| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER BAREILLY Name of Work: PROVN OF SPLIT AC IN BLDG NO P-201 PSM COY JCO MESS (STUDENTS) AT JLA UNDER GE WEST BAREILLY Contract No : CWE / BLY / GE(W) /89 OF 2025-26 Bidder Name : SCHEDULE A(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm, 3.5 core complete all as specified and directed. |
| 3 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/dence soil for laying of LT UG cables/base for Pole etc complete all as specified and directed. |
| 4 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard/ dense soil complete all as specified and directed. |
| 5 | Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 6 | M&L for sand cushioning laid in trenches for laying of LT UG cables complete all as specified and directed. |
| 7 | M&L for modular bricks common burnt clay building bricks, sub-class ‘B’ designation-75 for LT UG cable protection complete all as specified and directed. |
| 8 | S&F GI tubes light grade of dia 80 mm with all fitting and fixed complete for protection of LT UG Cables laid to walls or in floors or along with poles etc complete all as specified and directed. |
| 9 | S&F MCB single pole 6 to 32 Amp 240 Volt 'B' curve 10 KA complete all as specified and directed. |
| 10 | S&F MCCB triple pole 160 Amps 415 Volt curve 10 KA complete all as specified and directed. |
| 11 | S&F TPN DB -VTPN DB 8 way with provn of MCCB 160 Amps , 415 Volt, 3 Phase, 4 wire AC 50 Hz having aluminium Bas Bar phase and the neutral insulated with PVC sleeves, connected with appropriate size copper thimbles complete all as specified and directed. |
| 12 | M&L for earthing complete including taking out old unsv and replace with galvanised steel earth plate 600x600x 6mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate using 4 mm dia GI wire as earth wire electrode moulded and rivetted to earth plate at one end and connected to main switch/ control switches of buildings at another end, GI earth wire encased in and including 15 mm dia GI 'light grade' pipe from upper end of earth plate upto main switch board of building including 20 dia bore GI pipe 'light grade' as water pipe from earth chamber and including excavation and earth work, PCC 1:3:6 type C1 chamber and MS angle iron frame 40x40x3mm and RCC cover 40mm thick (1:2:4) type B1 using 20mm graded stone aggregate reinforced complete all as specified and directed. |
| 13 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 4 star rating and EER 3.2.of capacity of 2 TR capacity and testing on completion complete all as specified and directed. |
| 14 | S&F Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4.0 KVA complete all as specified and directed. |
| 15 | S&F in repairs sub-main wiring with 2 single core, 4 Sqmm PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper multi stranded conductor drawn in and including PVC conduits of 20mm size including drawing one run of PVC insulated, unsheathed, 1100 Volts grade, FRLS, copper conductor multi stranded,4 Sqmm size as continuous earth wire drawn through and connected to main switch/DB and testing on completion complete all as specified and directed. |
| 16 | S&F copper tubing of size 1/4\\" including cutting and brazing complete all as specified and directed. |
| 17 | S&F copper tubing of size 1/2\\" including cutting and brazing complete all as specified and directed. |
| 18 | S&F three core connection lead two single core, PVC insulated and sheathed Copper cable size 2.5 Sqmm including one earth wire of full guage complete all as specified and directed. |
| 19 | S&F Nitril vinyl insulation foam suitable for fixing with copper tube of size 3/8\\", 5/8\\" , 1/2\\" and 1/4\\" and packing with wide pvc tapes of black/white colour compete all as specified and directed. |
| 20 | S&F Wall/ floor mounting type iron stand for outdoor unit complete all as specified and directed. |
| 21 | S&F in repairs, miniature circuit breakers, type curve ‘B’ , 10 KA, SP, 6 to 32 Amps complete all as specified and directed. |
| 22 | S&F sheet metal enclouser with socket plug top and MCBs Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amps complete all as specified and directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |