| 1 | Dismantling and taking out old unserviceable LT panel of any type and shape after breaking of PCC foundation/platform and taking away from exisiting location after necessary disconnection of all out going and incomming cable joints, earth strips and making the surface smooth etc. complete all as specified and directed by Engr-in-Charge. |
| 2 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1700x400x1200 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 400 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-(a) MCCB 250A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming) (b) MCB SPN 63 Amps 240 volts, 10KA, C series -13 Nos (Out going) (c) Insulated Copper Bus bar 400 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No (f) Set of indicating lamp(RYB) LED type -01 Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 011 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. |
| 3 | M&L for disconnecting all the cable connection from indoor LT Panel and servicing to Panel board of any size, opening up all cubical doors, cleaning with air blower, removing the burnt out unserviceable copper wiring kit and burn out unserviceable extended copper terminals/copper cable and replacing terminal with suitable size along with required nut bolt, washers and cleaning with air blower to serviceable parts like MCCB's, all terminals, replacement of damaged aluminium/copper lugs any discription of LT UG cable/ copper wire incomming and out going, welding of broken door with suitable hinges, replacement of defective copper wiring with suitable copper conductor with circuit indiator replacement of defective rubber beading,writing various feeder complete all as specified and as directed. |
| 4 | Material and labor for demolished the old floor and scrabing the wall surface, Removing the dust and waste material from site and making the good/smooth suface of floor/wall of LT panels Room by concreate and cement work (Hard standing and Plaster ) and applying two coat paint as per direction with white colour complete all as directed. NOTE :- (I) Contractor is advised to visit the site before quoting the rates. |
| 5 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall mounted of size 1200x300x800 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 250 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-(a) MCCB 160A, 4 pole,adjustable thermal magnetic type,415volts ,25 KA=01 No (for incoming) (b) MCB SPN 63 Amps 240 volts, 10KA, C series -04 Nos (Out going) (c) Insulated Copper Bus bar 250 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings =1 set of four(d) Voltmeter Digital 0-500 volts with integrated selector switch and PTS - 01 No(e) Ammeter Digital 0-400 Amps with integrated selector switch and CTS - 01 No (f) Set of indicating lamp(RYB) LED type -01 Note :- (i) The single phase prepaid KWh energy meter retreaved from existing LT panel must be fitted in the provisional space for prepaid meter in the new LT Panel - 04 nos (ii) Time duration for replacement of LT Panel should not be more than 4 Hours. (iii) All out going feeder should be marked with quarter number. (iv) Testing certificate must be provided before installation (v) Rate quated are deemed to inclusive of all the fixture / fitting cater above. |
| 6 | M&L for fixing/ installation of Anti Corrosion with Hot Dip Galvanized (HDG) wire mesh Type cable tray of size 300 x 50 mm with 4-6 mm thick dia including all connecting accessories for fixing/installation in the wall, hang from the roof by using the joints plates, coupler, fast lock, fast fix splicer, strengtheng bar (SBR), corner strength Bar, Hanging Bracket, Tray holder, hanging hooks, hold down coupler, central hold down clip etc, for cable management, feataring open design, for cooling, dust, resistence and easy adaptation for low voltage/data cables, supporting diffrent load capacities with specific support spans and standered like NEMA VE 1, GB/T 33630-217, and size of mesh grid 50x100 mm complete all as specified and directed by Engr-in-charge. This work alos incluudes the following tasks which are considered part of the same project, which are as follows:- (i) The existing XLPE or PVC insulated cables will be excavated from the trench or wall , and the cable will be routed through a wire mesh cable tray, which will be properly laid and suspended from the roof or fixed to the wall. The cable will be run inside a conduit, and the conduit will be fitted into the wire mesh, all the rate of cable and conduit are included in this work. (ii) If some runing meter cable has to be added to the cable while connecting it to the LT Panel , then that will also be added in this job, the cable has to be connected properly using lugs/ cable joints etc. This cable can be of diffrent types and size of XLPE / PVC insulated copper FRLS cable etc, cable connection accessories will also be installed accordingly. NOTE :- (I) All the work mentioned above and all the rate for these above points will be considered as Runing meter for this job. (II) Contractor is advised to visit the site before quoting the rates. |
| 7 | S & F in repair factory made epoxy powder coated Load line Distribution Board VTPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specified. |
| 8 | Dismantling unserviceable burnt out MCCB by disconnecting the cable and Supply & Fix new MCCB's in the existing panel boards with new bolts, nuts,lugs& glands etc of the following capacities copmlete all as specified and directed. Note For items No. 6 to 9, MCCB make may varies due to existing LT Panel Space for MCCB fitting, Make of MCCB as per site space/existing make.(a) MCCB 100 Amps,4 pole 16KA, 440 Volts |
| 9 | All as per item No 08 but MCCB 125 Amps,4 pole 16KA, 440 Volts |
| 10 | All as per item No 08 but MCCB 160 Amps,4 pole 16KA, 440 Volts |
| 11 | All as per item No 08 but MCCB 250 Amps,4 pole 16KA, 440 Volts |
| 12 | S & F in repair MCB DP 40 to 63 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge . |
| 13 | S & F in repair MCB SP 6-32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge . |
| 14 | Maintenance of earthings of installations like cleaning of earth pits, treatment of earthing by pauring salt water, replacement of perished wire mesh, unserviceable funnel and repair works like patch works to the PCC chambers and RCC cover with cement mortar 1 : 4 all as directed. |
| 15 | Material and labor for preparation of old painted surfaces of LT panels by scrapping with wire brush and cleaning etc. and applying synthetic enamel paint with use of spray gun of approved grey colour and writing the all details (QTR NO.) as per direction with white colour complete all as directed. |
| 16 | S &F sheet metal enclosure one way for independent mounting of 4 Pole MCCB, Including MCCB 4 Pole 250 Amps 25 KA, 415 Volts complete all as specified |
| 17 | Supply and Fixing of XLPE, insulated, armoured, heavy duty, electric cable with stranded aluminium conductors, 1100 volts grade, laid in tranches/fixing on wall/poles or passing through pipe, including connecting up with suitable glands, lugs, nuts and bolts wherever required and testing on completion, including taking down existing unserviceable cable with GI protections pipes, complete all as specified and as directed by Engineer-in-Charge of following cross sectional area :- (a) 3.5 Core x 95 Sq mm. |
| 18 | All as per item No 17 but 2 Core x 16 Sq mm. Note :- (i) The contractor will arrange all necessary materials, tools, an equipments , as well as skilled laborers, for the fixing the cable in G+5 multi storey building. (ii) If an accident occurs while a workser is on duty, the MES Department will not be held resposible. The contractor will have to bear this resposibility. (iii) Contrator is advised to visit the site before quoting the rates. |
| 19 | All as per item No 17 but 2 Core x 10 Sq mm. |
| 20 | Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. not exceeding 10 sqm on plan and not exceeding 1.5m in depth and getting out in any type of soil complete as specified and as directed. |
| 21 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soil all as specified and directed. |
| 22 | Removing excavated materials (soil) not exc. 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed. |
| 23 | Supply and Fixing of HDPE double wall corrugated pipes conforming to IS-14930 Part-II with IP Protection of IP-67 having outer dia 50 mm and inner dia of 38 mm with necessary couplers, bends etc for protection of LT cable all as specified and directed. |
| 24 | Supply, Installation, Testing & Commissioning of Maintenance Free Earthing for Rocky Soil based on 17.2mm x 2000mm long Copper Bonded Steel Electrode (Met-Chem CEET3960) with Copper Bonding Thickness of minimum 250 Microns fixed with Nut bolts incl excavation/Earth work (Earth Pit not less than 2.25 Mtrs deep below Gd level). The Electrode is surrounded by Earth Enhanced Compound Material (CPRI Tested Material) a mixture of Graphite, Sulphate, Silica, Iron Oxide, Nickel Oxide, Magnesium Oxide, Sodium Oxide, Zinc Oxide etc. Each earth should have resistance <5 Ohm. Chemical Compound Powder to be provided minimum 30Kg per site, Standard like UL 467 certified The inspection joint provide for Earthing reference incl the manhole cover with locking facility be provided. Note:- Test certificate must be provided. |
| 25 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc of size 25X4 mm thick galvanised strip with duly fixed on suitable size of porcelain/ PVC insulator complete |
| 26 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc of size 4 mm dia galvanised wire complete |
| 27 | S & F in repair 35 W High efficient LED Street light fitting with pressure die cast Aluminum housing and Street Lighting with polycarbonate cover. System level efficacy of the Luminarie is 100lm/W . The color temperature is around 6500 K with a color rendering index of 70. The luminaire is IP:65 protected with IK05 impact resistance. It has an electronic driver complaint to IEC safety standards with a power factor>.0.9, voltage variation range 150-270V, High and low protection along with a surge protection of 4 KV including provision of 25 mm dia GI light grade pipe1.2 meter length bend to shape and necessary clamps etc for fixing the light fittings on pole fixed complete as specified and directed. . |
| 28 | S & F synthetic insulating mat of size 2 mtr X 1 mtr X 19 mm for LT panel, complete as specified and as directed. |
| 29 | Supply and fix loop in /loop out box of suitable size PVC moulded terminal box with locking arrangement comprising of one 4 way conncetor all as specified and directed |
| 30 | Supply & fix LED bollard lights,10W ,single phase with decorative LED bollard lights luminaire with suitable for LED bulb and provision of twin core flexible wire,copper conductor of 0.5 Sqmm from light fitting to loop in box complete and M&L for making foundation for bollard light of size 250mmx250mmx400mm and plastering & painting the surface of foundation complete all as specified and direcetd by Engineer-in-Charge. |
| 31 | Supply & fix LED Post Top latern lights, 25W ,single phase with decorative LED post top latern lights luminaire with diffuser and painted spun aluminium deflector pre wired and provision of twin core flexible wire, copper conductor of 0.5 Sqmm from light fitting to loop in box complete all as specified and as directed. |
| 32 | M & L for replacement only single core PVC insulated copper cable of size range 10- 25 sqmm (not less than 10 sqmm) FRLS unsheathed 1100 volts with copper multi strandrad conductor for making connections from MCB DP to bas bar in LT panel with suitable size (not less than 3 mtr) with suitable Lugs, nut bolt etc complete all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |
| 33 | M & L for replacement only single core PVC insulated copper cable of size range 10- 25 sqmm (not less than 10 sqmm) FRLS unsheathed 1100 volts with copper multi strandrad conductor for making connections from MCB DP to bas bar in LT panel with suitable size (not less than 3 mtr) with suitable Lugs, nut bolt etc complete all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |