| 1 | Distribution of wiring in 1.5 sq.mm single core standard ‘FR’ PVC insulated & unsheathed single core stranded copper wire ( Make – Polycab / Havells / KEI ) with ECC in 19 mm bore,3 mm thick PVC rigid pipe complete with all accessories embedded in wall to light/fan/call bell/ Ex.fan points with Modular type switch 6A (Cabtree/Standard /HPL make) fixed on sheet metal ( 16 SWG ) modular board with modular top cover flushed in wall including mending good damages to original finish. ( Average run 6 mtr.) |
| 2 | Distribution of wiring in 1.5 sq.mm single core strandad ‘FR’ PVC insulated & unsheathed single core strandad copper wire (Make – Polycab / Havells / KEI) in 19 mm bore ,3 mm thick PVC rigid pipe with all accessories embedded in wall to 240 V 5A 3 pin plug point incl.S&F 240V 6 A 3 pin modular type plug socket & switch ( Cabtree / Standard / HPL make) incl.S&F earth continuity wire,fixed on sheet metal MS module board with top cover flushed in wall incl.mending good damages to original finish. |
| 3 | a) On Board. |
| 4 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire |
| 5 | Supply & drawing of sub-main line wiring with 2 x 2.5 sq.mm PVC single core copper multistrand wire of make – Mescab / Polycab / Havells in PVC rigid pipe embedded in wall system with earth continuity wire for distribution of circuit & plug points for computer with power points. |
| 6 | Supply & drawing of sub - main line wiring with 2 x 4 sq.mm PVC single core copper multistrand wire of make - Polycab / Havells / KEI in PVC rigid pipe embedded in wall system with earth continuity wire for distribution of circuit. |
| 7 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 mtrs.long and 1x4 SWG GI ( hot dip ) wire ( 4 mt.long ) 13 mm dia x 80 mm long GI bolts, double washers including supply and fixing of 15 mm GI pipe protection ( 1 mtr.long ) to be fitted with bitumen partly under the ground level driven to an average depth of 3.65 mtr.below the ground level and restoring surface duly rammed as below. |
| 8 | Treatment of soil by using salt & charcoal or coke |
| 9 | Supply and fixing 415 V, 32 Amps. ICDP main switch with sheet steel enclosure on flat iron/ angle iron frame on wall with nuts bolts etc. in complete of make Havells / Standard /Legrand for outdoor light controlling. |
| 10 | Supply and fixing 415 V, 63 Amps. ICDP main switch with sheet steel enclosure on flat iron/ angle iron frame on wall with nuts bolts etc. in complete of make Havells / Standard /Legrand. |
| 11 | Supply & fixing SPN MCB, 2+4 way distribution board with IP 42/43 protection incl, inter connection with suitable size of copper wire and 40A Isolator & neutral link & provision of earthing arrangement along with 6-32A SP MCB in outgoing. Havells / Standard make. |
| 12 | Supply and drawing of PVC / XLPE Alumunium unarmoured cable 1.1 KV grade at work site of make Havells / Polycab / KEI. Size 10 sq.mm x 2 core |
| 13 | Laying of cable in underground trench 460 mm wide x 760 mm average depth,with brick protection on the top of the cable with 8 ( eight ) Nos.brick per meter,including filling the space between the brick & cable and also the trench with shifted soil,levelling up and restore the surface duly rammed |
| 14 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint |
| 15 | Supply & laying of GI pipe medium gauge (ISI medium) protection with necessary fittings and jointing materials as required. 40 mm dia |
| 16 | Finishing the end of following XLPE/PVC armoured cable by crimping method incl.supplying and fixing solderless vsocket, tapes, anticorrosive paste & jointing materials.Size 10 sq.mm x 2 core |
| 17 | Supply & installation of AC exhaust fan of 300 mm sweep, 240 V AC Exhaust Fan with GI Louver heavey duty including all accessories of make Usha / Orient / Polar |
| 18 | Supply of mounting rail type LED fittings of Philips make fittings compete with all accessories, Cat. No. TMC 501 1 x T-LED 18W P 3241 along with LED Tube 22 W. |
| 19 | Supply & fixing of 22 W Surface Mounted Plus LED Downlighter in complete set |
| 20 | Supply, fixing, connection & testing of 1 HP Pump with Motor sets and suitable type stator in complete as per direction of EIC. |
| 21 | Supply, fixing, connection & testing of outdoor type Street light fittings of IP66, IK05 LED Integral type streetlight luminaire with system lumen > 11500 Max system wattage 90 W with pressure die cast aluminium housing, Luminaire should be operable with auto adjustable 140V-270V supply voltage with same driver and with 3 KVA Surge protection, LM 80 For LED Source & LM79 for Luminaire is mandatory, Confirming the lighting level as per B1 category road of IS 1944 with spacing [Make: Philips (Cat no. BRP 409 LED 115 CW SLC FG PSU GR V2 SPD)/Approved equivalent from Crompton/Wipro/Bajaj make] |
| 22 | Supplying fitting and fixing plaque made of Granite slabs ( single piece) of 15 mm to 18 mm thick with uniform texture and without decorative veins in facia etc fixing with using Cement slurry at back side of granite @4.4 kg/sq.m and white cement slurry for joint filling @1.8 kg/sq.m.including making lettering , sign marks etc as per direction in the granite slabs with fixed at brick wall (in 1:6) as directed including earth cutting , 75 mm thick sand filling , 75 mm thick Cement concrete (1:2:4) and plastering with 20 mm thick sand cement mortar (6:1) as specifed by the Department including wall putty , Acrylic primer & Super Protective 100% Acrylic Emulsion two coats including all incedential charges for labours, materials, machinaries & transportig charges complete in all respect as per direction of EIC. |
| 23 | Sub Total |
| 24 | Add GST @ 18% on Sub-Total Cost, i.e. |
| 25 | Add Labour Welfare Cess @ 1% on Total cost after GST, i.e. Please Enable Macros to View BoQ information |