 19(b)(For First Floor) |
| 7 | Supply & fixing double door 6 way Enclosure (8GB31572RC) Vertical TPNMCBDB (Siemens) with IP 42/43 protection SS enclosure on angle iron frame on wall & mending good the damages to original finish incl. Interconnection with suitable size of copper wire & nuetral link & provision of earthing attachment comprising of the following accessories (All make Siemens):a)125 A four pole MCCB of breaking capacity 25KA/ 35KA with adjustable thermal & fixed magnetic setting --- 01 nob) 63 A TP MCB /100 A TP MCB ----02 Nosc) 40 DP MCB --- 01 Nosc)6-32A SP MCB ---10 nos[Ref:PWD SOR :-Page No-D-8(Item No-10)Page No-D-6,(Item No-7)Page No-D-11(Item No-15)](For First Floor) |
| 8 | Supply & fixing 6 way double door horizontal TPN MCB DB with SS enclosure ( Cat no.8GB32202RC06 )(Siemns) concealed in wall after cutting the wall & mending good the damages to original finish with earthing attachment comprising with the following. a) 100 A Four Pole MCB isolator (Siemens) b) 6 to 32 A range SP MCB. (Siemens) ---18 Nos. [Ref:PWD SOR :-Page No-D-6(Item No-7)Page No-D-5,(Item No-6)Page No-D-10(Item No-14) ] (For Ground Floor) |
| 9 | Supply & fixing 4 way double door horizontal TPN MCB DB with SS enclosure ( Cat no.8GB32202RC04 )(Siemns) concealed in wall after cutting the wall & mending good the damages to original finish with earthing attachment comprising with the following. a) 63 A Four Pole MCB isolator (Siemens) b) 6 to 32 A range SP MCB. (Siemens) ---12 Nos. [Ref:PWD SOR :-Page No-D-6(Item No-7)Page No-D-5,(Item No-6)Page No-D-10(Item No-14) ] |
| 10 | Supply & fixing SPN MCB DB (2+8) Way (Make Siemens) with S.S. Enclosure (8GB32102RC10) and IP-42/43 protection concealed in wall after cutting wall & mending good the damages & earthing attachment comprising with the following: a) 40 A DP isolator - 1 No. (Siemens) b) 6 to 32 A range SP MCB - 8 Nos.(Siemens)[Ref:PWD SOR Page No-D-5(Item No-6)Page No-D-6,(Item No-7)Page No-D-10(Item No-13)] |
| 11 | Supply & Fixing (2+12) way SPN MCBDB (Make Siemens) with S.S. Enclosure (8GB32102RC14) and IP-42/43 protection Concealed in wall & mending good the damages to original finish incl. Interconnection with suitable copper wire & nuetral link incl. earthing attachment comprising with the following:a) 40A DP MCB isolator --- 1 nob) 6 to 32 A SP MCB -- 12 nosPWD SOR :-Page No-D-5(Item No-6)Page No-D-6,(Item No-7)Page No-D-10(Item No-13)( For First Floor) |
| 12 | Supplying and fixing 20 mm size PVC Rigid Conduit 'FR' [Precision Make]on wall, ceiling with saddles and other accessories as required and mending good damages to building works.[Ref:PWD Page No-E-16,Item No-7(a)]NB - Should be use Precision make shaddle & the saddles should be fixed at 325mm interval . |
| 13 | Supplying and fixing 25 mm size PVC Rigid Conduit 'FR' [Precision Make]on wall, ceiling with saddles and other accessories as required and mending good damages to building works.[Ref:PWD SOR Page No-E-16,Item No-7(b) ]NB - Should be use Precision make shaddle & the saddles should be fixed at 325mm interval . |
| 14 | Cutting Channel of sizes (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge as per office supply pipe sample 19 mm bore, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG including supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles for the following sizes Pipes - **a)19 mm dia 3 mm thick polythene pipe without earth continuity wire(For circuit drawing & Point wiring / as per requirement of Job / as per instruction of EIC) NB - All rubbishes should be removed from work site & also Tee & Elbow should not be use in the conceal pipe,continuity wire.[Ref:PWD SOR Page No : E - 3 Item No : 6(a)] |
| 15 | Cutting Channel of sizes (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge as per office supply pipe sample 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG including supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles for the following sizes Pipes - **a) 25 mm dia 3 mm thick polythene pipe without earth continuity wire(For circuit drawing & Point wiring / as per requirement of Job / as per instruction of EIC) [E-3/6a & 7a)]NB - All rubbishes should be removed from work site & also Tee & Elbow should not be use in the conceal pipe,continuity wire.[Ref:PWD SOR Page No : E - 3 Item No : 7(a)] |
| 16 | Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaidpolythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages A) 4×16 sq mm + 2× 10 sq mm as ECC ( VTPNDB to TPNDB)**NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No:g1 ) |
| 17 | Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaidpolythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages B)2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC(TPNDB to SPNDB)**NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(z ) |
