| 1 | LT PANEL -Supply, delivery and installation of fabricated cubical type compartmentalized dust and vermin proof Floor cum wall mounted L.T. distribution panel board of suitable size made of 2 mm (14 SWG) thick M.S. sheet reinforced with (40x40x6 mm) angle iron frame work with individual hinged door with locking arrangement for all compartment and providing suitable ventilation arrangement. The complete panel board shall be painted by power coating paint, colour siemens white. The interconnection should be done with suitable size tinned copper strip between BBC to all main switches and other accessories including suitable stud connectors, socketing etc as required and earthing by nut, bolt in the body complete with base channel. The lower size of the base of panel board should rest on frame work (75x40x5 mm). The control panel will have suitable cable entry from bottom through data cable gland plate to access sufficient no. of cables as per direction of E.I.C. the panel comprising with following switches.(Make: Approved make of P.W.D & Work shop Panel .) Incoming : 315A, 415V FP SFU with propet HRC fuse (open execution type) --- 1 no. Painting : Board should be properly degreased, derusted before phospheting. Alkaline Melamine Epoxy based Powder coated paint to be done with minimum thickness of 70 micron avg. Shade will be Pebble Grey, No.RAL 7032 both inside and outside. 'CENTRAL POWER RESEARCH INSTITUTE' type test report for the Panel Board for Three phase and Neutral short circuit withstand strength test on main circuit BusBars to be Furnished. |
| 2 | 415V, 315 Amp 4 nos (4x40x5mm ) copper bus-bar with necessary nos of holes and different colour insulating tape on epoxy bus support.- 01 set suitable length each having for Phase and N. Busbar material will be Electrolytic Gr Copper, 90% & above pure in nature, semi soft, tined electroplated with heat srinkable PVC sleeve. (Certificate from Mfg. with challan to be submitted). 5.6 Gr Stainless Steel Bolt to be provided for Bus Bar Connection & spring washers to be provided for Bus Bar Connection. Termination : Incoming cable termination Bus should be suitable for termination of requisite nos. of Ar/Al XLPE/PVC cables. Outgoing feeder terminals should be as per rating.System Voltage : 415V, 50Hz, RYBN. Control wiring cable size : 1.5 sqmm PVC FR Cu multistrand flexible wire with proper socketing with PVC sleeve & identification ferruling. CT Secondary wiring to be done with 2.5 sqmm PVC FR Cu multistrand flexible wire. (Mk. RR Kabel / Havell's / Polycab/KEI).Outgoing : i)250A,415V TPN Change over switch(open execution type) ii) 315A, 415V TPN SFU with propet HRC fuse (open execution type)----1no. ii) 100A, 415V TPN SFU with propet HRC fuse(open execution type)----5 nos. iii) 63A, 415V TPN SFU with propet HRC fuse(open execution type)---- 2 nos.Suitable size of cable alleys on both sides provided. |
| 3 | Digital Multifunction Meter with selector switch --- 1 no. LCD single function Meter ( Make Siemens- 7KT0311),LED type indicating lamp with colour glasses ( Red / Yellow / Blue / Green) - quantity as per required of site (for incoming indication for 3 phase ) 50 / 5A, 5 VA, Cl.1 CT Coil (Mk. AE) - 3 nos. EI Danger Board --- 1 Nos. Supplying & Fixing 6 Amp SP MCB---- 3 nos. Slide lock fuse---- 3 nos.Make: L&T,Siemens approved by EIC. Interconnection -- i. From Input Main switch to Busbars - 4 x 50mm x 5mm Cu bars covered by coloured PVC Heat shrink.ii. From Busbars to 100/125 A output Main switch - 4 x 25 mm x 5 mm Copper bars covered by coloured PVC Heat shrink.iii. From Busbars to 63 A. output Main switch - 25 sq.mm. Copper wires (1.1 KV voltage grade single core stranded 'FR' PVC insulated & unsheathed copper wire).The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC. |
| 4 | Note: Panel drawing must approved by EIC prior to start the work. Catagory and model of diffrent switches should be approved before to start the work. An Auto Cad Drawing of the panel has to approved by EIC before making of panel.Enclosure shall provide Degree of protection IP -42/43 in accordance with IS : 2147 -1962 with its latest ammendment. The Panel box will be fabricated by CPRI approved fabricator. Approval should be submitted along with the drawing. ( DG Distribution Panel) |
| 5 | LT PANEL- Supply, delivery and installation of fabricated cubical type compartmentalized dust and vermin proof Floor cum wall mounted L.T. distribution panel board of suitable size made of 2 mm (14 SWG) thick M.S. sheet reinforced with (40x40x6 mm) angle iron frame work with individual hinged door with locking arrangement for all compartment and providing suitable ventilation arrangement. The complete panel board shall be painted by power coating paint, colour siemens white. The interconnection should be done with suitable size tinned copper strip between BBC to all main switches and other accessories including suitable stud connectors, socketing etc as required and earthing by nut, bolt in the body complete with base channel. The lower size of the base of panel board should rest on frame work (75x40x5 mm). The control panel will have suitable cable entry from bottom through data cable gland plate to access sufficient no. of cables as per direction of E.I.C. the panel comprising with following switches.(Make: Approved make of P.W.D & Work shop Panel .) Incoming : 315A, 415V FP SFU with propet HRC fuse (open execution type) --- 1 no. Painting : Board should be properly degreased, derusted before phospheting. Alkaline Melamine Epoxy based Powder coated paint to be done with minimum thickness of 70 micron avg. Shade will be Pebble Grey, No.RAL 7032 both inside and outside.. 'CENTRAL POWER RESEARCH INSTITUTE' type test report for the Panel Board for Three phase and Neutral short circuit withstand strength test on main circuit BusBars of , to be Furnished. |
| 6 | 415V, 315 Amp 4 nos (4x40x5mm ) copper bus-bar with necessary nos of holes and different colour insulating tape on epoxy bus support.- 01 set suitable length each having for Phase and N. Busbar material will be Electrolytic Gr Copper, 90% & above pure in nature, semi soft, tined electroplated with heat srinkable PVC sleeve. (Certificate from Mfg. with challan to be submitted). 5.6 Gr Stainless Steel Bolt to be provided for Bus Bar Connection & spring washers to be provided for Bus Bar Connection. Termination : Incoming cable termination Bus should be suitable for termination of requisite nos. of Ar/Al XLPE/PVC cables. Outgoing feeder terminals should be as per rating.System Voltage : 415V, 50Hz, RYBN. Control wiring cable size : 1.5 sqmm PVC FR Cu multistrand flexible wire with proper socketing with PVC sleeve & identification ferruling. CT Secondary wiring to be done with 2.5 sqmm PVC FR Cu multistrand flexible wire. (Mk. RR Kabel / Havell's / Polycab/KEI).Outgoing : i) 250A, 415V TPN SFU with propet HRC fuse(open execution type)----2 nos. ii) 160A, 415V TPN SFU with propet HRC fuse(open execution type)---- 2 nos.Suitable size of cable alleys on both sides provided. |
| 7 | Digital Multifunction Meter with selector switch --- 1 no. LCD single function Meter ( Make Siemens- 7KT0311), LED type indicating lamp with colour glasses ( Red / Yellow / Blue / Green) - quantity as per required of site (for incoming indication for 3 phase ) 50 / 5A, 5 VA, Cl.1 CT Coil (Mk. AE) - 3 nos. EI Danger Board --- 1 Nos. Supplying & Fixing 6 Amp SP MCB---- 3 nos. Slide lock fuse---- 3 nos.Make: L&T,Siemens approved by EIC. Interconnection -- i. From Input Main switch to Busbars - 4 x 50mm x 5mm Cu bars covered by coloured PVC Heat shrink.ii. From Busbars to 250A output Main switch - 4 x 40 mm x 5 mm Copper bars covered by coloured PVC Heat shrink.iii. From Busbars to 160 A. output Main switch - 25 sq.mm. Copper wires (1.1 KV voltage grade single core stranded 'FR' PVC insulated & unsheathed copper wire)The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC. |
| 8 | Note: Panel drawing must approved by EIC prior to start the work. Catagory and model of diffrent switches should be approved before to start the work. An Auto Cad Drawing of the panel has to approved by EIC before making of panel.Enclosure shall provide Degree of protection IP -42/43 in accordance with IS : 2147 -1962 with its latest ammendment. The Panel box will be fabricated by CPRI approved fabricator. Approval should be submitted along with the drawing. |
| 9 | Supply & Delivery of 1.1 KV Grade XLPE Insulated, Armoured, PVC Sheathed Aluminium Power Cable of following sizes, conforming to relevant IS specifications, approved (Make-Polycab / Finolex / RR Kabel)(i)4 Core 35 sqmm (VTPN to 3nos. ADM Residence) |
| 10 | 4 Core 50sqmm (DG Panel to DM Residence) |
| 11 | Laying of cable from 4 core 35 sqmm to 50 sqmm onwall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting (DG Panel to 3nos. ADM Residence) |
| 12 | Laying only Cable upto 50 sqmm through existing RCC/Hume/ GIPipe/open masonary trench for single, 2, 3, 3½ & 4 core |
| 13 | Laying of three cables upto 35 sqmm in an underground trench in single tier formation (horizontal) the trench size : 915 mm x 760 mm average depth with brick protection on the top of each cable with 8 nos. bricks per Mtr. and 4 nos. bricks per mtr. as separator between the cables including filling the space between the bricks and cables and also the trench with shifted soil, levelling up and restoring surface duly rammed. |
| 14 | Supplying and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :(i) For 4 core upto 35 sqmm |
| 15 | (ii) For 4 core 50 sqmm |
| 16 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :(i) 4 core 35 sqmm cable |
| 17 | (ii) 4 core 50 sqmm cable |
| 18 | Straigh through Jointing of cable of different size by compound jointing kit including S&F ferrul, tapes and jointing materials (Brand approved by EIC) 3½ / 4 core 25-35 sqmm cable |
| 19 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision or earthing attachment 8 way Enclosure (607914) (Make-Legrand/ABB/Schneider) ( for raw power supply) |
| 20 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment 4 Way Enclosure (607715 )(Make Legrand/ABB/Schneider) (Normal VTPN for ADM residence) |
| 21 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.(i)) 6-32 A SP |
| 22 | (ii)6-32 A TP |
| 23 | (iii) 63 A TP |
| 24 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. 63 A FP |
| 25 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (i) 63 A |
| 26 | (ii) 125 A |
| 27 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish ( Adjacent room of panel room).On Board |
| 28 | Average run 8 mtr |
| 29 | Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc. |
| 30 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR'(Precision make) incl. necy. fittings as required.2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC |
| 31 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.(i) 2.5sqmm |
| 32 | (ii) 4 sqmm |
| 33 | Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling with HW block and ceiling plates, nipples etc. as required. |
| 34 | Supply and delivery of 230 Volt AC operated, 18 Watt, T8 LED Tube, 1200 mm length, polycarbonate body, having minimum lumen output 2100 lumens, colour temperature 6500K (Cool Day Light), nominal lifetime minimum 40,000 burning hours, suitable for direct replacement in conventional fittings, complete as required.(Make: Philips Model MAS LEDTube 1200mm 18W 865 T8 I – 2100 lm or equivalent as approved by EIC.)with 01 no 18-20watt LED fitting. |
| 35 | Supply & Fixing of 1.1 KV Grade Single Core 50 Sq.mm Annealed Tinned Copper Conductor, EPR Insulated, Elastomeric Sheathed Cable, conforming to relevant IS specifications, complete with laying, clamping, dressing, and making necessary connections as required. (Make: Polycab India Limited or equivalent as approved by EIC) |
| 36 | Supply and fixing of single phase 220 Volt AC motor starter, Direct-On-Line (DOL) type, suitable for 2 HP motor, complete with thermal overload relay range 9–14 Amp, contactor, start-stop push buttons, enclosure, wiring, and all necessary accessories, complete in all respect as required. (Make: Larsen & Toubro Model MU-2P DOL Starter, Cat. No. CS90319KOAO or equivalent as approved by EIC). |
