| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division JPDCL Reasi Name of Work:- Supply, Installation, Testing and Commissioning for Creation of 200 KVA Sub Station along with HT Tap line for EV Charging Station of M/S BPCL at New Ganga Filling Station Jammu Road Katra under the jurisdiction of Electric Division JPDCL Reasi Contract No: e-NIT No. 47 of 2025-26 dt. 14.03.2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Erection of 11 KV Tapping Point |
| 4 | ST Pole 9 mtr ( ST 410 SP-33) |
| 5 | GI V cross-arm with top Bracket including clamp and GI Channel X-arm including clamps and braces |
| 6 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type |
| 7 | ACSR Weasel Conductor (30 Sq.mm) |
| 8 | 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 9 | 11kV Polymeric composite Disc Insulator with GI fitting 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm. |
| 10 | Galvinized Nuts and Bolts |
| 11 | Danger Plates with Clamps |
| 12 | Anti-Climbing Device with Clamps |
| 13 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25X3) mm. |
| 14 | Aluminium Paint |
| 15 | Cement bottoming 1:2:4 mix as per REC standards .5cum /pole |
| 16 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete. |
| 17 | Erection of 11 KV HT Line |
| 18 | ST Pole 9 mtr ST 410 SP33 |
| 19 | 50 mm² AB (HT) Cable (3x50 + 1x70 mm²) XLPE(11 kV, 3C +Earth) |
| 20 | Straight Through Joints for Cables |
| 21 | Cable Termination Kits (Indoor/Outdoor) |
| 22 | Creation of 200 kVA sub station |
| 23 | 11/0.433-0.200kV, 50Hz, Aluminium Wound Distribution Transformer of latest Energy Efficiency Levels (New 1.05.180 Part-I, Sch.4 as per latest spec) dap, amendment with externally fitted MCCB with cable box and 4x4 Mtrs. suitable cable of ratings. (Aluminium wound upto 200kVA, Copper wound for 250kVA or higher kVA ratings) |
| 24 | Gapless Surge Arrestor, 9 kV, 10 kA, LA with polymer housing, Stn. Type |
| 25 | 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 26 | 11kV Drop Out Fuse Set 3 Phase 200A |
| 27 | 185 mm2 (2ckt) Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type |
| 28 | 9 Mtr. Long Pole, ST-410 SP(3) |
| 29 | 11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 30 | GI Channel/Angle/Flat of sizes including clamps |
| 31 | Galvanized Nuts and Bolts. |
| 32 | Earthing of substation - Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of earthing pipe of 40 mm nominal bore & 4mm wall thickness, length 3.5 mtr long as per IS 239. GI Strip for neutral earthing of 25x3 mm 5 m for connection of transformer body. G.O Set & lightening arrestor as per IS 2629/85. GI nuts & bolts, refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 33 | 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 34 | Galvanised Stay Set with 50x6mm stay clamp, guy insulator(2nos.), anchor plate (200x200x6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter GI Stay Rod & 7/3.15 mm dia GI stranded wire complete. |
| 35 | Wedge Connectors/PG Clamps |
| 36 | Danger Plates with Clamps |
| 37 | GI Barbed Wire for Anti Climbing |
| 38 | LT Distribution Box for 200/250/400 kVA DTR with MCCB for incomer & SFU's for Outgoing Circuits |
| 39 | 11KV HT Metering with CT PT operated unit |
| 40 | Chain Link Mesh Fencing around the 11 KV S/Stn made out of wire mesh 1\\"x1\\" Square including fixing in cement1:2:4 including welding cutting etc. complete in all respect. |
| 41 | Cement bottoming 1:2:4 mix as per REC standards Scum/pole |
| 42 | Painting of Poles Red Oxide |
| 43 | Painting of Poles Aluminium Paint |
| 44 | Sundry items like Aluminium lugs, Jumpers, binding Tape |
| 45 | Galvanised Stay setwith 50x8mm stay clamp, Guy Insulator (2 Nos), Anchor Plate (200x200x6mm) nuts and Bolts, 2Nos Turn Buckles, 1.8 long, 16mm diameter solid GS Stay rod & 7/3.15mm dia GI Standard wire complete Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |