| 1 | M&L for point wiring complete with PVC insulated and unsheathed cable 1.5 sqmm (nominal area) ISI marked multi-stranded copper conductor single core including ISI marked 20mm dia 'medium grade' PVC conduit for point wiring in Surface conduit with pressed steel concealed Sunken boxes not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer complete including 1.5 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rule complete all as specified & directed. [ Make of cable - Finolex / Havell's / Anchor/KEI/ Polycab ] |
| 2 | One light/Fan/Exhaust fan point controlled by one switch |
| 3 | S&F switch piano, flush type, 5 amps single pole, one way |
| 4 | M&L in repair Sub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 1.50 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 1.50 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of PVC conduit drawn through rigid Surface concealed PVC conduit, heavey duty and connected to main board and making good disturbed surface complete all as specified and as directed. Make of conductor : Havells/polycab/KEI Note: Two runs each of 1.50 sqmm main cable and one RM of 1.50 sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose. |
| 5 | S&F in repair Recess mounting type fitting LED indoor luminaire powder coated, CRCA or powder coated aluminium panel 2' x 2' (Appx) system wattage 36 watt (cool white), minimum system lumen efficacy not less than 80 % , CRI not less than 80, colour temperature not less than 6000 K, power factor not less than 0.95, LED driver with constant output voltage and current at input voltage of 140volt to 285 volt AC, 50 HZ, Surge Protection>2 KV, IP protection IP 20, powder coated housing with ashthetic bottom frame, with excellent heat dissipation through high thermal conductivity, high efficiency transulence diffuser, suitable for any type of ceiling system including connection with PVC insulated copper conductor 3 core cable of 0.50 sqmm complete all as specified. |
| 6 | Supply and fix in repair of building security LED street light fitting 35 Watt 6500K pf >.90 efficency 100lm/W 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp fixing of wall,pole,building with impact and corrosion resistant including thermal management in multiple optics complete with IP 65 protection including suitable size bricket,clamps,fastner etc complete all as specified and as directed. |
| 7 | Supply and fixing in replacement LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified including taking down old. Make : Havells/Bajaj/C&S/Crompton |
| 8 | Supply and fixing in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified including taking down old.Make : Havells/Bajaj/C&S/Crompton |
| 9 | S & F street light bracket made out of 40/50 mm dia GI heavy grade tubing not less than 1.5 Mtr long bend to shape including pole clamps made out of 50 x 6 FI and nut bolts and washers all as specified and directed including taking down old. |
| 10 | Supply and fixing MCB Disribution 1 row 3 modules of polycarbonate themoplastic, IP 65 dust proof, jet water tight corrosion proof, halogen & silicon free, with high quality earth and neutral links, internally embedded gasket for led and enclosures made PUR with cable glands and other accessories with MCB 6 amps and required terminals, metric size knock transparent door & with cable enerty covered and suitable to accommodate any make of MCCB and tested as per IEC 60439-3 (Flame retardant self extinguishing of size 202x238x111 mm complete all as specified and directed including taking down old. Make : Hensel cat Ref No: KV 7103/legrand |
| 11 | Supply , laying and passing through pipes/poles cable wheather proof flat copper conductor twin core of size 2.5 sqmm for connection from junction box to pole with flexible conduit of apporipriate size if required at site all as directed by Engr-In -Charge at site including taking down old. ( Make of cable: Havells/polycab/finolex ) |
| 12 | Supply and fix in repairs 24 W Round LED surface lights fitting full glow panel, metal body, natural light 6500K, environmental friendly energy efficient, with driver, holder connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed by Engr-in-Charge. (CAT PART NO: Phiilips BOF5HW4QRT)/Crompton/Wipro |
| 13 | Supply and fix in repairs occupancy sensor with light sensor, 360 degree detection angle, energy saving motion detector, auto on & off ceiling mounted, 7 meter radius detection range complete all as specified and directed by Engr-in-Charge. (CAT PART NO: Schneider CSS54E_WE) |
| 14 | S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI / IEC 60439-2 approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016. The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel/Clipsal. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 63A TP 25KA Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. Six Nos Single Phase Sub-Meters. Output supply by MCB DP 32Amp 6 Nos. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Make- Hensel/siemens/Emitter/Schneider/ABB. |
| 15 | S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI / IEC 60439-2 approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016. The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel/Clipsal. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 125A TP 25KA Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. Eight Nos Single Phase Sub-Meters. Output supply by MCB DP 32Amp 8 Nos. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Make- Hensel/siemens/Emitter/Schneider/ABB. Please Enable Macros to View BoQ information |
| 16 | S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI / IEC 60439-2 approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016. The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel/Clipsal. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 125A TP 25KA Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. Eight Nos Single Phase Sub-Meters. Output supply by MCB DP 32Amp 8 Nos. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Make- Hensel/siemens/Emitter/Schneider/ABB. Please Enable Macros to View BoQ information |