| 37 | Supply and delivery of 220 Volt AC operated, 1400 mm sweep ceiling fan complete with blades, canopy, down rod, shackle, safety wire, all fixing accessories, having copper winding motor, 1 Star rated, with P2 capacitor, input power 76 Watt, suitable for single phase AC supply, complete as required.(Make: Usha Model STRIKER PWD ISI 1400 mm, 1 Star (Safety Wire & P2 Capacitor) or equivalent as approved by EIC.) |
| 38 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire |
| 39 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By ISI-Medium GI pipe |
| 40 | Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil |
| 41 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe |
| 42 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode |
| 43 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 44 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc |
| 45 | Supply & Fixing of 3 Core x 4 Sq.mm, 1.1 KV Grade, Round Copper Cable, PVC insulated and sheathed, conforming to relevant IS specifications, including laying, clamping, dressing, and making necessary end connections complete as required. (Make: Finolex Cables / Polycab India Limited / RR Kabel ) |
| 46 | Supply, Installation, Testing and Commissioning of Street Light Timer Controller Switch Panel including supply and fixing of following materials complete with wiring, connections, mounting and making the system operational:10+2 Way SPN Distribution Board – 01 No.6–32A, 4 Pole MCB – 01 No.MNX-9 Power Contactor – 01 No.Overload Relay MN2 Type (3–5 Amp) – 01 No.3 Phase Indicator Lamp(R,Y,B) – 01 SetGIC Digital Timer Clock – 01 No.Toggle Switch for Auto/Manual Operation – 01 No. |
| 47 | Supply & Fixing of 240 V, 90 W LED Street Light Fittings. (Philips-BRP033 LED90 CW SLR GR PSU/Crompton-CRP-404-90-30-SL-GL-NSG/ Jaguar). Manufacturer's warranty should be not less than five years. |
| 48 | Supply & Fixing of 240 V, 90 W LED Flood Light Fittings. (Philips-BVP282 LED120 CW FG SY5WB 100W V1 /Crompton/ Jaguar). Manufacturer's warranty should be not less than five years. |
| 49 | Supply & Fixing of 240 V, 26 W LED Gate Light Fittings. (Philips-BGP200 LED26 CW PSU GR CPC SPD /Crompton/ Jaguar- Manufacturer's warranty should be not less than five years. |
| 50 | Supply & Fixing of 240 V, 10 W LED Gardenlight Fittings. (Philips-/CromptonLBLSN-10-CDL/ Jaguar). Manufacturer's warranty should be not less than five years. |
| 51 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 40 mm dia |
| 52 | Supply and fixing of 12V, 130 AH VRLA Lead Acid Battery suitable for 125 KVA DG set, model EP130-12, including necessary connection and testing complete.(Make: Exide / Amaron / Luminous.) |
| 53 | Supply and fixing of 150A, 4 Pole Power Contactor complete with 220V AC coil, suitable for 415V AC system, model KCL54-150, make KOEL or equivalent, including necessary mounting, connections with existing wiring, testing and commissioning as required and as directed by the E.I.C |
| 54 | Supply and fixing of lube oil filter, model No. KFO-03-1-2608, suitable for KOEL DG set, make Kirloskar, including necessary fittings, replacement of old filter, complete in all respect, testing and commissioning as required and as directed by the |
| 55 | Supply and fixing of dry type replaceable element Air Filter suitable for 125 KVA KOEL make DG set having minimum air flow requirement 8760 m³/hr, including dismantling of old filter, fitting of new filter, necessary accessories, complete in all respect, testing |
| 56 | Supply and fixing of spin-on type diesel (fuel) filter suitable for 125 KVA KOEL make DG set, including dismantling of the existing filter, fitting and tightening of new filter with necessary sealing, complete in all respect, testing and commissioning as required and as directed by E.I.C |
| 57 | Supply and fixing of copper angle type battery cable terminal connector clamp clips suitable for DG battery connection, including necessary nuts, bolts, tightening and proper connection with battery cable, complete in all respect as required and as directed by the E.I.C |
| 58 | Add GST @18% On total from item no 1 to 44. |
| 59 | Add LWC @1% On total from item no 1 to 45. Please Enable Macros to View BoQ information |