| 18 | Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaidpolythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages (v)2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC ( for AC)**NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(v ) |
| 19 | Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaidpolythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages t)2× 2.5 sqmm + 1× 1.5 sqmm.(For Computer Board )**NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(s ) |
| 20 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.i) For 2.5 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(i)] |
| 21 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.i) For 4 sq mm Copper Wire.[Ref:PWD SOR Page No : F - 5 Item No : 9(ii)] |
| 22 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., includingsupplying sockets, tapes.i) For 6 sq mm Copper Wire.[Ref:PWD SOR Page No : F - 5 Item No : 9(iii)] |
| 23 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.i) For 10 sq mm Copper Wire.[Ref:PWD SOR Page No : F - 5 Item No : 9(iv)] |
| 24 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 16 sq mm Copper Wire.[Ref:PWD SOR Page No : F - 5 Item No : 9(v)] |
| 25 | Laying of cable above 3½ core 35 sqmm and upto 3½ core 50 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting.(for 3.5 Core 50 Sq mm Cable connecting GF Main Panel to FF BBC)[(Ref:PWD SOR Page No-F-1 Item No:2(c)] |
| 26 | Laying of cable upto 3.5 core 25 sqmm on wall/surface incl. S & FMS saddles with earthing attachment in 10 SWG GI (Hot Dip)Wire, making holes etc. as necy. mending good damages andpainting.[(Ref:PWD SOR Page No-F-1 Item No:2(b)] |
| 27 | Laying of cable as above 35 sqmm to 95 sqmm at an average depth of 100 mm infloor/pavement/wall etc in after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl.removing the rubbish[(Ref:PWD SOR Page No-F-3 Item No:5(ii)] |
| 28 | Supplying and fixing 3½ Core 50 sqmm compression type gland (Make:Dowels) complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables a (Ref:PWD SOR Page No-F-4 Item No:7(d) ] |
| 29 | Finishing the end of 3½ Core 50 sqmm XLPE unarmoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials.(PWD SOR Page No-F-5)Item No:8(b) [xvii] |
| 30 | Supplying and fixing 3½ Core 25 sqmm compression type gland (Make:Dowels) complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables a (Ref:PWD SOR Page No-F-4 Item No:7(d) ] |
| 31 | Finishing the end of 3½ Core 25 sqmm XLPE unarmoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials.(PWD SOR Page No-F-5)Item No:8(b) [xiv] |
| 32 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire, partly in 20 mm/25 mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19 mm bore, 3 mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded ''FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make:Gloster / Finolex (Gold) or as equivalent approved by EIC] , partly for ECC, to light/fan/call bell points with Piano Key type switch (Anchor Make) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar on Double Chair incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages tooriginal finish [only PVC Rigid Conduit on ceiling and remaining portion concealed]Avg Run- 5 Mtr(Ref:PWD SOR Page No-E-15 Item No:5) |
| 33 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire, partly in 20 mm/ 25 mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19 mm bore, 3 mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded ''FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make: Gloster / Finolex (Gold) or as equivalent approved by EIC] , partly for ECC, to light/fan/call bell points with Piano Key type switch (Anchor Make) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar on Double Chair incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages tooriginal finish [only PVC Rigid Conduit on ceiling and remaining portion concealed]Avg Run- 6 Mtr(Ref:PWD SOR Page No-E-15 Item No:6) |
| 34 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) singlecore stranded 'FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make:Gloster / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire,partly in 20 mm/25 mm size PVC rigid conduit 'FR'(Precision make) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythenepipe [for vertical run embedded in wall], with 1x22/0.3 (1.5sqmm) single core stranded ''FR'/'FRLSH'' PVC insulated & unsheathed copper wire [ Make:Gloster / Finolex (Gold) or as equivalent approved by EIC]for ECC, to light/fan/call bell points with Piano Key type switch (Anchor Make) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar bar on Double Chair incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finishAverage Run 6 Meter [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed](Ref:PWD SOR Page No-E-16 Item No:6) |
