| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER BAREILLY Name of Work: PROVN OF RING MAIN UNIT (RMU) AT SUB STATION NO 01 OF RTS AND DEPOT HEMPUR UNDER GE EAST BAREILLY Contract No : CWE / BLY / GE(E) /158 OF 2025-26 Bidder Name : SCHEDULE A(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply & Install testing and commisioning of 11 KV Ring Main unit (RMU) with one incoming and two outgoing with following specification :-Factory made and tested 11 KV RMU compact, metal-enclosed out foroor type rated for 11 KV system (50 Hz) compring of 01- Incoming - Vacum circuit breaker (VCB) unit.02 - Outgoing - Two Nos with load break switch (LBS) for feeders/Transformer connection.Single bus arrangement with earthing switch and provision for current transformers (CTs) and metering protection.* Rated Voltage - 11 KV (Phase to Phase) * Rated frequency 50 Hz. * Rated normal current - 630 A. * Rated short time with stand current (ICW) - 20 KA for 1 second.* Rated breaking current of VCB - as per IEC - 6227/-100. * RMU and its components shall comply with minimum.(a) Meal enclosed switch gear and controlger RMU assemblies IEC-62271-200.(b) IEC-60265-Load break switches/Disconnections earthing switchs.(c) IEC 60529-Enclosese protection (for type test and internal are test).(d) IEC-62271-100 for high voltage circuit breaker (VCB per formanced test) |
| 3 | * Main component vacum circuit breaker (Incoming) :-(i) Three pole VCB, rated for 11 KV, specified as 630 A.(ii) Rated breaking capacity 20 KA for 1 second.(iii) Mechnical/motorized operation with local manual oversize, padlockable isolating handle, position indicators (Open/Closed).(iv) Protection relay mounting provision load break switches (2 No outgoing) :-Three pole load break switch for 11 KV switch under load break as per IEC, motorized operation and manual operation on facility. Padlockable and mechnical nterlockes to prevent unsafe operation.Earthing switch - As per IEC requirments.SF6 insulated - eposxy insulated Design, wih PT, CTs metering compartment with transporent door, cable entries and gland plates with all necessary protection and control switches, fuses compact steel enxlosure, powder coated outdoor type IP-54 (or higher specified).Cotractor must provide - Drawing as per OEM with mounting locks and lifting provision.Earting - Dedicated external earthing terminal, internal eath bus bar 50 mm x 6 mm GI strip.Abient temp - 250 C to 400 CAltitude - upto 1000 m above sea level.Note :- All necessary test (Type test, routine test, factory acceptance test report must be submitted by contractor at his own cost with factory visit in the quoted rate of contractor. |
| 4 | Supply and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) earthed with aluminium conductor, 11000 volts grade cross secional area 95 Sqmm 3 core complete all as specified and directed. |
| 5 | Supply and laying cable jointing kit for 11 KV grade for outdoor termination end heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured AI conductor cable of size 50 to 95 Sq mm complete all as specified and directed. |
| 6 | M&L in replacement for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanized iron earth strip 32X6mm by means of bolts nuts check-nuts and washers of galvanized iron or steel as shown in electrical plate No 5 of MES schedule Part-I connecting to earthing test point and testing on completion with including 15mm bore light grade GI protection pipe, RCC 1:2:4 type B1 20mm thick cover reinforced with 6mm thick dia MS bars 3 Nos both ways with lifting hook made out of 6mm dia MS bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, earthing lead from earth plate to eqipment to point (up to 7.5M long) common salt and charcoal filling, necessary excavation and earth work complete all as specified and directed. |
| 7 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm galvanised iron strip complete all as specified and directed. |
| 8 | Excavation in trenches not exc. 1.5 metre wide and not exc. 1.50 mtr depth for laying of underground cable, erection of poles etc. and getting out in soft/loose soil including separating serviceable bricks for re-use at site obtained during excavation complete all as specified and directed. |
| 9 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 10 | Removal of surplus soil not exc 50mtr distance and depositing where complete all as specified and directed. |
| 11 | M&L for dry screened river bed sand cushioning 8cm before laying the cable and 15cm after laying the cable and further hand punned to form a uniform complete all as specified and directed. |
| 12 | M&L for laying bricks, sub class'B' for protection of cable, in trenches, laid in dry flat across the cable with length of whole bricks complete all as specified and directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |