| 1 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 metre deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in-Charge. |
| 2 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick using excavated soil complete all as specified and as directed. |
| 3 | Removing excavated soil n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed. |
| 4 | M & L for dry Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed.Note: Punned thickness (18 cm) shall be consider for measurement purpose |
| 5 | M&L laying well burnt old size bricks, sub class \\"B\\" bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified & directed by Engr-in-Charge. |
| 6 | Deployment of tools & manpower for Boring /drilling (Horizontal) manually / mechanically under existing road max 10 M in width) suitable for passing pipe of any description of dia 40 to 100 mm complete all as specified and directed by Engineer in Charge |
| 7 | M&L for 40 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable including taking down old cable complete all as specified and directed by Engr-in-Charge. |
| 8 | M&L for 50 mm bore mild steel galvanised water tubing, light grade with all fittings and fixed to walls or laid on floors / fixed to poles / or passing under road crossing, for protection of UG cable including taking down old cable complete all as specified and directed by Engr-in-Charge. |
| 9 | Material & Laying, jointing and testing in replacement of LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 3 core, complete all as specified laid in trenches / laid under floor or fixed naked with walls / on poles/ in ducts / in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. |
| 10 | All as per item No 09 above but LT under ground cable of size 10 Sqmm 4 core |
| 11 | All as per item No 09 above but LT under ground cable of size 16 Sqmm 3 core |
| 12 | All as per item No 09 above but LT under ground cable of size 16 Sqmm 4 core |
| 13 | All as per item No 09 above but LT under ground cable of size 25 Sqmm 4 core |
| 14 | Supply drawing, connecting and testing in replacement 3 core, 1.5 Sqmm PVC insulated and PVC round sheathed` copper conductor (flexible ) industrial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge. |
| 15 | Supply and install steel tubular swaged pole type 410 SP-31 (9 metre long) complete with MS base plate of size 300 x 300 x 6mm thick at bottom, welded at the centre with through hole of 14 mm dia at a height of 300 mm above the coping finial cap, painted with two coats of aluminium paint over a coat of red oxide primer with writing pole number including excavation up to required depth and PCC type C-2 1:3:6 (using 40mm graded) at bottom and PCC type B-1 1:2:4 (20mm graded) for mass filling and pole coping (60 x 60 x 30 cm) and rendering of coping with 05 mm thick in 1:4 cement mortar, including painting up to 1.5 metre above PCC coping in black and white strips 05 Nos each 30 cm high starting from bottom of pole & Marking number on pole with black paint, including taking down old pole complete all as specified and directed. |
| 16 | Dismantling and taking down old unservicable street light / flood light / Post top light fitting of any descreption and any capacity from street light poles any hieght and high mast light pole after disconnecteing of electrical connection complete all as specified and directed. |
| 17 | Supply and fix 35 W LED street light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 18 | Supply and fix 60 W LED street light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 19 | Supply and fix 70 W LED street light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 20 | Supply and fix 90 W LED street light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 21 | Supply and fix 70 W LED Flood light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 22 | Supply and fix 100 W LED Flood light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 23 | Supply and fix 120 W LED Flood light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 24 | Supply and fix 170 W LED Flood light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 25 | Supply and fix 210 W LED Flood light fitting with electronic driver set, having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover / IP lens, street light should have IP 66 protection, impact resistance of IK 07, system Lumen efficiency not less than 110 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70%, street light should have built in potted electronic LED driver with, lower THD, open circuit protection, over voltage protection, surge voltage protection, and provided with company LOGO engraved on housing of the street light complete all as specified and directed by Engr -in-Charge.Note :-The contractor shall take approval of technical specification of luminaries and driver from department before procurement. |