| 35 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) singlecore stranded 'FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make:Gloster / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire,partly in 20 mm/25 mm size PVC rigid conduit 'FR'(Precision make) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythenepipe [for vertical run embedded in wall], with 1x22/0.3 (1.5sqmm) single core stranded ''FR'/'FRLSH'' PVC insulated & unsheathed copper wire [ Make:Gloster / Finolex (Gold) or as equivalent approved by EIC]for ECC, to light/fan/call bell points with Piano Key type switch (Anchor Make) fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar bar on Double Chair incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finishAverage Run 8 Meter [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed](Ref:PWD SOR Page No-E-16 Item No:6) |
| 36 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make: Gloster / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire in 20 mm/ 25 mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copperwire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box andmending good the damages to original finisha) *On board(Ref.PWD SOR Page No-E-15 Item No:4(a) |
| 37 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (FR'/'FRLSH' PVC insulated & unsheathed copper wire [ Make: Gloster / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes**NB- Should be maintain colour combination of Circuit Wire in 20 mm/ 25 mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copperwire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box andmending good the damages to original finisha) b) Average Run 1.5 mtr(Ref.PWD SOR Page No-E-15 Item No:4(a) |
| 38 | Supply & Fixing 240 V, 20 A plug socket (Anchor make or Brand approved by EIC), without plug top and switch, on 100 mm x 100 mm x 65 mm sheet metal switch board with bakelite/perspex top cover by screws after making housing for combined plug switch by cutting bakelite/perspex top cover and making necy. connections with PVC wire and earth continuity wire etc. [For AC Power Socket](Ref: PWD SOR Page No-E-5,Item No-15(b) |
| 39 | Supply & Fixing 240 V, 25 A, Modular type starter (Make North West or equivalent Brand approved by EIC) with 25A Modular switch type DP MCB (C Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.(Ref:PWD SOR Page No-E-19 Item no.17) |
| 40 | Supply & Fixing 240 V, 4 nos. 6A, plug socket with separate 4nos. 6 A Piano key type switch, indicator & 16A kit-kat flush type fuse (Anchor Make or Equivalent Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.[ Charging Board](Ref.PWD SOR Page No-E-7,Item No-23 ) |
| 41 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator (All Anchor Make) & 20A switch type SP MCB (Make Siemens or equivalent Brand approved by EIC) on sheet metal switch board embedded in wall incl. S &F 240x200x65mm MS (16SWG) switch board andbakelite/perspex top cover of 3 mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. [Computer Board](Ref:PWD SOR Page No-E-7,Item No-26 ) |
| 42 | Supply & Fixing Socket type fan regulator (Step type) (Anchor Make or Equivalent Brand approved by EIC) on existing sheet metal switch board with bakelite/ perspex top cover by screw incl. making necy. connections etc.(Ref:PWD SOR Page No-E-6,Item No-18(b) |
| 43 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.[Ref: PWD SOR Page No-C-3 Item no. 21(a)] |
| 44 | Lowering and refixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. making necessary disconnection and connection as required.[Ref: PWD SOR Page No-C-3 Item no. 22] |
| 45 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts &washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20PVC insulated flexible copper wire 0.5 mt. length.[Ref: PWD SOR Page No-C-4 Item no. 29] |
| 46 | Fixing only starters (for Split AC Machine control) Concealed in wall after cutting the wall and making housing for the starter and mending good the damages to original finish .Direct online starter for 2 Ton ac Machine.[Ref: PWD SOR Page No-C-1 Item no. 7(a)] |
| 47 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works and also removing rubbises from work site .100 mm x 100 mm x 65 mm (Ref:PWD SOR Page No-E-4,Item No-11( a) |
| 48 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works and also removing rubbises from work site . 150 mm x 100 mm x 65 mm(Ref:PWD SOR Page No-E-4,Item No-11( b) |