| 26 | Supply and fix 20 Watt LED Post Top lanterns fitting, housing made of Die-cast aluminium spigot for mounting LED driver and spun aluminium canopy, epoxy powder coated matt black finish after phosphocreatine treatment, high quality polycarbonate cover is used over LED module to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light white / warm white, Powered by electronic integral , isolated potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD, output short / open circuit protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65, system lumen efficiency not less than 100 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70% fixed in position complete all as specified & durected. |
| 27 | Supply and fix 40 Watt LED Post Top lanterns fitting, housing made of Die-cast aluminium spigot for mounting LED driver and spun aluminium canopy, epoxy powder coated matt black finish after phosphocreatine treatment, high quality polycarbonate cover is used over LED module to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light white / warm white, Powered by electronic integral , isolated potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD, output short / open circuit protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65, system lumen efficiency not less than 100 lumen per watt, power factor >0.95, THD<10% at Full load CRI> 70% fixed in position complete all as specified & durected. |
| 28 | Supply and fix in repair canopy headed junction box, of size 300 x 250 x 150 mm, suitable for fixing on LT Pole for street light control, fabricated with 2.00 mm thick MS sheet with cover, including S&F of 04 Nos aluminium bus bar of size 25 x 3 mm for phase and neutral, 01 nos 06 Amps MCB SP, mounting channel for control street light cable gland, aluminium lug, MS FIixing clamp -02 nos with nut bolt washer and painting with two coat of synthectic enamel paint over a coat of red oxide primer on external and internal surface complete all as specified and directed |
| 29 | S&F in replacement GI bracket for street light fittings fabricated with GI tubing 40mm dia 'light grade' 1.5m long and bending to angle of 120 degree including mild steel clamp of suitable size with two coat aluminium paint suitable for fixing on PCC/steel poles complete all as specified and directed. |
| 30 | Supply & fixing in replacement automatic street light timer pannel 12 KW/ 40 Amp switch using Infrared Sensor based for automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) alongwith suitable power contactors, Input (supply) MCB and output (load) MCBs support terminals should be enclosed in pole/wall mountable encloser made of rust proof, termite proof and FR graded SMC juncation box conforming to IP-54 degree of ingress three phase 8 KW lightening load capacity including mounting bracket cable glands openable doors with lock complete all as specified and directed by EIC. |
| 31 | S&F in replacement wheather proof pole mounting PVC junction box, base and door of junction box made out of SMC having outside dimention 333 x 233 x 120 mm, inside dimention 300 x 200 x 105 mm, single door front openable provided with hinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulator including M&L for MCB SP 10 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including embossing / painting of danger notice of size not less than 10 cm x 7.5 cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body Complete all as directed by Engr-in-Charge |
| 32 | Supply, fixing, connecting and testing MCCB 63 Amps 4 pole 25 KA 415 volts 50 Hz, thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as directed. |
| 33 | Supply, fixing, connecting and testing MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz adjustable thermal & adjustable magnetic release with spreader, including taking down old existing unserviceable MCCB complete all as directed |
| 34 | Supply, fixing, connecting and testing MCCB 125 Amp, 4 pole 25 KA, 415 volts 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed |
| 35 | Supply, fixing, connecting and testing MCCB 160 Amp, 4 pole, 25 KA, 415 volts 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed |
| 36 | Supply, fixing, connecting and testing MCCB 200 Amp, 4 pole, 36 KA, 415 volts 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed. |
| 37 | Supply, fixing, connecting and testing MCCB 250 Amp, 4 pole, 36 KA, 415 volts, 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed |
| 38 | Supply, fixing, connecting and testing MCCB 400 Amp, 4 pole, 36 KA, 415 volts, 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed |
| 39 | Supply, fixing, connecting and testing MCCB 630 Amp, 4 pole, 50KA, 415 volts, 50 Hz adjustable thermal & adjustable magnetic release with spreader including taking down old existing unserviceable MCCB complete all as directed |
| 40 | S&F in replacement on load change over switch open execution of capacity 400 Amps, 4 pole, 415 volt, 50 Hz fixed in any type of existing LT panel / Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed |
| 41 | S&F in replacement on load change over switch open execution of capacity 250 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as directed Please Enable Macros to View BoQ information |