| 49 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works and also removing rubbises from work site . 175 mm x 100 mm x 65 mm (Ref:PWD SOR Page No-E-4,Item No-11( c) |
| 50 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works and also removing rubbises from work site . 200 mm x 150 mm x 65 mm(Ref:PWD SOR Page No-E-4,Item No-11( d) |
| 51 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works and also removing rubbises from work site .240 mm X 200 mm x 65 mm(Ref:PWD SOR Page No-E-4,Item No-11( e) |
| 52 | Supply & Fixing bakelite / perspex top cover on existingInspection board by Brass screws100 mm x 100 mm x 65 mm (Ref:PWD SOR Page No-E-5,Item No-13( a) |
| 53 | Supply & Fixing bakelite / perspex top cover on existingInspection board by Brass screws 150 mm x 100 mm x 65 mm(Ref:PWD SOR Page No-E-5,Item No-13( b) |
| 54 | Supply & Fixing bakelite / perspex top cover on existingInspection board by Brass screws 175 mm x 100 mm x 65 mm (Ref:PWD SOR Page No-E-5,Item No-13( c) |
| 55 | Supply & Fixing bakelite / perspex top cover on existingInspection board by Brass screws 200 mm x 150 mm x 65 mm(Ref:PWD SOR Page No-E-5,Item No-13 ( d ) |
| 56 | Supply & Fixing bakelite / perspex top cover on existingInspection board by Brass screws 240 mm X 200 mm x 65 mm(Ref:PWD SOR Page No-E-5,Item No-12( e) |
| 57 | Fixing only fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports incl. S&F EI conduit, ball socket/socket type ceiling plate /Supports also U type GI clamp made with 31 mmx 3 mm GI flat and suitable size fastner (as per sample to be provided)and connecting the length of PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10mt. length.(Ref:PWD SOR Page No-C-2,Item No-15) |
| 58 | Earthing the installation by 50 mm dia. G.I. Pipe (ISI-M) of 3.64 mtr. Long driven to an depth of 3.65 mtr. Below the ground level including S/F 1X4 SWG. G.I. Earth wire (4 mtr. Long) with nuts bolts & washers.(Ref:PWD SOR Page No-G-1,Item No-2(a)) |
| 59 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.(Ref:PWD SOR Page No-G-2,Item No-4(a)) |
| 60 | Connecting the equipments body to earth busbar including S &F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.(Ref:PWD SOR Page No-G-3,Item No-5(d) |
| 61 | Supplying, fitting and fixing boiling water proof ply conforming to IS: 710-1977bonded with phenol formaldehyde synthetic resin conforming to IS: 848-1974 ofapproved make and brand fitted and fixed as per design as per approval anddirection of Engineer-in-Charge.[Supply and Fixing 12 mm thick water and vermin proof super quality ply wood of size (6 ft x 5 ft) to be fixed on wall with suitable long screws fasterner / on iron structure etc after painting the near side with Japan paint.](PWD civil page no 173 item no 2 Rs. 1709.00/ sq mt) |
| 62 | Supply and delivery of 3.5 core 50 sqmm 1.1 KV grade aluminium XLPE Sheathed Armoured Aluminium Power Cable. (Make- Gloster / as equivalent approved by EIC )( Ref:Non Schedule Item ) |
| 63 | Supply and delivery of 3.5 core 25 sqmm 1.1 KV grade aluminium XLPE Sheathed Armoured Aluminium Power Cable. (Make- Gloster / as equivalent approved by EIC )( Ref:Non Schedule Item ) |
| 64 | Supply of 4' 20W Single LED Aluminium T8 tube (LTT8) with in built driver and efficacy of 100 lm/W. type tube light fitting on High efficiency integrated LED Batten to create a sustainable lighting environment with surface/suspended mounting, complete with all acessaries directly on ceiling with HW round block & suitable size of MS fastener (Make: Crompton -Batten (ECO-I)-IGP161LT8-16 1 x T8, Tube-CRYSTA LTT8-20-865-2/ Equivalent product Approved By EIC)( Ref:Non Schedule Item ) |
| 65 | Supply of recessed mounted LED 36 W 4000K dimension (mm) l |b | h =600 | 600 |60 low glare diffuser light on ceilling complete set.[Make:K-Lite Cat No:-KL-2281 or quivalent make approve by EIC )( Ref:Non Schedule Item ) |
| 66 | Supply and delivery of 1200 mm sweep, single phase, 240 Volt, 50 Hz Ac Ceiling Fan including down rod, top and buttom canopy, capacitor etc. (Make- Usha Striker PWD ISI 1 Star(Safety wire & S1 Capacitor)/Orient New Breeze or equivalent approved by EIC)( Ref:Non Schedule Items ) |
| 67 | Supply and delivery of 4 Metal Blade 450 mm sweep, single phase, 240 Volt, 85 W 50 Hz Ac Wall Fan including all accessories . (Make- EPC or equivalent Approve by EIC)( Ref:Non Schedule Item ) |
| 68 | Supply of control panel suitable for 2 Ton AC Machine,Relay Range 13 - 22 A comprising of DOL starter to be Concealed on wall incl making connection & necy earthing attachment. (Make -L&T MU-2P Single Phase Starters-CS90319KODO /Equivalent product Approved by EIC) |
| 69 | 18% GST |
| 70 | 1% CESS Please Enable Macros to View BoQ information |